ABB Installation Products R2T15J1-N0210 Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed…
UPC: 075114196178
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV outdoor-rated cable termination for jacketed concentric neutral cables.
- Accommodates insulation diameters from 0.64" to 1.12".
- Non-tracking silicone housing with superior memory and weathering characteristics.
- Four sheds for enhanced creepage and strike distances.
- Includes aluminum 2-hole spade connector for #2 AWG to 1250 kcmil conductors.
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | #2 SOL AWG , #2 COMPT AWG |
Connection Type | 2-Hole Spade #2-1250 kcmil |
Connection Type | 2-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Silicone, Aluminum |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Shrink-fit, Field-removable center core |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | Insulation Range: 0.64 inch - 1.12 inch, Conductor: #2-1250 kcmil |
Size | 0.64 inch - 1.12 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT1-0210-4-PB1(1)
15kV, Single Piece Terminator (Class 1), includes Universal Aluminum Rod Contact as standard, Power Cable Termination, Conductor Size - #2 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches. Positioning Bracket
R2T15J1-H0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 1-Hole Spade connector for #2 to 500 kcmil. 4/0 Stranded or 250 kcmil Solid
R2T15J1-H0240
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor 1/0 Stranded/Compressed or 2/0 Compact/Solid
R2IT15M4N0330
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 -2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15J1-H0220
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 1-Hole Spade connector for #2 to 500 kcmil. #2 Stranded to #1 Solid
R2IT15M4N0440
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 440 -Stranded or Compressed 1250 Compact or Solid N/A.
R2IT15M4-N2440
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - 1.30 inch - 2.10 inch. Copper 2-Hole Spade #2-1250 kcmil, Conductor 1250 Stranded/Compressed
R2IT15M4-N2380
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900.Frequently Asked Questions
What cable insulation diameters does this termination cover?
The R2T termination covers insulation diameters from 0.64 inches (16 mm) to 2.10 inches (53 mm).
What installation instructions are available for the R2T15?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is included in a standard R2T15 kit?
Each kit may contain a Ranger2 Housing, Silicone Lubricant, Plastic Glove, Butyl Auto Tape, and Silicon Tape Roll.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T15 is 9.5 kV.
What is the lightning impulse withstand voltage?
The lightning impulse withstand voltage (BIL Dry 110 Withstand) is 110 kV Crest.
What are the mounting options for the R2T15?
The R2T15 termination can be free hanging or mounted with an optional bracket.
What is the purpose of optional insulating silicone sleeves?
Optional insulating silicone sleeves are available when more creepage is required or when wildlife protection is needed to insulate the connectors.
What is the power system frequency range?
The power system frequency range for this termination is 48 to 62 Hz.
What is the ambient temperature range for the R2T15?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum operating altitude for this product?
The maximum operating altitude for the R2T15 termination is 3300 feet (1005 m).
How to Install Ranger 2 Cable Termination (R2T15/28J Series)
This guide provides step-by-step instructions for preparing the cable, installing the lug or connector, cleaning the cable insulation, and installing the Ranger 2 cable termination for 15kV and 28kV indoor/outdoor applications. Ensure all apparatus are de-energized before beginning.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Cable knife, Crimping tool, Measuring tape or ruler, Solvent applicator (e.g., clean cloth), Aluminum oxide abrasive (120 grit or finer, optional)
Supplies needed:
R2T15/28J Cable Termination Kit (includes Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves), Terminal lug or connector (compatible with cable and termination), Vinyl tape, Approved solvent, Silicone grease, Grounding wire and connectors
- Prepare the Cable for Termination
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits within the kit range using the Termination Selection Chart. Train the cable into position and cut to the required length, ensuring sufficient neutral wire length for grounding. Prepare the cable by removing the jacket, neutral wires, and semi-con insulation shield according to the specified dimensions (refer to Table 1 and 'Barrel Depth Plus X' diagram). Wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, stretching 50% and cutting flush without overlap. Bend the neutral wires back over the mastic and secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, stretching 50% and cutting flush. Finally, wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension.
- Install the Terminal Lug or Connector
If using a lug or connector that does not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug onto the prepared conductor and crimp it according to the manufacturer's directions, ensuring not to crimp the last 1/4 to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation thoroughly with an approved solvent, taking care not to allow the solvent to touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, avoiding the semi-con insulation shield. Be careful not to reduce the cable insulation diameter below the allowance specified by the kit.
- Install the Termination Assembly
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape (from the kit) around the base of the terminal lug. If the lug barrel diameter is smaller than the cable primary insulation, build up the tape to match the insulation diameter. Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step at the cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until it is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end, ensuring the termination body (not the core) is butted against the leading edge of the mastic seal without pushing or pulling the assembly. Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate skirt tabs). Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending the tape over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them securely to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.