Overview
- 25kV voltage rating
- 200A current rating
- Jacket seal for environmental protection
- Integrated test point for diagnostics
- Bi-metal compression lug for 2/0 stranded wire
Specifications
Amperage Rating | 200 A |
Application | 200 kV, 200 Amp |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 11.47 in |
Material | Housing - EPDM-Rubber |
Special Features | 25kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Built in cable jacket seal. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point and Jacket Seal |
Voltage Rating | 28 kV |
Width | 8.2 in |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

261LR-D2250
25/28kV, Load Break,200 Amp Elbow without Test Point, No Sealing Kit. .890 inch - 1.220 inch Cable Insulation Diameter. Wire Size 2/0 Stranded/Compressed, 3/0 Solid/Compact, 67.43 mm2. Copper Compression Lug. ANSI/IEEE Standard 386. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Crimp Chart, Installation Instructions.
262LRJS-C5230
25kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, #1 Stranded Wire Size, Bi-Metal Compression Lug.
262LR-D5250-S
200 Amp, 25kV, Loadbreak Elbow with Test Point, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS Jacket Seal Included.
262LR-D5260
25kV 200 Amp, Loadbreak Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 3/0 Stranded Wire Size, Bi-Metal Compression Lug.
262LR-D5270-S
200 Amp, 25kV, Loadbreak Elbow with Test Point, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.
262LRJS-D5240
25kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 1/0 Stranded - Compressed or 2/0 Compact - Solid Wire Size, Bi-Metal Compression Lug.
262LRJS-D5250
25kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 2/0 Stranded Wire Size, Bi-Metal Compression Lug.Frequently Asked Questions
Is the elbow optimized for switching operations?
Yes, the enhanced Elastimold 200 amp loadbreak elbow is optimized for switching operations.
Does the Elastimold elbow offer an optional jacket seal?
Yes, the enhanced Elastimold 200 amp loadbreak elbow offers an optional integral jacket seal.
Is the elbow compatible with Elastimold bushings?
Yes, it features a no-stick interface when used with Elastimold bushings, which has been NEETRAC tested.
What safety features are included in the enhanced elbow?
Safety features include improved insulation for 15 kV elbows, rigid probe support, a no-stick interface, a robust stainless-steel pulling eye, and dual grounding eye positions.
What certifications does the Elastimold loadbreak elbow hold?
It has Rural Utilities Service (RUS) acceptance from the USDA, is IEEE 386 compliant, and ANSI certified.
What are the voltage ratings for the Elastimold loadbreak elbow?
The Elastimold 200 amp loadbreak elbow is designed for 15 kV and 25 kV series applications.
What safety features are included in the enhanced elbow?
Safety features include improved insulation for 15 kV elbows, rigid probe support, a no-stick interface, a robust stainless-steel pulling eye, and dual grounding eye positions.
What certifications does the Elastimold loadbreak elbow hold?
It has Rural Utilities Service (RUS) acceptance from the USDA, is IEEE 386 compliant, and ANSI certified.
What are the voltage ratings for the Elastimold loadbreak elbow?
The Elastimold 200 amp loadbreak elbow is designed for 15 kV and 25 kV series applications.
Is the elbow compatible with Elastimold bushings?
Yes, it features a no-stick interface when used with Elastimold bushings, which has been NEETRAC tested.
How to Install 261LRJS/262LRJS Loadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 261LRJS (without test point) and 262LRJS (with test point) Loadbreak Elbow Connectors. These connectors are designed to terminate UD cable with jacketed concentric neutral wires and connect to 25kV class loadbreak bushings.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp tool, Wire brush, Wire strippers, Hotstick (for operation, not installation)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), 3 Sealing Strips, Mastic strips, Vinyl tape, No. 14 AWG / 2.5mm copper wire (or equivalent), Appropriate grounding connector
- Perform Initial Checks and Safety Precautions
DANGER: All apparatus must be de-energized during installation or removal of parts. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Check contents of package for completeness and damage. Verify all components fit properly with the cable and mating products. Thread the probe into the compression lug to check for resistance; replace damaged components if resistance is encountered. Read all instructions before starting and ensure all required tools are at hand. Maintain cleanliness throughout the procedure. If a test point cap is not installed, lubricate and install it.
- Train the Cable
Train the cable to ensure sufficient slack for ease of operation. To facilitate neutral connection to the tank ground and hotstick operation, ensure an extra length of concentric neutral wires or grounding braid wire is available (24-26 inches beyond the bushing centerline). Remove the outer jacket 7-3/4 to 8 inches further back from the tape mark at the bushing centerline. Unwrap the neutral wire back past the bushing centerline. Cut the excess cable squarely at the centerline of the bushing.
- Prepare the Cable End
Wrap one strip of mastic, stretching slightly, around the cable jacket. Bend all neutral wires straight back over the mastic and along the cable, pressing them into the mastic. Wrap a second strip of mastic completely around the outer jacket, overlapping the imbedded neutral wires. Use a third strip if needed to build up the outer diameter. Cover all mastic with vinyl tape. Remove the insulation shield and insulation from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Position the lug so the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the lug and cable. Remove the insulation shield as shown in the diagram and bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants. Keep the insulation clean. Slide the elbow connector onto the cable using a back and forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. The probe must turn freely for approximately four turns before becoming snug. Tighten the probe with the wrench until the wrench bends, indicating proper torque.
- Connect the Concentric Neutral
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm) or equivalent through the grounding eye on the elbow. Twist it tightly, ensuring not to damage the eye. Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and/or rolling the seal down. Twist all neutral wires together and connect them to ground using an appropriate connector. Provide adequate slack in the wires to allow for elbow operation.
- Connect Elbow to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Do not operate by hand. Use a hotstick for connection. Ensure the connector is clean and free of contaminants. Ensure the work area is clear of obstructions to allow for firm footing and a secure grasp on the hotstick tool. Maintain positive control over the movement of the loadbreak connector before, during, and after the operating sequence. If there is any question about the proper operating position, operate the connectors de-energized.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.