ABB Installation Products 168FLR1-B5220 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 075114279352
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal Fuse Voltage Rating: 8.3 kV
- Cable Insulation Diameter: 0.635 inch - 0.905 inch (16-23mm)
- Conductor Size: 2 AWG Stranded/Compressed, 1 AWG Solid/Compact (Bi-Metal)
- Fuse Test Ports: Two Capacitive Test Ports
- Housing Type: Molded, Small Housing Design
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | EPDM-Rubber |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact.
168FLR3-B5240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 1/0 AWG Stranded/Compressed, 2/0 AWG Solid/Compact.
168FLR3-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact.
168FLR3-B5220-S
8.3kV, 200 Amp, LoadBreak, Fused Elbow (Full Range Current Limiting). Large Housing. Cable Insulation .635-.905 inches, Aluminum Compression Lug, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid. With Jacket Seal
168FLR1-A0250-SG3
15kV, 200 Amp, LoadBreak, Fused Elbow (Full Range Current Limiting). Small Housing. Cable Insulation .575-.740 inches, Aluminum Compression Lug, Conductor Size 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cold-Shrinkable Seal with Copper Braid and Constant Force Spring
168FLR1-B5220-S
8.3kV, 200 Amp, LoadBreak, Fused Elbow (Full Range Current Limiting). Small Housing. Cable Insulation .635-.905 inches, Aluminum Compression Lug, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid. With Jacket Seal
168FLR1-A5230-S
8.3kv Fuse Elbow 200 Amp, Loadbreak With Sealing Kit, Cable Insulation Diameter 0.575 inch - 0.740 inch / 14.61-18.80mm, BI Metal Connector Only, #1 Stranded/Compressed or 1/0 Solid/Compact.
168FLR1-A5230
8.3kv Fused Elbow, 200 Amp, Loadbreak, No Sealing Kit, Cable Insulation Diameter 0.575 inch - 0.740 inch / 14.61-18.80mm, BI Metal Connector Only, #1 Stranded/Compressed or 1/0 Solid/Compact.Frequently Asked Questions
What is the primary application of the 168FLR Fused Elbow?
The 168FLR Fused Elbow protects light duty underground distribution systems, including sub-loops and radial taps, by replacing existing 200 Amp loadbreak tap elbows.
What is the symmetrical interrupting capability?
The symmetrical interrupting capability of the 168FLR Fused Elbow is 50,000 Amps.
What types of conductors are compatible with the crimp lugs?
Copper compression lugs are for copper conductors only. Bi-metal compression lugs are suitable for copper or aluminum conductors.
What industry standards does the Fused Elbow meet?
The Elastimold Fused Elbow meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47 standards.
Is the 168FLR Fused Elbow submersible?
Yes, the 168FLR Fused Elbow is fully sealed and submersible.
What is the current rating range of the fused elbow?
The current rating for the 168FLR Fused Elbow ranges from 3 to 80 Amps.
What is the maximum rated fuse voltage?
The maximum rated fuse voltage for this product is 10kV.
What is the nominal fuse voltage rating?
The nominal fuse voltage rating for the 168FLR Fused Elbow is 8.3kV.
What voltage class is the 168FLR Fused Elbow designed for?
The 168FLR Fused Elbow is designed for the 15kV voltage class.
What items are included in each Fused Elbow kit?
Each kit contains an elbow connector housing, a crimp connector, a probe lug, lubricant tubes, installation instructions, and a crimp chart.
How to Install the 168FLR or 274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe and proper installation of the 168FLR or 274FLR Loadbreak Fused Elbow Connector, including cable preparation, component assembly, and neutral connections. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 1h
Tools needed:
Probe Wrench, Allen Wrench (torque limiting), Wire brush, Crimp tool, Wire strippers, Cable cutting tool, Hotstick (for final connection)
Supplies needed:
Lubricant (supplied with kit), Compression Lug (supplied with kit), Fuse (supplied with kit), Hose Clamp (supplied with kit), Cable Half Housing (supplied with kit), Elbow Half Housing (supplied with kit), Probe (supplied with kit), Probe Connector (supplied with kit), UD cable (concentric neutral and extruded insulation shielding), Optional 200ECS Cold Shrink Cable Seal, No. 14 AWG / 2.5mm copper wire, Appropriate connector for grounding neutral wires, HV insulated cap(s) or connector(s) (if product supplied with shipping covers)
- De-energize Apparatus and Inspect Parts
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Failure to follow instructions will result in damage and serious or fatal injury. This product should be installed only by competent personnel trained in high voltage electrical equipment safety practices.
- Check Package Contents and Component Compatibility
Check the contents of the package to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. Check threads by threading the probe into the compression lug; if resistance is encountered, check for damage and replace the component. Read the entire installation instructions before starting and have all required tools at hand.
- Cut Excess Cable and Prepare Jacket
Using the bushing centerline as a reference, cut excess cable off at least 20 inches beyond the bushing. Slide the optional 200ECS Cold Shrink Cable Seal onto the cable if used. Remove the jacket from the excess cable length remaining AND the distance of 'A' (11-1/2 inches for FLR-1, 15-3/4 inches for FLR-3) plus 7-3/8 inches from the bushing centerline.
- Unwrap and Bind Concentric Neutral Wires
If a Cable Seal kit is used, follow its instructions. Otherwise, unwrap and fold the concentric neutral wires back over the jacket, and bind them securely.
- Squarely Cut Cable to Length 'A'
Using the bushing centerline as a reference, squarely cut off the cable at a distance of 'A', leaving 7-3/8 inches minimum of cable to terminate. Distance 'A' represents the length of the fuse body.
- Cut Cable End and Install Compression Lug
Cut 1-1/8 inches from the cable end, taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread the inhibitor. Crimp the unthreaded end of the compression lug to the conductor, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excess inhibitor from the outside of the lug and cable.
- Remove Insulation Shield and Clean Insulation
Remove the insulation shield 5-1/2 inches from the end of the lug. Bevel the insulation end 1/8 inch maximum. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Insert Cable into Cable Half Housing
Apply the supplied lubricant to the outside of the connector, cable insulation, conductive shield, and the cable half of the Fused Elbow cable entrance end. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'. This allows the fuse to be tightened before bottoming on the rubber.
- Insert and Hand-Tighten Fuse
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. HAND TIGHTEN the fuse. CAUTION: The fuse stud will fracture if over-torqued. Pull the housing up against the bottom of the tightened fuse.
- Assemble and Lock Probe Connector
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position by tightening the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Lubricate and Assemble Elbow Half to Cable Half
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other.
- Insert Probe and Tighten with Torque Wrench
Insert the probe into the probe connector. It may be necessary to push on the cable to align the probe with the fuse. Start the threads by hand, taking care not to cross-thread the probe. To tighten, use the special torque-limiting allen wrench supplied; insert the short end into the hole in the probe and tighten until the wrench bends and remains bent.
- Position and Tighten Hose Clamp
Position the hose clamp as shown in the diagram and tighten it. DO NOT OVERTIGHTEN the hose clamp.
- Connect Concentric Neutral Wires to Grounding Eyes
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eyes.
- Finish Cable Seal Installation and Connect Neutrals to Ground
Finish installing the 200ECS jacket seal if used. Twist all neutral wires, exercising care not to damage the grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Lubricate and Connect Elbow to Mating Bushing
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Operate per following instructions using a hotstick; DO NOT OPERATE BY HAND.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.