ABB Installation Products 167LRT-F5270 200 Amp, 15kV, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.640 inch to…
UPC: 783786537518
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp current rating for robust power handling.
- 15kV voltage rating suitable for medium-voltage systems.
- Accommodates cable insulation diameters from 0.640" to 0.820".
- Bi-metal compression lug for AWG 4/0 stranded or 250 mm² solid conductors.
- Includes 02800X bi-metal contact for enhanced conductivity.
Specifications
Amperage Rating | 200 A |
Application | 15kV, 200 Amps |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection Type | Compression Lug |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.640 inch to 0.820 inch |
Special Features | Includes 02800X Bi-Metal Contact |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Bolted Elbow with Tap |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

656LRTP-J5270
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K151SP-A2230
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.575 inch to 0.740 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
K151SR-B2200
15/25kV 200 Amp, Deadbreak Straight Receptacle (All Copper Lug), Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Conductor Size AWG Compressed Stranded #4/Solid #3/mmSquared 21.14.
K151SR-B0230
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
167LRT-F5240
200 Amp, 15kV, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes 02800X Bi-Metal Contact.
K151SP-B0230
15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
167RLR-F-5230
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.Frequently Asked Questions
What is the maximum cable insulation diameter for this elbow?
The ABB 167LRT-F5270 loadbreak elbow is designed to accommodate cable insulation diameters ranging from 0.640 inches to 0.820 inches.
What conductor sizes can be used with the bi-metal compression lug?
The bi-metal compression lug is suitable for compressed stranded conductors sized AWG 4/0 and solid conductors sized 250 mm² (126.67 mm²).
What is the current rating of the 167LRT-F5270 loadbreak elbow?
The ABB 167LRT-F5270 loadbreak elbow has a current rating of 200 Amps.
What is the voltage rating for this ABB loadbreak elbow?
This ABB loadbreak elbow connector is rated for 15kV.
Does the 167LRT-F5270 include a contact component?
Yes, the 167LRT-F5270 includes the 02800X bi-metal contact.
How to Install the 167LRT Loadbreak Bushing Tap
This guide provides step-by-step instructions for installing the 167LRT Loadbreak Bushing Tap, designed to terminate UD cable with concentric neutral and semi-con shielding, and provide an operating interface for 15kV class loadbreak elbow or accessory devices.
Estimated time: 1h 15m
Tools needed:
Wrenches, Crimp tool, Wire brush, Installation Tool
Supplies needed:
Lubricant (supplied, do not substitute), UD cable (concentric neutral and semi-con shielding), No. 14 AWG (2.5mm) copper wire, Appropriate grounding connector, 15kV class loadbreak elbow, insulated cap, or grounding elbow connector
- Observe Safety Precautions
Ensure all apparatus is de-energized before beginning installation or removal of parts. This product should only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, proper rating, and compatibility with mating parts before proceeding. Maintain cleanliness throughout the procedure.
- Train the Cable
Train the UD cable as shown in the documentation to ease future operation. Cut any excess cable squarely at the center line of the bushing, ensuring a minimum of 20 inches beyond the end of the cable.
- Prepare the Cable End
Unwrap and bind concentric neutral wires 8-1/2 inches back from the cable end. Remove the shield and insulation from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating it to spread inhibitor. Align the lug's threaded hole with the bushing bore. Crimp the lug starting at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe off excessive inhibitor. Remove the semi-con shield as shown and bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Bushing Well Contact
Thread the well contact onto the bushing well stud by hand, taking care not to cross-thread. Tighten with a wrench until the wrench bends, signifying the proper assembly torque has been reached.
- Assemble the Bushing Tap
Remove the protective cap from the bushing tap and retrieve the socket contact stored inside. Lubricate the cable insulation and the inside of the bushing housing with the supplied lubricant only; do not substitute. Slide the bushing tap onto the cable with a back and forth twisting motion, then wipe off all excess grease. Align the bushing with the compression lug hole and assemble the socket contact into the bushing tap, ensuring the socket contact stud passes through the lug hole.
- Lubricate and Mount the Bushing Tap
Inspect the apparatus bushing well to ensure it is dry and free from all contaminants. Lubricate the bushing well interface area of the bushing tap with the supplied lubricant or ELASTIMOLD approved lubricants. Place the lubricated bushing tap into the apparatus bushing well. Insert the installation tool into the bore of the bushing tap until fully seated. Insert a wrench through the wrench hole of the tool and turn in a clockwise direction until the wrench bends, indicating proper assembly torque. Remove the wrench and installation tool.
- Connect the Concentric Neutral
Insert one end of a No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the bushing tap and twist it tight, being careful not to damage the eye. Twist the neutral wires together and connect them to ground using an appropriate connector.
- Prepare for Mating Product Installation
Thoroughly wipe the bushing tap interface clean of any contaminants and apply a light, uniform coat of the supplied lubricant, working it thoroughly into the surface. CAUTION: Excess lubricant may prevent a loadbreak elbow from being fully seated in the “locked on” position. Install mating products (e.g., loadbreak elbow, insulated cap, or grounding elbow) following their specific instructions. If not immediately mating, replace the shipping cap. Do not energize or submerge the apparatus with the shipping cap, as it is for protection only and not insulated or watertight.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.