ABB Installation Products K151SP-B2230 200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included…
UPC: 783786514540
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp current rating
- 15/25 kV voltage rating
- Accommodates cable insulation diameter 0.635" - 0.905"
- Includes copper compression lug for AWG #1 to 1/0
- ABB K151SP Series Deadbreak Elbow Straight Plug
Specifications
Amperage Rating | 200 A |
Application | Designed to Terminate UD Cable having Concentric Neutral and Extruded instalation shielding |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection Type | Deadbreak Elbow Straight Plug |
Current Rating | 200 A |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 8.81 in |
Length | 223.774 mm |
Material | Copper, Poly |
Material | Housing - EPDM-Rubber |
Series | K151SP |
Size | 0.635-0.905 inch (cable insulation diameter) |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Plug |
Voltage Rating | 15/25 kV |
Voltage Rating | 15 to 25 kV |
Width | 2.55 in |
Width | 64.77 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
273RLR-G-5230
200 Amp, 25kV, Loadbreak Replacement Elbow Connector without Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
K151SP-D0270
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.890 inch to 1.220 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
376LR-J-2260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
K151SR-D0270
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.890 inch to 1.220 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid 250 or mmSquared 126.67.
168RLR-K-5270
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
168ELR88110-5240
200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
168ELR-6689-5240
200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.665 inch to 0.895 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.Frequently Asked Questions
What are the key features of the K151SP Deadbreak Straight Plug?
It is a 15/25kV, 200 Amp deadbreak straight plug with a fully shielded, submersible molded rubber housing and provision for a ground wire connection.
What is the continuous current rating for the K151SP?
The continuous current rating for the K151SP is 200 Amp for both 15kV and 25kV voltage classes.
Are bails included with the K151SP product?
No, bails are ordered separately but are required for the K151SP.
What standard does the K151SP meet?
The K151SP meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating for the 25kV class?
For the 25kV voltage class, the impulse withstand (BIL) is 125kV (1.2 x 50 microsecond wave).
What is the maximum operating voltage for the 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV, and the maximum phase-to-phase voltage is 26.3kV.
What is the impulse withstand rating for the 15kV class?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase voltage is 14.4kV.
What other Elastimold products are compatible with the K151SP?
The K151SP is designed to mate with the Elastimold K151T tee splice and the K151SR straight receptacle.
What cable insulation diameters are compatible with the K151SP?
The K151SP accommodates cable insulation diameters ranging from .575 inches to 1.220 inches.
How to Install the K151SP Straight Plug
This guide provides step-by-step instructions for preparing the cable, crimping the conductor, and installing the K151SP Straight Plug onto a cable and connecting it to a mating receptacle for 15kV and 25kV class systems. A bailing arrangement is required when used with any mating Elastimold deadbreak product.
Estimated time: 1h 30m
Tools needed:
Wire brush, Crimp tool, Rag, Approved solvent
Supplies needed:
Conductor Contact (female), Nylon Venting Rod, Lubricant (supplied with product), Collar, Silicone grease, ELASTIMOLD bail (required for mating), #14 AWG copper wire (customer supplied, if no grounding device)
- Prepare the Cable End
DANGER: All apparatus must be de-energized during installation or removal of parts. Cut and remove the cable jacket a distance of 8 inches from the cable end for jacketed concentric neutral cables. For copper tape shield cables, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the end of the cable. Allow sufficient concentric neutral wires for connecting to the ground point as required by the installation.
- Remove Insulation and Conductive Shield
Remove 7/8 inch to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1-3/4 inches to 1-7/8 inches. Cut squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel which contains inhibitor.
- Crimp the Socket Terminal
Crimp the socket terminal onto the bared conductor, holding the crimp barrel against the cable insulation. Refer to the crimp chart provided with the contact. Start the crimps at the crimp line imprinted on the barrel and rotate each successive crimp or indent 90 degrees. Carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare Insulation and Clean
Temporarily remove the plastic pin. Remove the semi-conductive shield to a point 7-3/4 inches to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut, ensuring not to cut or nick the insulation. Replace the plastic pin. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation to remove all traces of semi-conducting residue by wiping with a rag wet with an approved solvent, always wiping from the end of the cable toward the outer jacket. If using an ECS or MA grounding device, install it following its specific instructions.
- Lubricate Cable and Housing
Slide the collar, smaller end first, onto each cable. Reference the bailing instruction sheet. Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as shown and to the inside of the housing. Do not substitute lubricants, as other types may be harmful to this product or its mating product.
- Install Cable into Plug Housing
Push the cable into the plug housing. Ensure the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms, approximately 1-3/4 inches, taking care not to cut the rod. Insert the plug assembly into the receptacle as far as possible. Pull out the nylon rod. Secure the electrical connection with the aid of an ELASTIMOLD bail, referencing the Bailing Instruction Sheet (150TB-4).
- Connect Grounding (If No Device Used)
If an ELASTIMOLD grounding device is not being used, connect a length of #14 AWG or equivalent copper wire (customer supplied) through the grounding tab and twist tightly. Then, connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.