ABB - Installation Products 69TCJS1R246PVDHNN - 69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter
ABB - Installation Products

69TCJS1R246PVDHNN

UPC: 075114235303


Documents & Media
Specification SheetManufacturer Product Website

Contact for Pricing

Overview

This ABB 69kV Transmission Cable Joint, SKU 69TCJS1R246PVDHNN, is engineered for reliable power transmission applications. It features a Shieldbreak housing type, specifically Housing Style 1, designed for secure and effective cable termination. The housing size is R, with a bore diameter of 1.930 inches, accommodating insulation ranges from 2.200 to 2.580 inches. This joint is equipped with a copper connector, suitable for conductors with a diameter ranging from 1.328 to 1.377 inches, identified by Conductor Code 46P. The UNSPSC code for this product is 39121452. This component is crucial for maintaining the integrity and performance of high-voltage transmission networks. Its precise dimensions and material specifications ensure a secure connection and effective insulation, vital for preventing electrical faults and ensuring continuous power delivery in demanding electrical infrastructure. ABB's commitment to quality in their Installation Products division is evident in the design and construction of this cable joint, providing a dependable solution for utility and industrial power systems operating at 69kV.
  • 69kV Transmission Cable Joint
  • Shieldbreak Housing Type, Style 1
  • Housing Size R, 1.930 inch Bore Diameter
  • Insulation Range: 2.200-2.580 inch
  • Copper Connector for 1.328-1.377 inch Diameter Conductors (Code 46P)

Specifications

Application
For use on Solid Dielectric Cables - providing permanent, fully-shielded, fully submersible cable joints for direct burial or vault applications
Color
Black
Conductor Range
1.328 to 1.377 in
Connection
Compression
Insulation
Yes
Material
EPDM Rubber
Number Of Conductors
2
Special Features
Each Cable Joint is produced exactly to design, producing a quality not possible with field molding equipment or tape. Electrically tested in the factory to ensure consistent quality. Molding is done in the factory, reducing on-site time - no penciling of cable installation required. Easy to learn installation procedure. Field molds, wrapping machines or pre-stretch not required, and a low-cost assembly tool is available. Extended shelf life enables instant availability of spares. Designed with optimized pre-molded stress control and heat transfer capabilities
Standard
ANSI C119.4, Shield Test IEEE 592
Temperature Rating, Maximum
194 F
Temperature Rating, Maximum
90 C
Temperature Rating, Minimum
194 F
Temperature Rating, Minimum
90 C
Type
Transmission Cable Joint - Shieldbreak
Voltage Rating
69 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Size R Bore Diameter at Jacket/Insulation Transition 1.930. Connector Type - Aluminum/No connector Requiered, Connector Code 46P - Conductor Diameter Range - 1.328-1.377 inch (33.73-34.98mm), Heatsink Size/Bore - V - 2.046 inch Diameter. Type Shield - E - Lead, Metallic Screen Continuity Kit - J - 4/0 Bonding Cable 4 foot quantity 3 without split bolts, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrink

69TCJN1RA46PVEJNB

69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Size R Bore Diameter at Jacket/Insulation Transition 1.930. Connector Type - Aluminum/No connector Requiered, Connector Code 46P - Conductor Diameter Range - 1.328-1.377 inch (33.73-34.98mm), Heatsink Size/Bore - V - 2.046 inch Diameter. Type Shield - E - Lead, Metallic Screen Continuity Kit - J - 4/0 Bonding Cable 4 foot quantity 3 without split bolts, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrink
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.

15PCJ2F1240

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.

15PCJ2J1330

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #4/Solid #3.

15PCJ2F1200

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #4/Solid #3.
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum. Connector Code 47P - Conductor Diameter Range - 1.378-1.425 inch (35.00-36.19mm), Heatsink Size 55 - Outside Diameter 3.000 inch, Heatsink Bore - M - 1.468 inch. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - A - 4/0 Bonding Cable 6 foot quantity 1 with Split Bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink standard package

69TCJS45147P55MDANB

69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum. Connector Code 47P - Conductor Diameter Range - 1.378-1.425 inch (35.00-36.19mm), Heatsink Size 55 - Outside Diameter 3.000 inch, Heatsink Bore - M - 1.468 inch. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - A - 4/0 Bonding Cable 6 foot quantity 1 with Split Bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink standard package
69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter, Heatsink Size and Bore not Required, Type Shield B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit H - 4/0 Bonding Cable 4 foot long Quantity 2 without Split Bolts, Armour Kit Not Required, Outer Jacket Restoration Kit Not Required.

69TCJS1R246PNBHNN

69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter, Heatsink Size and Bore not Required, Type Shield B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit H - 4/0 Bonding Cable 4 foot long Quantity 2 without Split Bolts, Armour Kit Not Required, Outer Jacket Restoration Kit Not Required.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.

15PCJ2F1220

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

15PCJ2F1250

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

Frequently Asked Questions

What are TCJ transmission cable joints designed for?

TCJ transmission cable joints are designed for 46 kV through 138 kV class systems on solid dielectric cables. They provide permanent, fully shielded, fully submersible cable joints for direct-burial or vault applications.

What is the BIL rating for 138 kV TCJ cable joints?

For 138 kV systems, the Basic Impulse Level (BIL) rating is 650 kV (1.2 x 50μs; 10 positive, 10 negative impulses).

Are shield break options available for TCJ cable joints?

Yes, joints may be installed as a standard shield break or non-shield break. A shield break option is specifically provided for cross bonding purposes on Style 4.

What applications are TCJ transmission cable joints suitable for?

TCJ transmission cable joints are suitable for direct-burial or vault applications, providing permanent, fully shielded, and fully submersible cable joints.

What is the minimum corona extinction voltage for 138 kV joints?

The minimum corona extinction voltage for 138 kV TCJ joints is 120 kV with 3 pC sensitivity.

What is the minimum corona extinction voltage for 69 kV joints?

The minimum corona extinction voltage for 69 kV TCJ joints is 60 kV with 3 pC sensitivity.

What is the BIL rating for 69 kV TCJ cable joints?

For 69 kV systems, the Basic Impulse Level (BIL) rating is 350 kV (1.2 x 50μs; 10 positive, 10 negative impulses).

What are the nominal and maximum system voltages?

TCJ joints are rated for 69 kV and 138 kV nominal system voltages. The corresponding maximum system voltages are 72.5 kV and 145 kV, respectively.

What is the maximum continuous conductor temperature for TCJ joints?

The maximum continuous conductor temperature for TCJ transmission cable joints is 90 °C.

What cable insulation diameters are compatible with TCJ joints?

For Style 1 (through 69 kV), insulation diameters range from 1.43 inches to 2.58 inches. For Style 4 (through 138 kV), diameters range from 2.25 inches to 3.62 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.