ABB Installation Products SLK 1010-60 M Flood-Seal Street and Highway Lighting Mechanical Fuse and Disconnect Kits, In-Line…
UPC: 783786752317
Documents & Media
Contact for Pricing
Minimum Qty: 50
Multiplier: 50
*Contact for lower quantities*
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Accommodates 1/0-2 AWG stranded and solid copper conductors
- 600V rated for reliable outdoor lighting circuit protection
- In-line mechanical fuse and disconnect for safe maintenance
- Flood-Seal design provides watertight protection against moisture
- Includes line/load housings, fuse clips, assembly dowel, and silicone grease
Specifications
Application | Rated 600 Volts, 60 Amps Maximum, perfect for Heavy duty applications |
Conductor Range | 1/0 to #2 STR/SOL AWG |
Connection | Mechanical |
Connection Type | Fuse and Disconnect |
Insulation | True |
Material | Aluminum |
Material | EPDM-Rubber Housing |
Mounting Type | In-Line |
Number of Conductors | 2 |
Series | SLK |
Size | 1/0-2 AWG |
Special Features | EPDM Rubber housing ensures a fully insulated, watertight and submersible connection. Safe separations - fuse or connecting link stays in load side when separated. Dual-rated and approved for a wide range of Aluminum or Copper Conductors |
Type | Breakaway Street Light Kit Fused |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 0.2500 L |
Package Weight (Metric) | 0.1130 kg |

SDK 1010 M
Flood-Seal Street and Highway Lighting Mechanical Fuse and Disconnect Kits, In-Line Variable-Range, non-fused, conductor range stranded 1/0-2 and solid 1/0-2
SLK 2
Copper Flood-Seal Street and Highway Lighting Compression Fuse Kits - In-Line, Single Housing, wire size stranded 4 and solid 2
USK 750
Aluminum Flood-Seal Mechanical Splice Two-Wire Kits, conductor range 250-750 connector length 16-1/16 inch, screws per side 2
SDT 6
Copper Flood-Seal Street and Highway Lighting Compression Non-Fused Kits - In-Line, Twin Housing, wire size stranded 8-6 and solid 6-4
SDK 6-2
Copper Flood-Seal Street and Highway Lighting Compression Non -Fused Kits - In-Line, Single Housing, No. 6 side wire size stranded 14-10 and solid 14-8, No. 2 side wire size stranded #4 and solid #2
SDK 6
Copper Flood-Seal Street and Highway Lighting Compression Non-Fused Kits - In-Line, Single Housing, wire size stranded 14-10 and solid 14-8
SLK 22 M
Flood-Seal Street and Highway Lighting Mechanical Fuse and Disconnect Kits, In-Line Variable-Range, fused, conductor range stranded 2-14, and solid 2-14, Designed for 30 Amp Maximum Fuse.
SLT 2
Copper Flood-Seal Street and Highway Lighting Compression Fuse Kits - In-Line, Twin Housing, wire size stranded 2How to Install the SLK 1010-60 M Flood-Seal Street Light Fuse Kit
This guide provides step-by-step instructions for installing the SLK 1010-60 M Flood-Seal Street Light Fuse Kit, including cable preparation, assembly, and fuse insertion for a watertight electrical connection.
Estimated time: 30m
Tools needed:
Wire strippers, Torque screwdriver
Supplies needed:
60 Amp 13/32" cartridge fuse (max. 600 Volt, non-glass body), Silicone grease
- Ensure Safety and Prepare Components
Before starting, identify the line-side and load-side wires. De-energize all associated wires and the working area to prevent electric shock. Match the housing body parts (line-end and load-end assemblies) to their respective wires. Ensure you have a 60 Amp 13/32" cartridge fuse (max. 600 Volt, non-glass body) ready for the load-end.
- Prepare the Line-End Cable and Housing
Strip 3/4 inch of insulation from the line-end cable conductor. Wipe the cable clean and pencil the end of the insulation for easier installation. Apply silicone grease to the end of the cable and to the cut opening of the line-end housing. Select the correct cut-off ring on the line-end housing for your cable size and cut off the end housing at the arrow tip. Insert the cable into the line-end housing until it extends 2 to 3 inches beyond the housing. Insert the cable into the line-end assembly and torque the set screw to 25 in-lbs.
- Prepare the Load-End Cable and Housing
Repeat the cable preparation steps for the load-end cable: Strip 3/4 inch of insulation from the conductor. Clean the cable and pencil the insulation end. Apply silicone grease to the cable end and the cut opening of the load-end housing. Select the correct cut-off ring on the load-end housing for your cable size and cut off the end housing at the arrow tip. Insert the cable into the load-end housing until it extends 2 to 3 inches beyond the housing. Insert the cable into the load-end assembly and torque the set screw to 25 in-lbs.
- Insert Fuse and Grease Load-End
Insert the appropriate 60 Amp 13/32 inch (max. 600 Volt) cartridge fuse into the load-end assembly. DO NOT use a glass body fuse. Apply silicone grease to the sealing area of the load-end assembly. DO NOT grease the sealing rings on the line-end assembly.
- Complete Final Assembly
Mate one of the Flood-Seal rockets to the prepared line-end assembly for a watertight seal. Mate the second Flood-Seal rocket to the prepared load-end assembly for a watertight seal. Finally, mate the line-end and load-end housings together to make the electrical connection.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.