ABB - Installation Products R2T35M2-T0230-B3 - Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)

ABB Installation Products R2T35M2-T0230-B3 Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38…

UPC: 783786832361


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 35kV Outdoor Termination (SKU: R2T35M2-T0230-B3) is a high-reliability cable termination system designed for 35kV outdoor applications. This termination leverages shrink-fit technology and Elastimold’s pull-down jacket seal to deliver a field-proven solution with minimal model variation. The system accommodates cable insulation diameters from 0.84 to 1.38 inches (21.3 to 35.1 mm), covering a broad range of conductor sizes from #2 AWG to 1250 kcmil. It supports tape shield, wire shield, and unshielded cable constructions, including popular XLP and EPR insulation types. The termination features a non-tracking silicone housing with superior weathering resistance and memory, ensuring long-term performance in harsh outdoor environments. The eight-shed design provides optimized creepage and strike distances (minimum 16.8 inches / 427 mm), meeting critical electrical insulation requirements. Field-removable center cores simplify installation, while pull-down tabs enable quick jacket seal deployment. The system is engineered for restricted spaces and free-hanging applications, offering installation flexibility in utility and industrial power distribution networks. Conductor compatibility spans aluminum and copper, with support for stranded or compressed #1/0 AWG and solid #1/0 AWG. Copper wire leads range from #2 to #4/0 AWG. The included stainless steel mounting bracket (1.45–1.95 inches / 35–50mm diameter) ensures secure attachment to poles or structures. Optional connectors include copper stem, one-hole, and two-hole spade configurations, while insulating silicone sleeves are available for enhanced creepage or wildlife protection. Key electrical ratings include a maximum design voltage to ground of 22kV, coronal extinction voltage ≤3pC at 30kV, and a lightning impulse withstand of 200kV crest. The termination meets 10-second wet withstand of 80kV (60Hz), 1-minute dry withstand of 90kV (60Hz), 5-hour dry withstand of 75kV (60Hz), and 15-minute DC withstand of 140kV. This termination is ideal for utility substations, renewable energy installations, and industrial power distribution systems requiring dependable 35kV outdoor terminations.
  • 35kV outdoor termination for tape shield, wire shield, and unshielded cables
  • Accommodates 0.84–1.38" (21.3–35.1mm) insulation diameter; #2 AWG to 1250 kcmil conductors
  • Non-tracking silicone housing with 8 sheds for superior creepage/strike distances
  • Universal aluminum barrel supports aluminum or copper conductors (#2–#4/0 AWG wire leads)
  • Includes stainless steel mounting bracket (1.45–1.95" / 35–50mm diameter)

Specifications

Application
Cable Termination, Outdoor Application, 35kV
Cable Type
Copper Tape Shielded Wire
Color
Gray
Conductor Size
#1 STR AWG , #1 COMPR AWG , 1/0 SOL AWG , 1/0 COMPT AWG
Earthing
Products Includes Their Own Grounding System
Mounting
Product Need to have Cable Holder (not included)
Number Of Terminals
(1) Single Phase
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
35 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed #1 /Compact or Solid 1/0

R2T35J2-N0230

Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed #1 /Compact or Solid 1/0
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500/ Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)

R2T15J4-N0330-B2

Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500/ Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 through 1250 kcmil. Conductor Code 330 - 500 kcmil Stranded/Compressed or 600 kcmil Compact/Solid.

R2T35J4-N0330

Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 through 1250 kcmil. Conductor Code 330 - 500 kcmil Stranded/Compressed or 600 kcmil Compact/Solid.
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 400 /Compact or Solid 500. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

R2T15J2-N0310-B3

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 400 /Compact or Solid 500. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
Ranger2 Termination, Outdoor, 25/28kV, Cable Type - Tape Shield/Wire Shield/UniSheild, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Universal Aluminum Barrel for Aluminum or Copper with Copper Wire Lead #2-4/0. Conductor Code 240 - Stranded/Compressed 1/0 or Compact/Solid 2/0. Cable Mounting Bracket Size .80-1.25 inch (20-32mm), Bracket Material - Stainless Steel

R2T28M2T0240-B1

Ranger2 Termination, Outdoor, 25/28kV, Cable Type - Tape Shield/Wire Shield/UniSheild, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Universal Aluminum Barrel for Aluminum or Copper with Copper Wire Lead #2-4/0. Conductor Code 240 - Stranded/Compressed 1/0 or Compact/Solid 2/0. Cable Mounting Bracket Size .80-1.25 inch (20-32mm), Bracket Material - Stainless Steel
Ranger2 Termination, Outdoor, 25/28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral Cable, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Universal Aluminum Barrel for Aluminum or Copper with Copper Wire Lead #2-4/0. Conductor Code 240 - Stranded/Compressed 1/0 or Compact/Solid 2/0. Cable Mounting Bracket Size .80-1.25 inch (20-32mm), Bracket Material - Stainless Steel

R2T28J2T0240-B1

Ranger2 Termination, Outdoor, 25/28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral Cable, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Universal Aluminum Barrel for Aluminum or Copper with Copper Wire Lead #2-4/0. Conductor Code 240 - Stranded/Compressed 1/0 or Compact/Solid 2/0. Cable Mounting Bracket Size .80-1.25 inch (20-32mm), Bracket Material - Stainless Steel
Outdoor, Ranger2 Termination, 15kV, Cable Type Tape Shield/Wire Shield/Unishield, Insulation Range 1.30 to 2.10 inch (33-53mm). Connector Type Copper 2-Hole Spade #2-1250 kcmil. Conductor Size 1250 Compressed/Stranded.

