ABB Installation Products 167RLR-J-5270 200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable…
UPC: 783786626205
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp, 15kV Class loadbreak elbow connector
- Extended length housing and compression lug (+8-7/8 inches net gain)
- Fully shielded, submersible molded rubber housing
- Meets ANSI/IEEE Standard 386 with 95kV BIL impulse withstand
Specifications
Amperage Rating | 200 A |
Application | Designed for connecting to and operating 15kV Class, 95kV BIL apparatus |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection Type | Compression Lug |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Size | 0.980" - 1.180" |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured insulation, insert and jacket. Provision for hot stick operation, Provision for ground wire connection. Wide cable range with minimum number of sizes. Extended length housing and compression lug plus 10-1/2 inch (266.7mm) |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Replacement Elbow Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.2800 L |
Package Weight (Metric) | 1.9410 kg |

162LR-D5270-S
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.
273RLR-G-5220
25kV 200 Amp, Loadbreak Replacement Elbow Connector, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
167LRT-H-5270
15kV 200 Amp, Loadbreak Bolted Elbow with Tap. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
167RLR-F-5240
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
168RLR-G-5240
15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SP-GAB10AX
Straight Plug, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.825 inch to 0.935 inch.
168RLR-F-5220
15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
167LRT-F5220
15kV 200 Amp, Loadbreak Bolted Elbow with Tap. Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.Frequently Asked Questions
What is the current rating of the elbow connectors?
The elbow connectors are rated for 200 A loadbreak applications.
What voltage classes do these connectors support?
The ABB Elastimold loadbreak repair and replacement elbows are available for 15 kV and 25 kV voltage classes.
How much length does the repair elbow add?
The repair elbow features an extended housing and compression lug length that is 3 1/4 inches longer than the standard elbow.
How much length does the replacement elbow add?
The replacement elbow extends its housing and compression lug length to 8 7/8 inches over the standard elbow.
What material are the elbows constructed from?
The elbows are constructed from specially formulated, non-rigid ethylene propylene diene monomer (EPDM) rubber.
Are these elbow connectors certified?
Yes, these connectors are IEEE 386 compliant, ANSI certified, and Rural Utilities Service (RUS) accepted.
Where are Elastimold elbows manufactured?
Elastimold 200 A repair and replacement elbows are designed, molded, and tested in Albuquerque, NM, USA.
What is the test point cap catalog number?
The test point cap catalog number for elbows with a test point is 156-7.
What is the cable insulation diameter range for 167/168RLR?
For 167/168RLR, the cable insulation diameter ranges from 0.640 to 1.310 inches, depending on the specific symbol (F, G, H, J, K) in Table W4.
What is the primary purpose of these elbow connectors?
They facilitate switchgear and transformer replacement, especially live-front to dead-front conversions, by addressing varying bushing heights and insufficient cable length.
How to Install 167RLR/168RLR Loadbreak Replacement Elbow Connectors
This guide provides step-by-step instructions for installing the 167RLR and 168RLR Loadbreak Replacement Elbow Connectors, converting a livefront termination to a deadfront for UD cable. It covers cable preparation, lug installation, elbow assembly, and neutral connection.
Estimated time: 2h
Tools needed:
Cable cutting tool, Cable stripping tool, Wire brush, Crimping tool, Hotstick
Supplies needed:
Copper wire (No. 14 AWG / 2.5mm), Appropriate connector for neutral wires, HV insulated cap(s) or connector(s)
- De-energize and Remove Livefront Termination
DANGER: All apparatus must be de-energized during installation or removal of parts. Remove the rubber cap from the terminator. Cut off the connector at the top of the terminator. Disconnect the ground lead from the base of the terminator. Finally, remove the terminator housing from the cable.
- Prepare the Cable
Train the cable to be straight and in-line with the bushing centerline. Cut the cable to measure 10-1/2 inches from the bushing centerline. Remove 1-3/8 inches of cable insulation from the end of the cable, cutting squarely. DO NOT NICK THE CONDUCTOR during this process.
- Install the Compression Lug
Wire brush the bare aluminum conductor thoroughly. Immediately install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug starting at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe any excessive inhibitor from the outside of the lug and cable.
- Assemble the Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants, as they may be harmful. Keep the insulation clean of dirt and grime, and do not introduce excess grease into the gap between the lug and the insulation. Slide the elbow connector onto the cable using a back and forth twisting motion. Wipe off all excess grease. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Connect the Concentric Neutral
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through the grounding eye on the elbow. Twist it tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack in the wires for elbow operation. Add the hose clamp as shown in the documentation, tightening it snugly. Do Not overtighten.
- Connect Elbow to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Operate per the following instructions (refer to Loadmake Operation in the full document). DO NOT OPERATE BY HAND. Securely fasten a hotstick to the loadbreak connector pulling eye for connection.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.