ABB Installation Products R2T15J2-N0210 Outdoor Ranger2 Cable Termination, 15kV, Concentric neutral/Jacketed Concentric Neutral…
UPC: 075114333337
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage rating with 9.5 kV max design voltage to ground
- Supports #2 AWG to 1250 kcmil conductors with 0.84–1.38" insulation
- Aluminum 2-hole spade connector for secure, low-resistance terminations
- Non-tracking silicone housing with four sheds for superior creepage and strike distances
- Shrink-fit housing with field-removable center core for easy installation
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | #2 SOL AWG , #2 COMPT AWG |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT1-0210-4-PB1(1)
15kV, Single Piece Terminator (Class 1), includes Universal Aluminum Rod Contact as standard, Power Cable Termination, Conductor Size - #2 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches. Positioning Bracket
R2T15J2-N2310
Outdoor Ranger2 Cable Termination, 15kV, Concentric neutral/Jacketed Concentric Neutral Cable Type, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code 310 - 400 Stranded/Compressed or 500 Compact/Solid.
R2T15M4-N0410-B3
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N0 - Alunimum 2-Hole Spade #2-1250 kcmil, Conductor Code 410 - Compressed 1000, Cable Mounting Bracket B3 - Material Stainless Steel - Size - 1.45 inch to 1.95 inch (37mm - 50mm)
R2T28J4-N0380-B4
25/28kV, Ranger2 Cable Termination. Outdoor. Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range 1.30-2.10 inch. Connector Type Aluminum 2 Hole Spade #2-1250kcmil. Conductor Size 750kcmil Stranded/compressed 900kcmil Solid/Compact. Stainless Steel Cable Mounting Bracket 1.80-2.40 inches
R2T15J2-N0270-B2
Outdoor, Ranger2 Termination, 15kV, Cable Type Concentric Neutral/Jacketed Concentric Neutral, Insulation Range .84 to 1.38 inch (21-35mm). Connector Type Aluminum 2-Hole Spade #2-1250 kcmil. Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. Cable Mounting Bracket 1.10-1.50 inch (28-38mm), Plated Mild Steel.
R2T15J4-N2410-B3
15kV, Outdoor, Ranger2 Termination with Mounting Bracket, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30-2.10 inch (33-53mm), Connector Type N2 - Copper 2-Hoel Spade #2-1250 kcmil. Conductor Code 410 - 1000 kcmil Stranded/Compressed. Cable Mounting Bracket Material - B3 - Stainless Steel - 1.45-1.95 inch (37-50mm).
R2T15M1H0270
15kV, Ranger2 Cable Termination. Outdoor. Cable Type - Tape Shield/Wire Sheild/Unisheild. Insulation Range .64-1.12 inch. Connector Type Aluminum 1 Hole Spade #2-500kcmil. Conductor Size 4/0 Stranded/compressed 250kcmil Solid/Compact.
R2T15M1T0220
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 220 -Stranded/Compressed #2 or Compact/Solid #1.Frequently Asked Questions
What cable sizes does the R2T15 termination support?
The R2T15 termination supports cables with insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil.
What power system frequency does it support?
The R2T15 termination supports a power system frequency range of 48 to 62 Hz.
How many sheds does the R2T15 outdoor model have?
The R2T15 outdoor model has four sheds.
What is the IEEE classification for the R2T15?
The R2T15 outdoor termination has an IEEE Classification of Class 1A.
What is the maximum altitude for operation?
The R2T15 termination has a maximum altitude range of 3300 feet (1005 m) for operation.
What is the operating ambient temperature range?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
What is the voltage rating of the R2T15 termination?
The voltage rating for the R2T15 outdoor termination is 15 kV.
What cable types are compatible with R2T15 terminations?
R2T15 terminations accommodate popular XLP and EPR cable types and various shield constructions.
Where can I find installation instructions?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
How to Install the R2T15J2-N0210 Ranger 2 Cable Termination
This guide provides step-by-step instructions for installing the R2T15J2-N0210 15kV Ranger 2 Cable Termination on concentric and jacketed concentric neutral cables for indoor/outdoor applications.
Estimated time: 1h
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, if needed), Vinyl tape or binding wire, Gloves
Supplies needed:
R2T15J2-N0210 Silicone Rubber Termination kit, Silicone Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Connector/Lug (Elastimold copper or aluminum recommended)
- Ensure Safety and Verify Components
DANGER: De-energize all apparatus before installation or removal. Install and operate in accordance with all individual user, local, and national work rules. Do not touch or move energized products. Inspect all parts for damage, rating, and compatibility with mating parts. Confirm the cable size fits within the kit's specified range as shown in the Termination Selection Chart.
- Prepare Cable for Termination
Train the cable into position and cut to the required length, ensuring sufficient neutral wire length for grounding. Prepare the cable using the dimensions provided in the instructions, accounting for terminal lug depth and additional conductor distance for aluminum lugs. Wrap one band of sealing mastic 1/4 inch (6mm) from the jacket end with 50% stretch, cutting flush. Bend neutral wires back over the mastic, press them in, and secure to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and previous mastic, cutting flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, maintaining the 1/4 inch (6mm) dimension.
- Install the Terminal Lug or Connector
If using a lug that will not fit through the termination core, clean the insulation and slide the termination onto the cable *before* installing the lug. Do not remove the core at this time. Position the connector/lug and crimp it according to its specific directions. Do not crimp the last 1/4 to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only. Do not use abrasive on the semi-con insulation shield, and be careful not to reduce the cable insulation diameter below the kit's allowed range.
- Mount the Termination Body
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, build up the tape band to match the insulation diameter. Apply a liberal coating of silicone grease over the edge of the semi-con insulation shield to fill the step at the cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top until it is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted against the mastic seal's leading edge. Do not push or pull the assembly during core removal.
- Finalize Sealing and Grounding Connections
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but avoid lubricating the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending the tape over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them securely to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.