ABB Installation Products R2T15J2-N2330-B3 Ranger2 Termination, Outdoor, 15kv, Cable Type - Concentric Neutral/Jacketed Concentric…
UPC: 075114275019
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Outdoor 15kV termination for Concentric Neutral/Jacketed Concentric Neutral cables
- Insulation Range: 0.84" - 1.38" (21mm-35mm)
- N2 Copper 2-Hole Spade Connector: #2 AWG - 1250 kcmil
- B3 Stainless Steel Cable Mounting Bracket: 1.45" - 1.95" (37-50mm)
- Manufacturer: ABB - Installation Products
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 500 to 600 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2IT15J1-N0330
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 500 Stranded/Compressed or 600 Compact/Solid
R2IT15M1N2220
Ranger2 Termination, Indoor, 15kv, Cable Type - Tape Shield/WireShield/UniShield, Insulation Range - .64 ich - 1.12 inch (16mm-28mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid, No Cable Mounting Bracket
R2IT15J1-N0270-B2
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable. Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil. Conductor Code 270 - Stranded 4/0, Solid 250. Cable Mounting Bracket - B2 -Stainless Steel, 1.10-1.50 inches (28-38mm)
R2T15J2-T0260
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .84 inch - 1.38 inch. Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0, Conductor 3/0 Stranded/Compressed or 4/0 Compact/Solid
R2T35M2H0220
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor #2 Stranded/Compressed or #1 Compact/Solid
R2IT15J1-N0300
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 350 Stranded/Compressed or 400 Compact/Solid
R2IT15M1-N0300
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T35M2N2250-B2
Outdoor, Ranger2 Termination, 35kV, Tape Shield/Wire Shield/UniShield Cable Type, Insulation Range - .84-1.38 inch (21-35mm). Connector Type Copper 2-Hole Spade #2-1250 kcmil. Conductor - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cable Mounting Bracket Material - Stainless Steel, Size 1.10-1.50 inch (28-38mm).Frequently Asked Questions
What is the maximum design voltage to ground for R2T15?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
Where can I find installation instructions for R2T15?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is the power system frequency range for R2T15?
The R2T15 termination is designed for power system frequencies ranging from 48 to 62 Hz.
What is the maximum altitude for R2T15 installation?
The R2T15 termination can be installed at a maximum altitude of 3300 feet (1005 meters).
What is the operating temperature range for the R2T15?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the voltage rating of the R2T15 termination?
The R2T15 cable termination has a voltage rating of 15 kV.
What cable sizes does the R2T15 termination support?
The R2T15 termination supports cable insulation diameters from 0.64 inches to 2.10 inches, covering #2 AWG through 1250 kcmil.
What is the power system frequency range for R2T15?
The R2T15 termination is designed for power system frequencies ranging from 48 to 62 Hz.
What cable sizes does the R2T15 termination support?
The R2T15 termination supports cable insulation diameters from 0.64 inches to 2.10 inches, covering #2 AWG through 1250 kcmil.
What is the voltage rating of the R2T15 termination?
The R2T15 cable termination has a voltage rating of 15 kV.
How to Install the 15kV Ranger 2 Cable Termination (R2T15J2)
This guide provides step-by-step instructions for installing the 15kV Ranger 2 Cable Termination (R2T15J2) on concentric and jacketed concentric neutral cables for indoor/outdoor applications.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional), Vinyl tape or binding wire
Supplies needed:
Silicone Rubber Termination (R2T15J2 kit), Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Elastimold copper or aluminum lug/connector, Silicone grease, Cable Support Bracket (optional)
- Perform Pre-Installation Checks and Safety Procedures
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Inspect the kit contents for completeness and damage. Verify all components fit properly with the cable and mating products. Read these instructions thoroughly and gather all required tools, maintaining cleanliness throughout the procedure. Confirm the cable size is within the kit's specified range.
- Prepare the Cable
Train the cable into its final position and cut it to the required length, ensuring sufficient neutral wire length for the grounding connection. Prepare the cable according to the dimensions provided in the 'Prepare Cable' section, allowing for the terminal lug depth and additional exposed conductor distance for aluminum lugs.
- Apply First Mastic Seal
Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket, 1/4 inch (6mm) from the jacket end. Position the mastic precisely as it serves as a marker for terminator placement. Cut the mastic flush, ensuring no overlap.
- Secure Neutral Wires
Bend the neutral wires back over the applied mastic and press them firmly into the mastic. Secure these wires to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire.
- Apply Second Mastic Seal and Tape
Apply a second mastic band over the neutral wires and the previously applied mastic, using 50% stretch. Cut this band flush without overlapping. Wrap two half-lapped layers of vinyl tape around the entire mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.
- Install the Lug or Connector
If using a lug that will not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug. Position the connector or lug and crimp it according to its specific directions, ensuring the last 1/4 inch to 3/8 inch of the connector remains uncrimped. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, taking care not to allow the solvent to touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, avoiding the semi-con insulation shield. Ensure the cable insulation diameter is not reduced below the kit's allowed specifications.
- Create Lug Base Moisture Seal
Wrap a band of gray silicone rubber tape (from the kit) around the base of the terminal lug to create a track-resistant moisture seal. If the barrel diameter is equal to or greater than the cable primary insulation, do not exceed two layers of tape. If the barrel diameter is smaller, use the tape strip to build up the tape band to equal the insulation diameter.
- Apply Silicone Grease to Semi-Con Edge
Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield. This grease is crucial for filling the step at the semi-con cut-off.
- Prepare Termination Core (if applicable)
For lower terminations equipped with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination body.
- Install Termination Body
Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is firmly butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.
- Lubricate and Fold Down Skirt
Apply a thin film of silicone lubricant to the skirt and the mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.
- Complete Lug Area Moisture Seal
Using the remaining gray silicone rubber tape, complete the lug area moisture seal. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Connect Neutral Wires to Ground
Twist the concentric neutral wires together and securely connect them to the system ground.
- Verify High-K Step
Confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.