R2T15M4-N2440

Outdoor, Ranger2 Termination, 15kV, Cable Type Tape Shield/Wire Shield/Unishield, Insulation Range 1.30 to 2.10 inch (33-53mm). Connector Type Copper 2-Hole Spade #2-1250 kcmil. Conductor Size 1250 Compressed/Stranded.
Ranger 2 Terminator, Outdoor, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84 -1.38 inch (21-35mm) Connector Type - Copper 2-Hole Spade #2-1250 kcmil. 350 Stranded/Compressed or 400 Compact/Solid.

R2T15J2N2300

Ranger 2 Terminator, Outdoor, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84 -1.38 inch (21-35mm) Connector Type - Copper 2-Hole Spade #2-1250 kcmil. 350 Stranded/Compressed or 400 Compact/Solid.

Frequently Asked Questions

What cable sizes are compatible with R2T35?

The R2T35 termination accommodates cables with insulation diameters from 0.84 in to 2.10 in, covering #2 AWG through 1250 kcmil.

What is the maximum altitude for operation?

The maximum altitude for operation of the R2T35 is 3300 feet (1005 m).

What is the IEEE classification for outdoor use?

The R2T35 outdoor termination has an IEEE Classification of Class 1A.

What are the minimum strike and creepage distances?

The minimum strike distance is 16.8 in (427 mm), and the creepage distance is 30.0 in (762 mm).

How many sheds does the 35 kV outdoor model have?

The 35 kV outdoor model of the R2T35 termination has eight sheds.

Is a support bracket available for the R2T35?

Yes, an optional cable and support bracket is available in four sizes, ranging from 0.80 in to 2.40 in O.D.

What installation method does the R2T35 use?

The R2T35 uses shrink-fit housing with common installation procedures and cable preparation dimensions. It features a field-removable center core for easy installation.

What power system frequency does it support?

The R2T35 supports a power system frequency range of 48 to 62 Hz.

What is the operating ambient temperature range?

The R2T35 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).

What is the maximum design voltage to ground?

The maximum design voltage to ground for the R2T35 termination is 22 kV.

How to Install the R2T35M2 35kV Silicone Rubber Termination for Tape Shielded Cable

This guide provides step-by-step instructions for the safe and proper installation of the R2T35M2 35kV Ranger 2 Shrink fit Silicone Rubber Termination on tape shielded cables, including cable preparation, ground braid installation, lug connection, and termination placement.

Estimated time: 1h 30m

Tools needed:

Crimping tool, Wire strippers, Knife, Measuring tape

Supplies needed:

Silicone Rubber Termination Halves, Silicone Lubricant, Gray Silicone Rubber Electrical Tape, Constant Force Spring, Preformed Ground Braid, Sealing Mastic, Copper Foil Tape, Gloves, Vinyl Tape, Approved Solvent, Aluminum Oxide Abrasive (120 grit or finer), Terminal Lug/Connector (compatible with cable)

  1. Prepare the Cable and Apply Copper Foil Tape

    DANGER: All apparatus must be de-energized during installation. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Verify the cable size fits within the insulation range and cut the cable to the required length. Measure and remove the cable jacket, semi-conductive layer, and tape shield according to the specified dimensions, allowing for terminal lug growth. Secure the tape shield edge with a single wrap of the supplied copper foil tape to prevent unrolling.

  2. Install the Ground Braid Assembly

    Wrap one band of sealing mastic (using 50% stretch) around the cable jacket 1/4 inch (6mm) from the jacket end, cutting it flush without overlap. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket using vinyl tape and press the solder block firmly into the mastic. Apply a second mastic band (50% stretch) over the solder block and previous mastic, then wrap two half-lapped layers of vinyl tape around the mastic seal. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Cinch the spring tightly after wrapping the final winding and secure it with two wraps of vinyl tape. For cloth or paper semi-conductive shields, overwrap with one half-lapped layer of highly stretched semi-conductive rubber tape.

  3. Install and Clean the Terminal Lug/Connector

    Check to ensure the termination assembly fits over the selected lug. If the lug will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector/lug and crimp it according to the manufacturer’s directions, ensuring not to crimp the last 3/8 inch to 1/2 inch of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges following crimping. Wipe the cable insulation with an approved solvent, taking care not to allow the solvent to touch the semi-conductive insulation shield. If abrasive must be used, apply it only on the insulation (not the semi-con shield) using aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit allowance.

  4. Install the Lower Termination Half

    Create a track-resistant moisture seal between the termination insulator and the lug/connector using the supplied gray silicone rubber electrical tape. Wrap a band of silicone tape around the base of the terminal lug; if the barrel diameter is smaller than the cable primary insulation, use the tape strip to form the tape band equal to the insulation diameter. Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. On the lower termination with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue to remove the core, and do not push or pull on the termination assembly while removing it.

  5. Install the Upper Termination Half and Complete Sealing

    Using the second housing, carefully pull the core down to within one coil of the bottom. Slide the termination over the cable and carefully pull the core counter-clockwise, overlapping the first termination by 1-1/2 inches (40mm). Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate skirt tabs). Carefully fold down the skirt over the mastic seal. With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber electrical tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.

  6. Finalize Ground Connection and Verify

    Connect the ground braid to the system ground. Confirm that the High-K step does not exceed 1.5 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.