ABB Installation Products 252LR-B5220-S 15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 075114345804
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV, 200 Amp deadbreak elbow connector
- Accommodates cable insulation diameters from 0.635-0.905 inches (16.13-22.99mm)
- Bi-metal lug for conductor sizes 220 - #2 Stranded/Compressed, #1 Solid/Compact
- Includes test point for diagnostic capabilities
- Cold-shrinkable jacket seal for secure termination
Specifications
Amperage Rating | 200 A |
Application | 15/25kV, 200 Amp Deadbreak Connector |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 7.531 in |
Length | 191.2874 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, fully Submersible Molded Rubber Housing. Provision for Hot Stick Operation. Non-Corrosive, Capacitive Test Point. Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Width | 5.454 in |
Width | 138.5316 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
252LR-B5260
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 260 - 3/0 Stranded/Compressed, 4/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5270-S
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 270 - 4/0 Stranded/Compressed, 250kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter. Cold-Shrinkable Jacket Seal.
252LR-C5230
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.805-1.060 inches (20.45-26.92mm), Bi-Metal Lug, Conductor Size 230 - #1 Stranded/Compressed, 1/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5230
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 230 - #1 Stranded/Compressed, 1/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5270
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 270 - 4/0 Stranded/Compressed, 250kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-C5250
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.805-1.060 inches (20.45-26.92mm), Bi-Metal Lug, Conductor Size 250 - 2/0 Stranded/Compressed, 3/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
K675LR-K2330
15/25kV, 900 Amps, Deadbreak Elbow without Test Point. Cable Insulation Diameter K - 1.090-1.310 inch (27.689-33.274mm). Copper Compression Lug. Conductor Size 330 - Stranded/Compressed 500 kcmil, Solid/Compact 600 kcmil, mmsq 250/300.Frequently Asked Questions
What is the product's voltage rating?
The product is rated for 15/25kV voltage classes, with operating voltages of 8.3kV (phase-to-ground) for 15kV and 15.2kV (phase-to-ground) for 25kV.
What if my cable's OD is less than 0.565 inches?
For cables with an outside diameter less than 0.565 inches, a cable adapter 160CA-XX must be ordered.
Where can I find installation instructions for sealing kits?
For the 200ECS sealing kit, refer to installation instruction IS-459. For the 200ECSG3 kit, refer to IS-460.
What sealing kit is used for Jacketed Concentric Neutral Cables?
For Jacketed Concentric Neutral Cables, the sealing kit part number is 200ECS, or add suffix "-S" for cables with nominal O.D. within 0.80 in. - 1.50 in.
Is a sealing and grounding kit required for installation?
For safety purposes, a sealing and grounding kit with the deadbreak elbow is highly recommended.
Which elbow housing is compatible with the 160CA adapter?
The 160CA adapter can only be used in a 165/166LR elbow size housing.
What is the purpose of the 160CA Elbow Cable Size Adapter?
The 160CA adapter is designed for small cables with insulation outside diameters between 0.495 in. to 0.685 in.
What type of conductors are compatible with the bi-metal lug?
The bi-metal compression lug has a universal aluminum barrel suitable for both copper and aluminum conductors.
What is the impulse withstand rating?
The impulse withstand (BIL) is 95kV for the 15kV class and 125kV for the 25kV class.
Can this connector be operated with a hot stick?
Yes, the unit includes provisions for de-energized operation using standard hotstick tools.
How to Install the 252LR Deadbreak Elbow Connector
This guide provides step-by-step instructions for installing the Elastimold 252LR Deadbreak Elbow Connector, designed to terminate UD cable with concentric neutral and semi-con shielding, connecting it to a 25kV class deadbreak bushing or accessory device.
Estimated time: 1h 30m
Tools needed:
Wrench, Crimp tool, Wire brush, Hot stick, Wire strippers, Suitable sensing device (for voltage test, if performed)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Probe Contact, Lubricant (supplied), Hold-down Bail, No. 14 AWG / 2.5mm copper wire, Appropriate grounding connector, HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Perform Pre-Installation Checks and Safety Procedures
DANGER: All apparatus must be de-energized during installation or removal. Do not touch or move energized products. This product should be installed only by competent personnel trained in high voltage electrical equipment safety. Ensure all apparatus are installed and operated in accordance with user, local, and national work rules and electrical standards. Inspect all parts for damage, rating, and compatibility with mating parts. Check package contents for completeness. Verify elbow housing cable entrance size and compression lug size match the cable. Thread the probe into the compression lug to check for damage; replace if resistance is encountered. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Ensure the unit will be bailed.
- Prepare Cable for Termination
Train the UD cable as shown in the documentation to ease operation, ensuring a minimum of 20 inches (508.0mm) beyond the end of the cable pad mount transformer. Cut excess cable squarely at the center line of the bushing. Unwrap and bind concentric neutral wires 8-1/2 inches (216.0mm) back from the end of the cable. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread inhibitor and position it so the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the semi-con shield as shown and bevel the insulation end a maximum of 1/8 inch (3.2mm). Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble Elbow Connector
Clean and lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE. Keep insulation clean of dirt and grime. Slide the elbow connector onto the cable with a back and forth twisting motion. Wipe off all excess silicone lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. Tighten the probe with the supplied wrench until the wrench bends.
- Install Hold-Down Bail
Place the hold-down bail into the hold-down bracket. Compress the bail and insert it securely into the brackets.
- Connect Concentric Neutral
Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through the grounding eye on the elbow. Twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing Plug
Clean the receptacle portion of the elbow connector and the mating bushing, then lubricate with the supplied lubricant. IMPORTANT: Lubricate only if the transformer and elbow are known to be de-energized. Use a fully insulated hot stick to place the elbow onto the bushing. DO NOT OPERATE BY HAND. DO NOT SEPARATE IF ENERGIZED.
- Secure Elbow with Bail
Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt in a clockwise direction. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator. The nut should act as a stop to prevent the eyebolt from applying excessive force on the elbow. Once the nut is in its final position, it will not need to be readjusted when removing and replacing the elbow.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.