ABB Installation Products R2IT15M4-N2440 Indoor Ranger2 Cable Termination. 15kV, Cable Type - Tape Shield/Wire Shield/UniShield.…
UPC: 075114295161
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV rated for medium-voltage applications
- Supports tape shield, wire shield, or UniShield cable types
- Accommodates 1.30" to 2.10" insulation diameter range
- Copper 2-hole spade terminal compatible with #2 to 1250 kcmil
- Stranded and compressed conductor design for reliable contact
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2IT15M4N0440
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 440 -Stranded or Compressed 1250 Compact or Solid N/A.
R2IT15M4-N2380
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900.
R2IT15M4-N0410
Ranger2 Termination for 15KV indoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000.
R2T15J1-N0220-B1
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 220 -Stranded or Compressed #2 Compact or Solid #1. Cable Mounting Bracket - B1 - Stainless Steel - Size .80 inch - 1.25 inch.
R2IT15M4-N0380
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 380 -Stranded or Compressed 750 Compact or Solid 900.
R2IT15M2N0270
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 4/0 / Compact or Solid 250.
R2IT15M2-H0250
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 1-Hole Spade connector for 500 kcmil
R2IT15M2N0280
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 250 / Compact or Solid 300.Frequently Asked Questions
What is the voltage rating of this termination?
The R2IT15M4-N2440 is rated for 15kV medium-voltage applications.
What cable insulation diameter does this termination support?
The R2IT15M4-N2440 supports cable insulation diameters ranging from 1.30 inch to 2.10 inch.
What conductor sizes are compatible with this termination?
This termination is compatible with copper conductors sized #2 through 1250 kcmil.
What types of cable shields does this termination support?
The R2IT15M4-N2440 supports tape shield, wire shield, and UniShield cable configurations.
Is this termination suitable for outdoor use?
No, the R2IT15M4-N2440 is designed for indoor applications only.
How to Install the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination (R2IT15M Series)
This guide provides step-by-step instructions for the indoor installation of the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination (R2IT15M series), covering cable preparation, ground braid installation, lug connection, and termination body placement. Specific cable preparation steps are detailed for tape shielded cables.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools (e.g., cable knife, wire strippers), Crimping tool, Measuring tape or ruler, Solvent and cleaning pads, Abrasive (aluminum oxide, grit 120 or finer, if needed)
Supplies needed:
15kV Ranger 2 Shrink-Fit Silicone Rubber Termination kit (R2IT15M series), Preformed Ground Braid, Constant Force Spring, Silicone Lubricant, Copper Foil Tape, Vinyl Tape, Terminal Lug or Connector, Cable (Tape shield, Wire shield, or UniShield® type)
- Safety First: De-energize and Inspect
DANGER: De-energize all apparatus in the work area before beginning installation. Do not touch or move energized products. Inspect all kit parts for damage, proper rating, and compatibility with mating parts. Ensure this product is installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Prepare Cable (Tape Shielded Cable Example)
Verify the cable size fits within the termination's insulation range. Train and cut the cable to the required installation length. Remove the cable jacket, semi-conductive layer, and insulation to the specified dimensions (e.g., 9-1/4" (235mm) jacket removal), allowing for terminal lug depth and aluminum lug growth allowance. Secure the tape shield edge with a single wrap of the supplied copper foil tape to prevent unrolling. (Note: Cable preparation steps vary for Wire Shielded and UniShield® cables; refer to the full documentation for specific instructions for those types).
- Install Ground Braid
Carefully wrap one band of vinyl tape around the cable jacket 1/4" (6mm) from the jacket end. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over this vinyl tape marker. Secure the ground braid to the cable jacket using vinyl tape. Apply a second vinyl tape band directly over the original marker and ground braid solder block, maintaining the 1/4" (6mm) dimension. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring, wrapping the spring in the same direction as the braid. Cinch (tighten) the spring after the final winding and secure it with two wraps of vinyl tape.
- Install Terminal Lug or Connector
Check to ensure the termination assembly (with its core) fits over the selected lug or connector. If the lug will not fit, clean the insulation and slide the termination onto the cable before installing the lug; do not remove the core at this time. Position the connector or lug and crimp it according to the manufacturer’s directions, ensuring the last 3/8" to 1/2" (10-13mm) of the connector is not crimped. Remove any excess oxide inhibitor and all sharp crimp flashings or edges following crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation thoroughly with solvent-saturated pads, taking care not to allow solvent to touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, avoiding the semi-conductive shield, and ensure the cable insulation diameter is not reduced below the kit's allowed specifications.
- Install Termination Body and Ground
Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. Slide the termination body onto the cable, aligning its edge with the forward edge of the vinyl tape marker. Carefully begin to remove the core by pulling counter-clockwise. Recheck the termination position and continue removing the core, ensuring not to push or pull on the termination assembly during this process. Finally, connect the ground braid to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.