ABB Installation Products 252LR-B5260 15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 075114345835
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV, 200 Amp rated deadbreak elbow connector
- Bi-metal lug compatible with 260 - 3/0 AWG stranded/compressed and 4/0 AWG solid/compact conductors
- Cable insulation diameter range: 0.635-0.905 inches (16.13-22.99mm)
- Non-corrosive capacitive test point for safe voltage testing
- Kit includes elbow housing, probe, wrench, bail assembly, V.D. Cap, lubricant, crimp chart, and instructions
Specifications
Amperage Rating | 200 A |
Application | 15/25kV, 200 Amp Deadbreak Connector |
Color | Blue |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Deadbreak Elbow Connector |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 7.531 in |
Length | 191.2874 mm |
Material | Bi-Metal Lug, Polyethylene (assumed from description) |
Material | Bi-Metal Lug, Poly (assumed from description) |
Material | Housing - EPDM-Rubber |
Series | 252LR |
Size | 5.454 x 7.531 inches, 2.097 inch diameter |
Special Features | Fully Shielded, fully Submersible Molded Rubber Housing. Provision for Hot Stick Operation. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 5.454 in |
Width | 138.5316 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

376LR-J-5260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
252LR-B5270-S
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 270 - 4/0 Stranded/Compressed, 250kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter. Cold-Shrinkable Jacket Seal.
252LR-C5230
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.805-1.060 inches (20.45-26.92mm), Bi-Metal Lug, Conductor Size 230 - #1 Stranded/Compressed, 1/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5230
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 230 - #1 Stranded/Compressed, 1/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5270
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 270 - 4/0 Stranded/Compressed, 250kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-C5250
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.805-1.060 inches (20.45-26.92mm), Bi-Metal Lug, Conductor Size 250 - 2/0 Stranded/Compressed, 3/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
K675LR-K2330
15/25kV, 900 Amps, Deadbreak Elbow without Test Point. Cable Insulation Diameter K - 1.090-1.310 inch (27.689-33.274mm). Copper Compression Lug. Conductor Size 330 - Stranded/Compressed 500 kcmil, Solid/Compact 600 kcmil, mmsq 250/300.
162LR-B5250-SG2
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.Frequently Asked Questions
What is the purpose of the 160CA Elbow Cable Size Adapter?
The 160CA adapter is designed for small cables with an insulation outside diameter between 0.495 in. and 0.685 in.
Is a sealing and grounding kit recommended for safety?
Yes, for safety purposes, a sealing and grounding kit with the deadbreak elbow is highly recommended.
Which elbow housing is compatible with the 160CA adapter?
The 160CA adapter can only be used in a 165/166LR elbow size housing.
What is the voltage rating of the 252LR Elbow Connector?
It is a fully-rated 15/25kV, 200Amp Class dead-break connector.
What standards does the 252LR Elbow Connector meet?
The connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating for this connector?
The continuous current rating for both 15kV and 25kV voltage classes is 200 Amp.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What is the maximum operating voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV and phase-to-phase is 26.3kV.
Can the connector be operated with a hot stick?
Yes, the 252LR Elbow Connector includes provisions for de-energized operation using standard hotstick tools.
What type of conductors are compatible with the bi-metal lug?
The bi-metal compression lug with a universal aluminum barrel is suitable for both copper or aluminum conductors.
How to Install the 252LR Deadbreak Elbow Connector
This guide provides step-by-step instructions for installing the Elastimold 252LR deadbreak elbow connector on UD cable with concentric neutral and semi-con shielding, including cable preparation, assembly, and connection to a 25kV class deadbreak bushing.
Estimated time: 1h 30m
Tools needed:
Wrench, Wire brush, Crimp tool, Fully insulated hot stick, Suitable voltage sensing device
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Probe Contact, Lubricant (silicone grease), Hold-down Bail, No. 14 AWG / 2.5mm copper wire, Appropriate grounding connector, Test point cap (if not pre-installed)
- Perform Initial Checks and Ensure Safety
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all parts for damage, rating, and compatibility with mating parts. Check the package contents to ensure they are complete and undamaged. Verify the elbow housing cable entrance size and compression lug size for proper fit with the cable. Thread the probe into the compression lug by hand to check threads; if resistance is encountered, inspect for damage and replace components as needed. If the test point cap is not installed, lubricate the cap and test point, then install the cap. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Train and Prepare the Cable
Train the UD cable as shown in the diagram to ease operation, ensuring a minimum of 20 inches (508.0mm) beyond the end of the cable pad mount transformer. Cut any excess cable squarely at the centerline of the bushing. Unwrap and bind concentric neutral wires 8-1/2 inches (216.0mm) back from the end of the cable. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the semi-con shield as indicated (6-7/8 inches / 175.0mm from the lug end). Bevel the insulation end a maximum of 1/8 inch (3.2mm). Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Connector
Clean and lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE other lubricants. Slide the elbow connector onto the cable with a back and forth twisting motion. Wipe off all excess silicone lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. Tighten the probe with the supplied wrench until the wrench bends.
- Assemble Bail and Connect Neutral Wires
Place the hold-down bail in the hold-down bracket, then compress the bail and insert it into the brackets. Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through the grounding eye on the elbow and twist tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing and Secure
Clean the receptacle portion of the elbow connector and the mating bushing, and lubricate with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Use a fully insulated hot stick to place the elbow on the bushing; DO NOT OPERATE BY HAND and DO NOT SEPARATE IF ENERGIZED. Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt in a clockwise direction. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator, acting as a stop to prevent excessive force on the elbow.
- Perform Voltage Test (Post-Installation Verification)
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line with the test point assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the suitable sensing device used to determine if the cable is energized. Contamination, moisture, dirt, or using the wrong measuring equipment can provide a false “no voltage” indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the “no voltage” test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.