ABB Installation Products R2IT15J1-H0310 Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12…
UPC: 075114264754
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Supports Concentric Neutral and Jacketed Concentric Neutral cables (0.64-1.12" insulation diameter)
- Aluminum 1-Hole Spade connector compatible with #2-500kcmil conductors (stranded/compressed 400kcmil, compact/solid 500kcmil)
- Non-tracking silicone housing with superior weathering and memory for long-term performance
- Shrink-fit housing with field-removable center core for simplified installation in restricted spaces
- Compatible with stranded/compressed 400kcmil and compact/solid 500kcmil conductors
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 400 to 500 kcmil |
Connection Type | 1-Hole Spade |
Connection Type | Concentric Neutral and Jacketed Concentric Neutral Cable |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | 1-Hole Spade #2-500kcmil |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.64 - 1.12 inches |
Size | 0.64-1.12 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J2-N0310-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 400 /Compact or Solid 500. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15J2-N2330-B3
Ranger2 Termination, Outdoor, 15kv, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch (21mm-35mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, 500 Stranded/Compressed or 600 Compact/Solid, B3 - Cable Mounting Bracket - Stainless Steel - 1.45 inch - 1.95 inch (37-50mm)
R2IT15M1N2220
Ranger2 Termination, Indoor, 15kv, Cable Type - Tape Shield/WireShield/UniShield, Insulation Range - .64 ich - 1.12 inch (16mm-28mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid, No Cable Mounting Bracket
R2IT15J1-N0270-B2
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable. Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil. Conductor Code 270 - Stranded 4/0, Solid 250. Cable Mounting Bracket - B2 -Stainless Steel, 1.10-1.50 inches (28-38mm)
R2T15J2-T0260
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .84 inch - 1.38 inch. Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0, Conductor 3/0 Stranded/Compressed or 4/0 Compact/Solid
R2T35M2H0220
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor #2 Stranded/Compressed or #1 Compact/Solid
R2IT15J1-N0300
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 350 Stranded/Compressed or 400 Compact/Solid
R2IT15M1-N0300
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.Frequently Asked Questions
Where can I find installation instructions for R2IT15?
Installation instructions are provided with the kit, specifically IS-1134 for R2IT15J, IS-1135 for R2IT15M, and IS-1136 for R2IT15L.
What is the voltage rating of the R2IT15 termination?
The R2IT15 cable termination has a voltage rating of 15 kV.
What cable sizes are compatible with R2IT15 terminations?
R2IT15 terminations accommodate cables with insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil.
What cable types are compatible with R2IT15 terminations?
R2IT15 units accommodate popular XLP and EPR cable types and various shield constructions.
What is the minimum strike distance for R2IT15?
The minimum strike distance for the R2IT15 termination is 8.4 in (213 mm).
What is the creepage distance for R2IT15?
The creepage distance for the R2IT15 termination is 8.4 in (213 mm).
What is the operating temperature range for R2IT15?
The R2IT15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum altitude for R2IT15 installation?
The R2IT15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What power system frequency does R2IT15 support?
The R2IT15 termination supports a power system frequency range of 48 to 62 Hz.
How can the R2IT15 termination be mounted?
The R2IT15 termination can be mounted free hanging or with an optional bracket.
How to Install the 15kV Ranger 2 Cable Terminator (Indoor)
This guide provides step-by-step instructions for installing the 15kV Ranger 2 Cable Terminator for indoor applications on concentric and jacketed concentric neutral cables. It covers cable preparation, lug installation, cleaning, and termination.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (optional), Gloves
Supplies needed:
Silicone Rubber Termination, Lubricant, Terminal lug/connector, Vinyl tape, Silicone grease
- Prepare the Cable for Termination
DANGER: Ensure all apparatus is de-energized before beginning installation to prevent serious or fatal injury. Verify the cable size fits within the kit's range using the Termination Selection Chart. Train the cable into position and cut it to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable according to the provided dimensions, accounting for terminal lug depth and additional exposed conductor distance for aluminum lugs/connectors. Bend neutral wires back and secure them with vinyl tape as instructed.
- Install the Terminal Lug or Connector
If using non-Elastimold lugs that won't fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector or lug and crimp it according to the manufacturer’s directions, leaving the last 1/4” to 3/8” uncrimped. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.
- Clean Cable Insulation and Lug
Wipe the cable insulation with an approved solvent, being careful not to let the solvent touch the semi-con insulation shield. If using an abrasive, apply only to the insulation (not the semi-con shield) and use aluminum oxide abrasive, grit 120 or finer. Ensure the cable insulation diameter is not reduced below the kit's allowed range.
- Install the Silicone Rubber Termination
Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step at the semi-con cut-off. Slide the terminator body onto the cable, aligning its skirt with the edge of the cable jacket. Carefully remove the core by rotating the lead counter-clockwise while pulling. Recheck the terminator position and continue core removal. Do not push or pull on the terminator assembly during this process. Finally, twist the concentric neutral wires together and connect them securely to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.