ABB Installation Products K151SR-B0220 15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included…
UPC: 783786484102
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25 kV voltage rating for high-voltage applications
- 200 Amp current rating for substantial power handling
- Accommodates cable insulation diameters from 0.635" to 0.905"
- Aluminum compression lug for secure conductor termination
- Designed for deadbreak connections, ensuring safety
Specifications
Amperage Rating | 200 A |
Application | Designed to connect a cable to another cable or apparatus |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Width | 2.74 in |
Width | 69.596 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
K151SP-C0240
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SP-B0220
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K151SR-B0240
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SR-B2250
15/25kV 200 Amp, Deadbreak Straight Receptacle (All Copper Lug) Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151SP-B0240
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SP-A0250
Straight Plug, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151SP-B0250
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.Frequently Asked Questions
What is the maximum cable insulation diameter supported?
The receptacle supports cable insulation diameters ranging from 0.635 inches to 0.905 inches.
What conductor sizes can be terminated with this receptacle?
It accommodates AWG compressed stranded #2 or solid #1 conductors, equivalent to 33.62 mm².
Does this receptacle include bails?
No, bails are required for operation but are not included and must be ordered separately.
What is the current rating of this ABB receptacle?
The ABB K151SR-B0220 has a current rating of 200 Amps.
What is the voltage rating for this deadbreak receptacle?
This deadbreak receptacle is rated for 15/25 kV.
What type of connection is used for the conductor?
It utilizes an aluminum compression lug for conductor termination.
How to Install the K151SR Straight Receptacle
This guide provides step-by-step instructions for preparing the cable, crimping the conductor contact, and assembling the K151SR/K151SR Straight Receptacle for connection to other Elastimold products.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Rag
Supplies needed:
K151SR Straight Receptacle, Conductor Contact (male), Nylon Venting Rod, Lubricant (supplied), Crimp Chart, Approved solvent, Silicone grease, Elastimold bail, #14 AWG copper wire, Sealing material, Elastimold insulating plug (K150DP) (optional)
- Perform Initial Safety Checks and Component Verification
Before starting, ensure all apparatus is de-energized. Verify the contents of the K151SR/K151SR package are complete and undamaged, including the Straight Receptacle, Conductor Contact, Nylon Venting Rod, Lubricant, and Crimp Chart. Inspect all components for proper fit with the cable and mating products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare Cable Jacket
For jacketed concentric neutral cable, cut and remove the cable jacket 8 inches from the cable end, ensuring sufficient concentric neutral wires for grounding. For copper tape shield cable, cut and remove the cable jacket 7 1/2 inches from the cable end, then remove the copper tape shield 6 1/2 inches from the cable end. Refer to specific grounding device instructions if using an ECS or MA device.
- Prepare Cable Insulation and Conductive Shield
Remove 7/8 to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1 3/4 to 1 7/8 inches. Cut the cable squarely; do not pencil the cut. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel, which contains inhibitor.
- Crimp Conductor Contact
Crimp the socket terminal onto the bared conductor, ensuring the conductor remains fully seated in the connector. Consult the crimp chart provided with the contact for specific instructions. Begin crimping at the crimp line on the barrel and rotate each successive crimp or indent 90 degrees. If using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Remove Semi-Conductive Shield and Clean Insulation
Remove the semi-conductive shield to a point 7 9/16 to 7 5/8 inches back from the end of the pin with a straight, smooth, squared cut. Do not cut or nick the insulation. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent and a rag to remove all traces of semi-conducting residue, wiping from the cable end toward the outer jacket. If using an ECS or MA grounding device, install it now per its instructions.
- Lubricate Receptacle and Cable
Remove the protective cap from the straight receptacle, keeping the cable insulation and receptacle clean. Apply the supplied lubricant sparingly to the cable as indicated in the instructions and to the inside of the receptacle housing. Do not substitute lubricants, as others may be harmful to the product.
- Insert Cable into Receptacle
Push the prepared cable into the receptacle housing until the base of the pin chamfer is flush with the inside face of the receptacle. If the receptacle will not be immediately connected to a mating plug, replace the protective cover. Note that the shipping cover only offers protection from dirt and is not an insulating device; obtain an Elastimold insulating plug (K150DP) if an insulating device is required.
- Connect to Mating Plug (if applicable)
If connecting to a mating plug, first lubricate the nose of the plug with silicone grease. Place the nylon venting rod into the receptacle face until it bottoms (approximately 1 3/4 inches), ensuring the rod is not cut. Insert the plug assembly into the receptacle as far as possible, then pull out the nylon rod. Secure the electrical connection with an Elastimold bail.
- Ground the Cable
If an ELASTIMOLD grounding device is not being used, connect a length of #14 AWG (or equivalent) copper wire (customer supplied) through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.