Authorized ABB Distributor (Installation Products)
ABB - Installation Products 25PCJ1-K1280 - 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size kcmil Stranded-Compressed 250, Solid-Compact 300.

ABB Installation Products 25PCJ1-K1280 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…

UPC: 075114208840


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 25PCJ1-K1280 is a 25kV power cable joint designed for reliable medium-voltage cable connections in industrial and utility applications. This joint accommodates aluminum conductors with insulation diameters between 1.090 and 1.310 inches, supporting stranded-compressed sizes of 250 kcmil and solid-compact sizes of 300 kcmil. The single-piece housing simplifies installation, reducing assembly time and potential error points compared to multi-part designs. Engineered for compatibility with existing 25kV systems, this joint ensures consistent electrical performance and mechanical integrity in underground or aerial cable runs. The compressed aluminum conductor design minimizes resistance and heat generation, improving long-term reliability in high-load scenarios. Suitable for new installations or retrofits, this joint meets utility-grade standards for durability and fault tolerance. Order by SKU 25PCJ1-K1280 for direct integration into ABB-compatible systems.
  • Rated for 25kV medium-voltage applications
  • Supports aluminum conductors: 250 kcmil (stranded-compressed) and 300 kcmil (solid-compact)
  • Single-piece housing for simplified installation and reduced failure points
  • Compatible with cable insulation diameters from 1.090 to 1.310 inches
  • Designed for underground or aerial cable systems

Specifications

Application
For Direct Burial, Vault, Submersible and Other Severe Service Applications
Color
Black
Conductor Range
250 kcmil , 300 kcmil
Connection
Compression
Insulation
Yes
Material
Aluminum
Material
EPDM Rubber
Number Of Conductors
2
Series
25PCJ1
Size
14-3/8 inch long
Size
1.090 inch to 1.310 inch
Special Features
Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable
Standard
IEEE Standard 404
Type
Power Cable Joint
Voltage Rating
25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. CTN.

25PCJ1H (CTN)

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. CTN.
69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter

69TCJS1R246PVDHNN

69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.

15PCJ2F1240

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.

15PCJ2J1330

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #4/Solid #3.

15PCJ2F1200

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #4/Solid #3.
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum. Connector Code 47P - Conductor Diameter Range - 1.378-1.425 inch (35.00-36.19mm), Heatsink Size 55 - Outside Diameter 3.000 inch, Heatsink Bore - M - 1.468 inch. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - A - 4/0 Bonding Cable 6 foot quantity 1 with Split Bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink standard package

69TCJS45147P55MDANB

69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum. Connector Code 47P - Conductor Diameter Range - 1.378-1.425 inch (35.00-36.19mm), Heatsink Size 55 - Outside Diameter 3.000 inch, Heatsink Bore - M - 1.468 inch. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - A - 4/0 Bonding Cable 6 foot quantity 1 with Split Bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink standard package
69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter, Heatsink Size and Bore not Required, Type Shield B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit H - 4/0 Bonding Cable 4 foot long Quantity 2 without Split Bolts, Armour Kit Not Required, Outer Jacket Restoration Kit Not Required.

69TCJS1R246PNBHNN

69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter, Heatsink Size and Bore not Required, Type Shield B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit H - 4/0 Bonding Cable 4 foot long Quantity 2 without Split Bolts, Armour Kit Not Required, Outer Jacket Restoration Kit Not Required.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.

15PCJ2F1220

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.

Frequently Asked Questions

What conductor sizes are compatible with this joint?

The joint supports 250 kcmil stranded-compressed and 300 kcmil solid-compact aluminum conductors.

What voltage rating does this cable joint support?

This joint is rated for 25kV medium-voltage applications, suitable for power distribution systems.

What is the insulation diameter range for this joint?

The joint accommodates cable insulation diameters between 1.090 and 1.310 inches.

What type of housing does this joint use?

This joint features a single-piece housing for simplified installation and improved reliability.

