ABB Installation Products R2T15J4-N2380 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10…
UPC: 075114259026
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Designed for 15KV outdoor applications
- Accommodates cable insulation diameter 1.30 - 2.10 inches
- Suitable for Concentric Neural and Jacketed Concentric Neutral Cable
- Features Copper 2-Hole Spade connector
- Compatible with #2-1250kcmil stranded/compressed (750kcmil) and compact/solid (900kcmil) conductors
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 750 to 900 kcmil |
Connection Type | 2-Hole Spade |
Current Rating | 1250kcmil |
Earthing | Products Includes Their Own Grounding System |
Material | Copper |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 1.30 - 2.10 inches |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Voltage Rating | 15kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15M4-N2380-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/Unshield Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900. - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2IT15J1-H0230
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 230 -Stranded or Compressed #1, Compact or Solid 1/0.
R2T35M4N2280
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 350/ Compact or Solid 300 .
R2T15J2-N2290
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 300 /Compact or Solid 350.
R2IT15M1N2270
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 4/0 / Compact or Solid 250.
R2IT15J1-H0310
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 1-Hole Spade #2-500kcmil, Stranded or Compressed 400, / Compact or Solid 500.
R2T15J2-N2330-B3
Ranger2 Termination, Outdoor, 15kv, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch (21mm-35mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, 500 Stranded/Compressed or 600 Compact/Solid, B3 - Cable Mounting Bracket - Stainless Steel - 1.45 inch - 1.95 inch (37-50mm)
R2IT15M1N2220
Ranger2 Termination, Indoor, 15kv, Cable Type - Tape Shield/WireShield/UniShield, Insulation Range - .64 ich - 1.12 inch (16mm-28mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid, No Cable Mounting BracketFrequently Asked Questions
What cable insulation diameters does the Ranger2 termination support?
The Ranger2 termination supports cable insulation diameters ranging from 1.30 to 2.10 inches.
What type of cable is this Ranger2 termination designed for?
This Ranger2 termination is designed for Concentric Neural and Jacketed Concentric Neutral cable types.
What conductor sizes are compatible with the copper spade connector?
The copper 2-hole spade connector is compatible with #2 AWG to 1250 kcmil conductors, including stranded/compressed 750 kcmil and compact/solid 900 kcmil.
What is the voltage rating for this ABB Ranger2 termination?
This Ranger2 termination is rated for 15KV applications.
What manufacturer produces the R2T15J4-N2380 termination?
The R2T15J4-N2380 termination is manufactured by ABB - Installation Products.
How to Install Ranger 2 Cable Termination (15kV & 28kV)
This guide provides step-by-step instructions for the installation of 15kV and 28kV Ranger 2 Cable Terminations on concentric and jacketed concentric neutral cables for indoor/outdoor applications.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (120 grit or finer, optional)
Supplies needed:
Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Terminal lug (copper or aluminum), Vinyl tape or binding wire, Connector (optional), Cable Support Bracket (optional)
- De-energize and Prepare for Safety
De-energize all apparatus before beginning installation or removal of any parts. Ensure all individual user, local, and national work rules are followed. This product should only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment. Wear appropriate personal protective equipment, including gloves.
- Verify Components and Cable Compatibility
Check the kit contents to ensure they are complete and undamaged. Verify that all components, including the cable termination and any optional connectors or lugs, are compatible with the cable and mating products. Read the entire installation instructions before starting.
- Prepare the Cable
Train the cable into its final position and cut it to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable by stripping the jacket, neutral wires, and semi-con insulation shield according to the dimensions provided in the 'Table 1' and 'Prepare Cable' diagrams, ensuring to account for the terminal lug's depth and any conductor growth during crimping. Apply a band of sealing mastic 1/4 inch (6mm) from the cable jacket end, stretching it 50% and cutting it flush without overlap. Bend the neutral wires back over the mastic and press them into the sealing mastic, securing them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second band of mastic over the neutral wires and the previously applied mastic, stretching it 50% and cutting it flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.
- Install the Lug or Connector
If using a lug that will not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer's directions. Do not crimp the last 1/4 to 3/8 inch (6-10mm) of the connector. Remove any excess oxide inhibitor and sharp crimp flashings following crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent. Do not allow the solvent to touch the semi-con insulation shield. If an abrasive must be used, apply it only to the insulation, not the semi-con insulation shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below that allowed by the kit.
- Apply Initial Moisture Seal with Silicone Tape
Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber tape provided in the kit. Wrap a band of silicone tape around the base of the terminal lug. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed two layers. If the barrel diameter is smaller than the cable primary insulation, use the tape strip to form the tape band equal to the insulation diameter.
- Apply Silicone Grease to Semi-Con Edge
Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease. This silicone grease is used to fill the step at the semi-con cut-off and does not serve as a lubricant for this product.
- Install Termination Body and Remove Core
For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination. Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is firmly butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.
- Lubricate and Fold Down Skirt
Apply a thin film of silicone lubricant to the skirt and mastic seal area. Do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.
- Complete Lug Area Moisture Seal
With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1 inch (25mm) and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Connect Neutral Wires to Ground
Twist the concentric neutral wires together and securely connect them to the system ground.
- Confirm High-K Step Dimension
Confirm that the High-K step does not exceed 1.5 inches (38mm).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.