ABB Installation Products R2T15J1-H0270 Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12…
UPC: 783786971411
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Designed for 15KV outdoor applications
- Suitable for Concentric Neutral and Jacketed Concentric Neutral cables
- Accommodates cable insulation diameters from 0.64 to 1.12 inches
- Includes Aluminum 1-Hole Spade connector
- Spade connector supports cable sizes #2 AWG to 500 kcmil (4/0 Stranded, 250 kcmil Solid)
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 4/0 AWG , 250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10270-3
15kV, Single Piece Terminator (Class 1), Two Hole Spade Lug. Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T15J1-H0240
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor 1/0 Stranded/Compressed or 2/0 Compact/Solid
R2IT15M4N0330
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 -2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15J1-H0220
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 1-Hole Spade connector for #2 to 500 kcmil. #2 Stranded to #1 Solid
R2IT15M4N0440
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 440 -Stranded or Compressed 1250 Compact or Solid N/A.
R2IT15M4-N2440
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - 1.30 inch - 2.10 inch. Copper 2-Hole Spade #2-1250 kcmil, Conductor 1250 Stranded/Compressed
R2IT15M4-N2380
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900.
R2IT15M4-N0410
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000.Frequently Asked Questions
What cable sizes does the R2T15 termination support?
The R2T15 termination supports cable insulation diameters from 0.64 inches to 2.10 inches, covering #2 AWG through 1250 kcmil.
What is the voltage rating of the R2T15 termination?
The R2T15 cable termination has a voltage rating of 15 kV.
What is the operating temperature range for the R2T15?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum altitude for R2T15 installation?
The R2T15 termination can be installed at a maximum altitude of 3300 feet (1005 meters).
What is the power system frequency range for R2T15?
The R2T15 termination is designed for power system frequencies ranging from 48 to 62 Hz.
Where can I find installation instructions for R2T15?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is the maximum design voltage to ground for R2T15?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
What cable types are compatible with the R2T15 units?
The R2T15 units accommodate popular XLP and EPR cable types and shield constructions.
How is the R2T15 cable termination mounted?
The R2T15 termination can be free hanging or mounted using an optional support bracket.
What is the purpose of insulating silicone sleeves?
Insulating silicone sleeves are available to provide more creepage or for wildlife protection to insulate the connectors.
How to Install the R2T15/28J Cable Termination
This guide provides detailed instructions for the installation of 15kV and 28kV Ranger 2 Cable Terminations for both indoor and outdoor applications on concentric and jacketed concentric neutral cables. Installation should only be performed by competent personnel trained in high voltage electrical equipment safety practices.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (if needed)
Supplies needed:
Silicone Rubber Termination kit (R2T15/28J series), Silicone lubricant, Grey silicone rubber tape, Sealing mastic, Gloves, Terminal lug or connector, Silicone grease, Vinyl tape or binding wire
- Verify Cable Compatibility and Initial Preparation
Verify that the cable size is compatible with the kit range as shown in the Termination Selection Chart. Train the cable into its final position and cut it to the required length, ensuring sufficient neutral wire length is available for the grounding connection. Prepare the cable according to the specified dimensions, allowing for the depth of the terminal lug and additional exposed conductor distance for aluminum lugs.
- Apply First Mastic Seal and Secure Neutral Wires
Carefully wrap one band of sealing mastic around the cable jacket 1/4" (6mm) from the jacket end, stretching it to 50% of its original length. Position the mastic precisely as it serves as a marker for the terminator, then cut it flush without overlapping. Bend the neutral wires back over the applied mastic and press them firmly into the seal. Secure these wires to the cable jacket 4-6" (100-150mm) from the cut edge using vinyl tape or binding wire.
- Apply Second Mastic Seal and Tape
Apply a second band of sealing mastic over the neutral wires and the previously applied mastic, stretching it to 50% of its original length. Cut this mastic flush, ensuring no overlap. Wrap two half-lapped layers of vinyl tape around the entire mastic seal, carefully maintaining the 1/4" (6mm) dimension from the jacket end.
- Install Terminal Lug or Connector
If using a lug that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer's directions, ensuring the last 1/4" to 3/8" of the connector is left uncrimped. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation thoroughly with an approved solvent, taking care not to allow the solvent to touch the semi-con insulation shield. If an abrasive must be used, apply it only to the insulation and use only aluminum oxide abrasive, grit 120 or finer. Be cautious not to reduce the cable insulation diameter below the kit's allowed range.
- Create Initial Moisture Seal at Lug Base
Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber tape provided in the kit. Wrap a band of silicone tape around the base of the terminal lug. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed two layers. If the barrel diameter is smaller, use the tape strip to build up the tape band to equal the insulation diameter.
- Apply Silicone Grease and Prepare Termination Core
Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease; this grease is crucial for filling the step at the semi-con cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination.
- Install Termination Body and Remove Core
Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is firmly butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.
- Lubricate and Fold Down Skirt
Apply a thin film of silicone lubricant to the skirt and the mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal to complete this part of the installation.
- Complete Lug Area Moisture Seal and Ground Neutrals
Complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1" and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and securely connect them to the system ground.
- Final Inspection
Confirm that the High-K step does not exceed 1.5 inches (38mm) to ensure proper termination performance and safety.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.