ABB Installation Products K151SR-B0190 Straight Receptacle, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.635 inch…
UPC: 783786476770
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Ampere current rating for robust power handling.
- 15/25KV voltage class for medium-voltage applications.
- DeadBreak design ensures safe circuit isolation.
- Accommodates cable insulation diameters from 0.635" to 0.905".
- Aluminum compression lug for reliable conductor connection (AWG #4 / 16.76mm²).
Specifications
Amperage Rating | 200 A |
Application | Designed to connect a cable to another cable or apparatus |
Color | Black |
Conductor Range | #4 SOL/COMPT AWG |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Width | 2.74 in |
Width | 69.596 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K151SP-B0190
Straight Plug, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Solid #4/mmSquared 16.76.
K151SR-C0240
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SR-D0240
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.890 inch to 1.220 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0 or mmSquared 53.49.
K151SR-B0250
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151SR-B0220
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K151SP-C0240
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151SP-B0220
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K151SR-B0240
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.Frequently Asked Questions
What is the current rating of the K151SR-B0190 receptacle?
The ABB K151SR-B0190 Straight Receptacle has a current rating of 200 Amperes.
What is the voltage class for this ABB receptacle?
This ABB receptacle, model K151SR-B0190, is designed for 15/25KV voltage applications.
What cable insulation diameter range does the K151SR-B0190 support?
The K151SR-B0190 receptacle supports cable insulation diameters from 0.635 inches to 0.905 inches.
What type of lug is used for conductor connection?
The K151SR-B0190 features an aluminum compression lug for conductor connection.
What conductor sizes are compatible with the aluminum compression lug?
The aluminum compression lug is designed for compressed solid conductors of AWG #4 or 16.76 mm².
What is the primary function of a DeadBreak receptacle?
A DeadBreak receptacle, like the K151SR-B0190, allows for the safe connection and disconnection of energized medium-voltage cables.
How to Install the 151SR/K151SR Straight Receptacle
This guide provides step-by-step instructions for preparing the cable, crimping the conductor, and installing the 151SR/K151SR Straight Receptacle for connecting solid dielectric type cables to other electrical apparatus. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 1h
Tools needed:
Wire strippers, Crimp tool, Wire brush, Rag, Approved solvent
Supplies needed:
151SR/K151SR Straight Receptacle, Conductor Contact (male), Nylon Venting Rod, Lubricant (supplied), Crimp Chart, #14 AWG copper wire (or equivalent), Elastimold bail, Elastimold insulating plug (K150DP) (optional)
- Perform Initial Checks and Safety Precautions
Before starting, check the package contents for completeness and damage. Verify all components fit properly with your cable and mating products. Read all instructions thoroughly and ensure all required tools are at hand. Maintain cleanliness throughout the procedure. DANGER: All apparatus must be de-energized during installation or removal of parts. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare Jacketed Concentric Neutral Cable
If using jacketed concentric neutral cable, cut and remove the cable jacket a distance of 8 inches from the cable end. Ensure sufficient concentric neutral wires are left for connecting to the ground point as required by your installation.
- Prepare Copper Tape Shield Cable
If using copper tape shield cable, cut and remove the cable jacket a distance of 7 1/2 inches from the cable end. Then, remove the copper tape shield a distance of 6 1/2 inches from the end of the cable. (Note: For ECS or MA grounding devices, follow their specific instructions for outer jacket cut back.)
- Prepare Conductor Insulation and Shield
Remove 7/8 inch to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1 3/4 inches to 1 7/8 inches. Cut squarely; do not pencil the conductor. Wire brush any bare aluminum conductors and immediately insert them into the crimp barrel, which contains an inhibitor.
- Crimp Socket Terminal
Crimp the socket terminal onto the bared conductor, ensuring the conductor remains fully seated in the connector. Refer to the crimp chart provided with the contact. Start crimps at the imprinted crimp line and rotate each successive crimp or indent 90 degrees. If using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare Semi-Conductive Shield and Clean Insulation
Remove the semi-conductive shield to a point 7 9/16 inches to 7 5/8 inches back from the end of the pin with a straight, smooth, 'squared' cut. DO NOT CUT OR NICK THE INSULATION. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation to remove all traces of semi-conducting residue by wiping with a rag wet with an approved solvent, always wiping from the end of the cable toward the outer jacket. If using an ECS or MA grounding device, install it following its instructions.
- Lubricate Receptacle and Cable
Remove the protective cap from the straight receptacle. Keep the cable insulation and receptacle clean. Apply the supplied lubricant sparingly to the cable as shown in the documentation and to the inside of the housing. DO NOT SUBSTITUTE other lubricants, as they may be harmful to this product or its mating product.
- Insert Cable into Receptacle Housing
Push the prepared cable into the receptacle housing until the base of the pin chamfer is flush with the inside face of the receptacle. IMPORTANT: If the receptacle is not to be immediately connected to a mating product, replace the shipping cover with an Elastimold insulating plug (K150DP), as the shipping cover only offers protection from dirt and is not an insulating device.
- Connect to a Mating Plug
To connect to a mating plug, first lubricate the nose of the mating plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1 3/4 inches), taking care not to cut the rod. Insert the plug assembly into the receptacle as far as possible. Pull out the nylon rod. Finally, secure the electrical connection with the aid of an Elastimold bail.
- Ground the Cable
If an ELASTIMOLD grounding device is not being used, connect a length of #14 AWG (or equivalent) copper wire (customer supplied) through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.