ABB Installation Products K151SR-B2250 15/25kV 200 Amp, Deadbreak Straight Receptacle (All Copper Lug) Cable Insulation…
UPC: 783786487271
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating with 200 Amp capacity
- All-copper compression lug for superior conductivity
- Accommodates cable insulation diameters from 0.635" to 0.905"
- Compatible with compressed stranded conductors 2/0 AWG to solid 3/0 AWG (67.43 mm²)
- Straight configuration for simplified cable routing and installation
Specifications
Amperage Rating | 200 A |
Application | Designed to connect a cable to another cable or apparatus |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Width | 2.74 in |
Width | 69.596 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR3B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
K151SP-B0240
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SP-A0250
Straight Plug, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151SP-B0250
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
273RLR-J-5230
200 Amp, 25kV, Loadbreak Replacement Elbow Connector without Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
K151SP-B2250
15/25kV 200 Amp, Deadbreak Straight Plug Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
168ELR-6689-5210
15kV 200 Amp, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Bi-Metal Contact. Cable Insulation Diameter 0.665 inch to 0.895 inch. Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67.
755LR-L0290
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.Frequently Asked Questions
What are the voltage and current ratings?
The K151SR is rated for 15/25kV and 200 Amp continuous current.
What is the maximum operating voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV and phase-to-phase is 26.3kV.
What standards does the K151SR meet?
The K151SR meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What is the continuous current rating of the K151SR?
The continuous current rating for both 15kV and 25kV voltage classes is 200 Amp.
What items are included in the K151SR kit?
Each kit contains a straight receptacle housing, a receptacle pin connector, a tube of lubricant, installation instructions, and a crimp chart.
What cable insulation diameters are supported by K151SR?
The K151SR supports cable insulation diameters from .575 inches through 1.220 inches.
Does the K151SR require mating products for connection?
Yes, it requires an appropriate Elastimold® mating product installed on the other cable or apparatus.
What conductor sizes does the K151SR accommodate?
It accommodates conductor sizes from No. 4 solid through 4/0 stranded.
What cable types are compatible with the K151SR?
It terminates UD cable with concentric neutral and extruded insulation shielding. Other cable types can be used with a proper Elastimold® cable shield adapter.
How to Install the 151SR/K151SR Straight Receptacle
This guide provides detailed instructions for the installation, cable preparation, and connection of the Elastimold 151SR/K151SR straight receptacle, designed for 15kV or 25kV class systems.
Estimated time: 1h
Tools needed:
Wire strippers, Wire brush, Crimp tool, Rag, Approved solvent
Supplies needed:
151SR/K151SR Straight Receptacle, Conductor Contact (male), Nylon Venting Rod, Lubricant, Crimp Chart, Inhibitor (in crimp barrel), Elastimold bail, Copper wire (#14 AWG or equivalent), Elastimold insulating plug (K150DP, optional)
- Ensure De-energized State and Review Safety
Before beginning installation, ensure all apparatus is de-energized. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions can result in serious injury. Review all individual user, local, and national work rules.
- Prepare Jacketed Concentric Neutral Cable (if applicable)
For jacketed concentric neutral cable, cut and remove the cable jacket 8 inches from the cable end. Ensure sufficient concentric neutral wires remain for connection to the ground point as required by your installation.
- Prepare Copper Tape Shield Cable (if applicable)
For copper tape shield cable, cut and remove the cable jacket 7 1/2 inches from the cable end. Then, remove the copper tape shield 6 1/2 inches from the end of the cable. If using an ECS or MA grounding device, follow its specific instructions for outer jacket cut back.
- Prepare Cable Insulation and Conductive Shield
Remove 7/8 to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1 3/4 to 1 7/8 inches. Cut squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel, which contains inhibitor.
- Crimp Socket Terminal
Crimp the socket terminal onto the bared conductor, ensuring the conductor remains fully seated in the connector. Refer to the crimp chart provided with the contact. Start crimps at the imprinted crimp line and rotate each successive crimp or indent 90 degrees. If using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare Semi-Conductive Shield and Clean Insulation
Remove the semi-conductive shield to a point 7 9/16 to 7 5/8 inches back from the end of the pin with a straight, smooth, 'squared' cut. Do not cut or nick the insulation. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent, wiping from the cable end toward the outer jacket, to remove all traces of semi-conducting residue. If using an ECS or MA grounding device, install it now following its instructions.
- Lubricate Cable and Receptacle
Remove the protective cap from the straight receptacle. Keep the cable insulation and receptacle clean. Apply the supplied lubricant sparingly to the cable and to the inside of the housing. Do not substitute lubricants, as others may be harmful to the product.
- Insert Cable into Housing
Push the prepared cable into the housing until the base of the pin chamfer is flush with the inside face of the receptacle. If the receptacle will not be immediately connected, replace the protective cover. Note that the shipping cover only offers protection from dirt and is not an insulating device; use an Elastimold insulating plug (K150DP) if insulation is required.
- Connect to Mating Plug (if applicable)
If connecting to a mating plug, first lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1 3/4 inches), ensuring the rod is not cut. Insert the plug assembly into the receptacle as far as possible. Pull out the nylon rod. Secure the electrical connection with an Elastimold bail.
- Ground the Cable
If an ELASTIMOLD grounding device is not being used, connect a length of customer-supplied #14 AWG (or equivalent) copper wire through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.