Is this joint suitable for underground installations?

Yes, this joint is designed for both underground and aerial cable systems.

How to Install the 15/25/35PCJ1 Cable Joint

This guide provides step-by-step instructions for installing the 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for connecting aluminum to aluminum or aluminum to copper conductors in wire-shielded cables.

Estimated time: 2h

Tools needed:

Wire strippers, Wire-brush, Crimping tool, T&B WT3D tool (recommended for 35kV cable ties)

Supplies needed:

Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied, for grounding wires), DELTECt Cable ties TYD5135 (for 35kV only), No. 14 AWG copper wire or equivalent (if shield wires are smaller)

  1. De-energize Apparatus and Inspect Components

    Ensure all apparatus are de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts and cables. Failure to follow these instructions will result in damage to the product and serious or fatal injury.

  2. Read Instructions and Gather Tools

    Read the entire installation instructions thoroughly before beginning. Have all required tools at hand and maintain cleanliness throughout the procedure. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.

  3. Overlap and Cut Cables

    Overlap both cables and cut them to 12 inches (305mm) from the centerline of the joint. This ensures sufficient length of shield wires to be able to rejoin over the joint.

  4. Remove Cable Jacket

    Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and that of Cable 2 to 21 inches (530mm) from the joint centerline.

  5. Fold Back Shield Wires

    Carefully fold back the shield wires on both cables.

  6. Cut Cables at Centerline

    Cut both cables precisely at the joint centerline.

  7. Taper and Lubricate Cable 1 Insulation Shield

    Taper the edge of Cable 1's insulation shield at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield.

  8. Lubricate and Store Joint Housing

    Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to the shield wires for temporary storage. Tests have shown this procedure will not contaminate electrical interfaces.

  9. Prepare Cables for Splice Installation

    Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the dimensions 'X' and 'Y' provided in the document's table for your conductor size. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.

  10. Prepare and Insert Conductors into Splice

    If conductors are aluminum, wire-brush them thoroughly. Immediately insert the prepared conductors into the splice. Check the dimension against the 'Max Check Before' table in the document; if it exceeds, redo the assembly.

  11. Crimp the Splice

    Crimp the splice following the recommendations provided with the splice.

  12. Clean and Check Splice

    Wipe off all excess inhibitor where applicable. Check the distance between cable insulations against the 'Max Check After' table in the document; if it exceeds, redo the assembly.

  13. Remove Protrusions and Clean Area

    Remove any sharp protrusions or burrs that were generated when crimping the splice. Metal chips or filings must be removed from the splice and joint assembly area prior to sliding the joint housing.

  14. Clean and Lubricate Cables for Housing

    Clean the cables where indicated. Lubricate in the direction of the arrows to provide a build-up or ramp of lubricant at the edge of the insulation shield.

  15. Slide Housing into Final Position

    Slide the joint housing into its final position. Proper positioning is ensured by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.

  16. Install DELTECt Cable Ties (35kV ONLY)

    For 35kV installations ONLY: Install two DELTECt Cable ties (TYD5135) on each end of the cable entrance. Begin by installing the outer ties approximately 1/4 inch (6mm) from the edge of the splice, then install the second ties approximately 1/4 inch (6mm) from the first with an offset of the locking heads. The T&B WT3D tool (not included) is recommended to tighten and trim the ties.

  17. Remove Grounding Pin (35kV ONLY)

    For 35kV installations ONLY: Remove the yellow pin from the joint grounding eye and discard it.

  18. Retrain and Secure Shield Wires

    Retrain the shield wires and secure them to the ends of the joint as shown in the diagram.

  19. Insert Shield Wires into Grounding Eye

    Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye. Repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent.

  20. Connect Grounding Wires

    Connect the joint grounding wires and the remaining shield wires, using an appropriate user-supplied connector, as shown in the diagram.

  21. Reconstruct Cable Jacket

    Where applicable, reconstruct the cable jacket over both cables and the joint housing to complete the installation.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.