ABB Installation Products 274ELR-K-5270 25kV 200 Amp, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation…
UPC: 783786505920
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV, 200 Amp fully rated loadbreak repair elbow connector
- Extended housing and compression lug (+3.25 inches / 82.6 mm) for repairing short cables
- Bi-metal compression lug supports copper/aluminum conductors (4/0 AWG to 250 mm²)
- Non-corrosive capacitive test point for safe voltage verification without disconnection
- Fully shielded, submersible molded rubber housing with 100% peroxide-cured insulation
- Meets ANSI/IEEE Standard 386 with 125kV BIL impulse withstand rating
- Provisions for hot stick operation and ground wire connection
- Compatible with cable insulation diameters from 1.090 inch to 1.310 inch
Specifications
Amperage Rating | 200 A |
Application | Designed for connecting to and operating 25kV Class, 125kV BIL apparatus |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 11.71 in |
Length | 297.434 mm |
Material | Bi-Metal |
Material | Housing - EPDM-Rubber |
Series | 274ELR |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured insulation, insert and jacket. Provision for hot stick operation, Provision for ground wire connection. Wide cable range with minimum number of sizes. Extended Length Housing and Compression Lug - plus 3-1/4 inch (82.6mm). Non-Corrosive Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Repair Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 8.4 in |
Width | 213.36 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.4500 L |
Package Weight (Metric) | 1.1110 kg |

656LRTP-J5270
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K151SP-B2230
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Includes a copper compression lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41
273RLR-G-5230
200 Amp, 25kV, Loadbreak Replacement Elbow Connector without Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
K151SP-D0270
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.890 inch to 1.220 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
376LR-J-2260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
K151SR-D0270
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.890 inch to 1.220 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid 250 or mmSquared 126.67.
168RLR-K-5270
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.Frequently Asked Questions
What material are the elbows constructed from?
The elbows are constructed from specially formulated, non-rigid ethylene propylene diene monomer (EPDM) rubber.
Are these elbow connectors certified?
Yes, these connectors are IEEE 386 compliant, ANSI certified, and Rural Utilities Service (RUS) accepted.
Where are Elastimold elbows manufactured?
Elastimold 200 A repair and replacement elbows are designed, molded, and tested in Albuquerque, NM, USA.
What is the test point cap catalog number?
The test point cap catalog number for elbows with a test point is 156-7.
What is the current rating of the elbow connectors?
The elbow connectors are rated for 200 A loadbreak applications.
What voltage classes do these connectors support?
The ABB Elastimold loadbreak repair and replacement elbows are available for 15 kV and 25 kV voltage classes.
How much length does the repair elbow add?
The repair elbow features an extended housing and compression lug length that is 3 1/4 inches longer than the standard elbow.
How much length does the replacement elbow add?
The replacement elbow extends its housing and compression lug length to 8 7/8 inches over the standard elbow.
How much length does the repair elbow add?
The repair elbow provides a net gain of 3 1⁄4 inches in length compared to a standard elbow.
Where are these elbow connectors manufactured?
These Elastimold 200 A repair and replacement elbows are designed, molded, and tested in Albuquerque, New Mexico, USA.
How to Install Elastimold 273ELR/274ELR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and wiring of Elastimold 273ELR and 274ELR Loadbreak Elbow Connectors on UD cable, including cable preparation and grounding procedures.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp Tool (specific to lug), Wire Brush, Wire Strippers, Hotstick, Suitable Voltage Sensing Device
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (supplied, do not substitute), UD Cable, No. 14 AWG (2.5mm) Copper Wire, Appropriate Ground Connector
- Perform Initial Safety Checks and Inspection
Before starting, ensure all apparatus is de-energized. Inspect all parts for damage, proper rating, and compatibility with mating parts. Check package contents for completeness. Read all instructions and have required tools ready. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions can result in serious injury or product damage.
- Train and Cut Cable
Train the UD cable to ease operation, ensuring a minimum of 20 inches extends beyond the end of the cable pad mount transformer. For new installations, cut any excess cable squarely at the center line of the bushing.
- Prepare Concentric Neutral Wires
Unwrap and bind the concentric neutral wires 'X' inches back from the end of the cable. Refer to the compression lug's specific 'X' dimension (e.g., 13 inches or 9-1/2 inches).
- Remove Cable Shield and Insulation
Carefully remove the cable shield and insulation 3-1/4 inches back from the end of the cable. Cut squarely, taking extreme care not to nick the conductor insulation.
- Install Compression Lug
Wire brush the bare aluminum conductors immediately. Install the compression lug, rotating it to spread the inhibitor. Position the lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe any excessive inhibitor from the lug and cable.
- Bevel and Clean Cable Insulation
Remove the insulation shield 10 inches from the lug end. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue, ensuring a straight, smooth, and squared surface without nicks.
- Lubricate Elbow Housing and Cable
Lubricate the cable insulation and the inside of the elbow housing using only the supplied lubricant. DO NOT SUBSTITUTE, as other lubricants may harm the product. Keep the insulation clean of dirt and grime during this process.
- Slide Elbow onto Cable
Slide the elbow connector onto the prepared cable using a back-and-forth twisting motion. Once fully seated, wipe off any excess grease from the exterior.
- Install Probe
Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring not to cross-thread. The probe should turn freely for approximately four turns before becoming snug. Tighten the probe with the probe wrench until the wrench bends, indicating proper torque.
- Connect Concentric Neutral to Ground
Insert one end of a separate No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the elbow and twist it tight, taking care not to damage the eye. Twist all concentric neutral wires together with the wire from the grounding eye and connect them to ground using an appropriate connector. Ensure adequate slack in the wires for elbow operation.
- Lubricate Elbow and Bushing for Connection
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. IMPORTANT: Only lubricate if the transformer and elbow are known to be de-energized to prevent serious injury.
- Connect Elbow to Bushing
Securely fasten a hotstick to the loadbreak connector pulling eye. Place the elbow connector receptacle over the bushing plug, inserting the elbow male contact until slight resistance is felt. Immediately push the elbow home with a fast, firm, straight motion to engage the internal lock on the elbow and bushing interface. DO NOT OPERATE BY HAND.
- Perform Voltage Test (Optional)
To perform a voltage test, remove the test point cap with a hotstick, peeling it off at an angle. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. WARNING: This is a capacitance device; do not use conventional voltage measuring equipment. Treat the elbow as energized until confirmed otherwise by other means. After testing, clean, lubricate, and replace the cap.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.