ABB Installation Products 168RLR-G-5240 15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation…
UPC: 783786630967
Contact for Pricing
Minimum Qty: 8
Multiplier: 8
*Contact for lower quantities*
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV rated, 200 Amp continuous current capacity
- Loadbreak replacement elbow connector with integrated test point
- Bi-metal compression lug for copper/aluminum conductor compatibility
- Accommodates cable insulation diameters 0.760-0.950 inch
Specifications
Amperage Rating | 200 A |
Application | Designed for connecting to and operating 15kV Class, 95kV BIL apparatus |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.760 inch to 0.950 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured insulation, insert and jacket. Provision for hot stick operation, Provision for ground wire connection. Wide cable range with minimum number of sizes. Extended Length Housing and Compression Lug - plus 10-1/2 inch (266.7mm). Non-Corrosive Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Replacement Elbow Connector with Test Point |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.0100 L |
Package Weight (Metric) | 1.8190 kg |

K655LR-H0240
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
K151SP-GAB10AX
Straight Plug, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.825 inch to 0.935 inch.
168RLR-F-5220
15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
167LRT-F5220
15kV 200 Amp, Loadbreak Bolted Elbow with Tap. Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
274RLR-H-5240
25kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
167RLR-G-5240
15kV 200 Amp, Loadbreak Replacement Elbow Connector, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Bi-Metal Contact. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
168RLR-G-5250
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
167LRT-G5230
200 Amp, 15kV, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Includes 02800X Bi-Metal Contact.Frequently Asked Questions
Does this connector include a test point?
Yes, it features an integrated test point for safe voltage verification.
What voltage rating does this elbow connector support?
This connector is rated for 15kV medium-voltage applications.
What cable insulation diameter range does this connector support?
The connector supports cable insulation diameters from 0.760 inch to 0.950 inch.
Is this connector suitable for both copper and aluminum conductors?
Yes, the bi-metal compression lug is designed for compatibility with both copper and aluminum conductors.
How to Install 167RLR/168RLR Loadbreak Replacement Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of Elastimold 167RLR and 168RLR Loadbreak Replacement Elbow Connectors, converting livefront terminations to deadfront for UD cable.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Wire brush, Crimping tool, Cable cutting tool, Cable insulation removal tool, Screwdriver, Hotstick
Supplies needed:
Replacement Elbow Connector Housing, Compression Lug, Probe, Lubricant (supplied with product), Hose Clamp, No. 14 AWG (2.5mm) Copper Wire, Appropriate Ground Connector, HV Insulated Cap(s) or Connector(s)
- Pre-Installation Checks and Safety
Before starting, ensure all apparatus is de-energized. Inspect the package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Check the probe threads by hand-threading it into the compression lug; if resistance is met, check for damage. If the product was supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. DANGER: All apparatus must be de-energized during installation. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Remove Livefront Termination
Remove the rubber cap from the existing terminator. Cut off the connector at the top of the terminator. Disconnect the ground lead from the base of the terminator. Carefully remove the terminator housing from the cable.
- Prepare the Cable for Termination
Train the cable to be straight and in-line with the bushing centerline. Measure and cut the cable to a length of 10-1/2 inches from the bushing centerline. Verify the insulation shield measures less than 6-1/2 inches; if it is greater, consult an ELASTIMOLD representative. Remove 1-3/8 inches of cable insulation from the end, ensuring the cut is square and the conductor is not nicked.
- Install the Compression Lug
Wire brush the bare aluminum conductor immediately after preparation. Install the compression lug onto the conductor, rotating it to spread the inhibitor. Position the lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart provided, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe off any excessive inhibitor from the outside of the lug and cable.
- Assemble the Elbow Housing and Probe
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; do not substitute. Keep the insulation clean and avoid introducing excess grease into the gap between the lug and insulation. Slide the elbow connector onto the cable using a back-and-forth twisting motion, then wipe off any excess grease. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Connect the Concentric Neutral and Hose Clamp
Insert one end of a separate No. 14 AWG (2.5mm) copper wire through the grounding eye on the elbow and twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack in the wires for elbow operation. Add the hose clamp as shown in the product diagram and tighten it snugly, but do not overtighten.
- Prepare for Connection to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY if the transformer and elbow are known to be de-energized. Once lubricated, the elbow is ready for connection to the bushing plug using a hotstick as per the operating instructions. Do not attempt to operate by hand. DANGER: Loadbreak connectors must be operated with a full insulated 'hotstick' type live-line tool. Consult company safe work practices for the required live-line tool length.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.