ABB Installation Products R2T28J2T0240-B1 Ranger2 Termination, Outdoor, 25/28kV, Cable Type - Concentric Neutral/Jacketed…
UPC: 075114324052
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Rated for 25/28kV outdoor power applications
- Accommodates Concentric Neutral/Jacketed Concentric Neutral cables
- Insulation range: 0.84-1.38 inch (21-35mm)
- Universal Aluminum Barrel for Al/Cu conductors (#2-#4/0 AWG)
- Includes stainless steel mounting bracket (20-32mm)
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 1/0 STR AWG , 1/0 COMPR AWG , 2/0 SOL AWG , 2/0 COMPT AWG |
Connection Type | Universal Aluminum Barrel for Aluminum or Copper with Copper Wire Lead #2-4/0 |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum, Copper, Stainless Steel |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Cable Mounting Bracket |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84-1.38 inch (21-35mm) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28 kV |
Voltage Rating | 25/28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10240-3
15kV, Single Piece Terminator (Class 1), Two-Hole Spade Lug. Power Cable Termination, Conductor Size - 1/0 Stranded/Compressed or 2/0 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T15M4-N2440
Outdoor, Ranger2 Termination, 15kV, Cable Type Tape Shield/Wire Shield/Unishield, Insulation Range 1.30 to 2.10 inch (33-53mm). Connector Type Copper 2-Hole Spade #2-1250 kcmil. Conductor Size 1250 Compressed/Stranded.
R2T15J2N2300
Ranger 2 Terminator, Outdoor, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84 -1.38 inch (21-35mm) Connector Type - Copper 2-Hole Spade #2-1250 kcmil. 350 Stranded/Compressed or 400 Compact/Solid.
R2T15J2-N2270
15kV, Ranger2 Cable Termination, Outdoor, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84-1.38 inch (21-35mm), Connector Type - N2 - Copper 2-Hole spade #2-1250 kcmil, Conductor Code 270 - 4/0 Strandeed/Compressed or 250 Compact/Solid.
R2T15J1-H0250
15kV, Outdoor, Ranger2 Cable Termination, Cable Type - Concentric Neutral/Jacket Concentric Neutral. Insulation Range 0.64 to 1.12 iches, Connector Type H0 - Aluminum 1-Hole Spade #2-500kcmil. Conductor Size - 250 - 2/0 Stranded/Compressed or 3/0 Solid/Compact.
R2T15J2-N0210
Outdoor Ranger2 Cable Termination, 15kV, Concentric neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84-1.38 inch (21-mm), Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code 210 - #2 Compact/Solid.
R2T15J2-N2310
Outdoor Ranger2 Cable Termination, 15kV, Concentric neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code 310 - 400 Stranded/Compressed or 500 Compact/Solid.
R2T15M4-N0410-B3
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N0 - Alunimum 2-Hole Spade #2-1250 kcmil, Conductor Code 410 - Compressed 1000, Cable Mounting Bracket B3 - Material Stainless Steel - Size - 1.45 inch to 1.95 inch (37mm - 50mm)Frequently Asked Questions
What cable sizes does the R2T28 termination support?
The R2T28 termination supports cables with insulation diameters from 0.84 inches to 2.10 inches, covering #2 AWG through 1250 kcmil.
How many sheds does the R2T28 outdoor model have?
The R2T28 outdoor model has six sheds.
What is the maximum altitude for installing the R2T28?
The R2T28 can be installed at a maximum altitude of 3300 feet (1005 m).
What is the operating ambient temperature range for the R2T28?
The R2T28 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the creepage distance for the R2T28 termination?
The creepage distance for the R2T28 termination is 22.8 inches (579 mm).
What is the minimum strike distance for the R2T28 termination?
The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).
What is the Lightning Impulse Withstand Voltage (BIL) for R2T28?
The Lightning Impulse Withstand Voltage (BIL Dry 110 Withstand) for the R2T28 is 150 kV Crest.
What is the maximum design voltage to ground for the R2T28?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
What is the voltage rating of the R2T28 cable termination?
The R2T28 cable termination has a voltage rating of 25/28 kV.
What cable types are compatible with the R2T28 termination?
The R2T28 termination accommodates popular XLP and EPR cable types and various shield constructions.
How to Install the Ranger 2 Cable Termination (R2T28J2)
This guide provides step-by-step instructions for preparing the cable, installing the lug, and properly installing the 15kV & 28kV Ranger 2 Cable Termination for indoor/outdoor applications.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Crimping tool, Approved solvent applicator (e.g., clean cloth), Aluminum oxide abrasive (120 grit or finer, optional), Measuring tape or ruler
Supplies needed:
Ranger 2 Cable Termination kit (termination, lubricant, silicone tape, mastic, gloves), Terminal lug or connector, Approved solvent, Vinyl tape or binding wire
- Prepare Cable for Termination
DANGER: Ensure all apparatus is de-energized. This product must be installed by competent personnel trained in high voltage safety practices. Check cable size against the kit range. Train and cut the cable to the required length, allowing sufficient neutral wire for grounding. Prepare the cable by stripping the jacket, semi-con, and insulation according to the specified dimensions, allowing for terminal lug depth. Wrap one band of sealing mastic 1/4 inch (6mm) from the jacket end. Bend neutral wires back, press into mastic, and secure 4-6 inches (100-150mm) from the cut edge with vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic. Wrap two half-lapped layers of vinyl tape over the mastic seals, maintaining the 1/4 inch (6mm) dimension.
- Install Terminal Lug or Connector
Select an appropriate copper or aluminum terminal lug or connector. If using a lug that won't fit through the termination core, slide the termination onto the cable before installing the lug (do not remove the core yet). Position the lug/connector and crimp it according to manufacturer directions, ensuring the last 1/4 to 3/8 inch (6-10mm) of the connector is not crimped. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, being careful not to let the solvent touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (120 grit or finer) on the insulation, not the semi-con shield. Ensure the cable insulation diameter is not reduced below the kit's allowed range.
- Install the Termination Body
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape around the base of the terminal lug. Adjust tape layers if the barrel diameter differs from the cable primary insulation. Liberally coat the edge of the semi-con insulation shield with silicone grease to fill the step at the cut-off. For terminations with a fold-down skirt, pull the loose end of the removable core through the top until it's flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, ensuring the termination body, not the core, butts against the mastic seal. Do not push or pull the assembly during core removal.
- Complete Termination Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, avoiding the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch (25mm) and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches (38mm).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.