ABB Installation Products K151SR-B0230 15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included…
UPC: 783786554669
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Voltage Rating: 15/25kV (25kV max phase-to-ground, 26.3kV phase-to-phase)
- Current Rating: 200 Amp continuous, 10kA sym 10-cycle momentary
- Cable Compatibility: Insulation diameter 0.635"–0.905" (16.13–22.99 mm)
- Conductor Range: #1 AWG compressed stranded or solid 1/0 AWG (42.41 mm²)
- Features: Fully shielded, submersible, capacitively coupled test point, aluminum compression lug
Specifications
Amperage Rating | 200 A |
Application | Designed to connect a cable to another cable or apparatus |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection Type | Compression |
Current Rating | 200 A |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Material | Aluminum Compression Lug |
Size | Cable Insulation Diameter 0.635 inch to 0.905 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 2.74 in |
Width | 69.596 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656YSR-H0230
600 Amp, 15/25kV, Deadbreak, Straight Receptacle with Test Point, Cable Insulation Diameter .850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1 or Compacted Solid 1/0.
167LRT-F5240
200 Amp, 15kV, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes 02800X Bi-Metal Contact.
K151SP-B0230
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
167RLR-F-5230
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
167RLR-H-5230
15kV 200 Amp, Loadbreak Replacement Elbow Connector, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Bi-Metal Contact. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
167RLR-J-5270
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
273RLR-G-5220
25kV 200 Amp, Loadbreak Replacement Elbow Connector, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
167LRT-H-5270
15kV 200 Amp, Loadbreak Bolted Elbow with Tap. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.Frequently Asked Questions
What are the key features of the K151SR receptacle?
It is a 15/25kV, 200 Amp deadbreak straight receptacle with a fully shielded, submersible molded rubber housing and provision for ground wire connection.
What is the maximum phase-to-ground operating voltage for 25kV systems?
For 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV.
Are copper compression lugs compatible with all conductors?
Copper compression lugs are suitable for all copper conductors only.
What items are included in the K151SR kit?
Each kit contains a straight receptacle housing, a receptacle pin connector, a tube of lubricant, installation instructions, and a crimp chart.
What types of cables can the K151SR terminate?
It is designed to terminate UD cable with concentric neutral and extruded insulation shielding. It can also terminate other cable types with a proper Elastimold® cable shield adapter.
What standards does the K151SR receptacle meet?
The K151SR receptacle meets ANSI/IEEE Standard 386, Latest Revision.
When can the disconnectible feature of the K151SR be used?
The disconnectible feature can be used only when the circuit is de-energized.
What is the maximum phase-to-ground operating voltage for 15kV systems?
For 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.
What is the continuous current rating for the K151SR?
The K151SR has a continuous current rating of 200 Amps for both 15kV and 25kV voltage classes.
What cable insulation diameters are supported by the K151SR?
The K151SR accommodates cable insulation diameters from 0.575 inches through 1.220 inches.
How to Install the K151SR/K151SR Straight Receptacle
This guide provides detailed instructions for installing the K151SR/K151SR Straight Receptacle, designed to connect solid dielectric type cables to other cables or electrical apparatus. DANGER: All apparatus must be de-energized during installation. Installation should only be performed by competent personnel trained in high voltage safety.
Estimated time: 1h
Tools needed:
Wire strippers/cutting tools, Wire brush, Crimping tool, Rag, Approved solvent
Supplies needed:
Conductor Contact (male), Nylon Venting Rod, Lubricant (supplied), Inhibitor (pre-filled in crimp barrel), Elastimold bail, Copper wire (#14 AWG or equivalent), Elastimold Insulating Plug (K150DP)
- Prepare the Cable Jacket
Prepare the cable end by cutting and removing the jacket. For Jacketed Concentric Neutral cables, remove 8 inches of jacket. For Copper Tape Shield cables, remove 7 1/2 inches of jacket, then remove 6 1/2 inches of the copper tape shield from the cable end. Refer to specific grounding device instructions if applicable.
- Prepare the Conductor and Insulation
Remove 7/8 to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1 3/4 to 1 7/8 inches. Cut the conductor squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel, which contains inhibitor.
- Crimp the Socket Terminal
Crimp the socket terminal onto the bared conductor, ensuring the conductor remains fully seated. Start crimps at the crimp line imprinted on the barrel and rotate each successive crimp or indent 90 degrees. If using aluminum cable, carefully wipe excess inhibitor from the contact and cable insulation.
- Prepare the Semi-Conductive Shield and Insulation
Remove the semi-conductive shield 7 9/16 to 7 5/8 inches back from the end of the pin with a straight, smooth, squared cut, taking care not to cut or nick the insulation. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent, wiping from the cable end toward the outer jacket. Install any ECS or MA grounding device if required.
- Lubricate the Cable and Receptacle
Remove the protective cap from the straight receptacle, keeping the cable insulation and receptacle clean. Apply the supplied lubricant sparingly to the prepared cable end and to the inside of the housing. Do not substitute other lubricants, as they may be harmful to the product.
- Insert Cable into Housing
Push the cable into the housing until the base of the pin chamfer is flush with the inside face of the receptacle. If the receptacle is not to be immediately connected, replace the protective cover with an appropriate HV insulated cap or an Elastimold Insulating Plug (K150DP), as the shipping cover offers dirt protection only and is not an insulating device.
- Connect to a Mating Plug
To connect to a mating plug, first lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1 3/4 inches), ensuring the rod is not cut. Insert the plug assembly into the receptacle as far as possible, then pull out the nylon rod. Secure the electrical connection with an Elastimold bail.
- Ground the Cable
For cable grounding, if an ELASTIMOLD grounding device is not being used, connect a length of #14 AWG (or equivalent) copper wire (customer supplied) through the grounding tab and twist tightly. Connect this grounding assembly to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.