- 25/28kV rated, 200 Amp continuous current capacity
- Loadbreak design for safe operation under load
- Compatible with 0.890–1.220" cable insulation diameters
- Supports 2/0 stranded or 3/0 solid wire sizes
- Bi-metal compression lug for reliable electrical contact
Specifications
Amperage Rating | 200 A |
Application | 25/28 kV, 200 Amp |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection Type | Loadbreak Jacket Seal Elbow Connector |
Current Rating | 200 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal Compression Lug |
Size | 11.47 inch End to Center of Installation Eye X 4.13 inch End to Bushing Datum, 2.87 inch Diameter |
Size | 0.890 inch - 1.220 inch Cable Insulation Diameter, 2/0 Stranded or 3/0 Solid Wire Size |
Special Features | 25/28kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Built in Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector and Jacket Seal |
Voltage Rating | 25 to 28 kV |
Voltage Rating | 25/28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR3B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
261LRJS-C5230
25/28kV, 200 Amp, Loadbreak Jacket Seal Elbow Connector, .805 inch - 1.060 Inch Cable Insulation Diameter, #1 Stranded Wire Size, Bi-Metal Compression Lug.
261LRJS-C5220
25/28kV, 200 Amp, Loadbreak Jacket Seal Elbow Connector, .805 inch - 1.060 Inch Cable Insulation Diameter, #2 Stranded Wire Size, Bi-Metal Compression Lug.
261LR-D5270
25/28kV, 200 Amp, Loadbreak Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug.
261LR-D5270-S
25/28kV, 200 Amp, Loadbreak Elbow without Test Point, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.
261LR-D5240
25/28kV, 200 Amp, Loadbreak Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug.
261LR-D5230
25/28kV, 200 Amp, Loadbreak Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, #1 Stranded Wire Size, Bi-Metal Compression Lug.Frequently Asked Questions
What voltage rating does the 261LRJS-D5250 support?
The connector is rated for 25/28kV medium-voltage applications.
What cable insulation diameters are compatible?
The connector fits cable insulation diameters from 0.890 to 1.220 inches.
What wire sizes does this connector accommodate?
It supports 2/0 stranded or 3/0 solid wire sizes.
What is the current rating of this connector?
The connector has a 200 Amp continuous current rating.
Is the 261LRJS-D5250 a loadbreak connector?
Yes, it features a loadbreak design for safe operation under load conditions.
How to Install 261LRJS and 262LRJS Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 261LRJS and 262LRJS Loadbreak Elbow Connectors, including cable preparation, elbow assembly, and connection to a 25kV class loadbreak bushing or accessory device. Installation must be performed by competent personnel trained in high voltage electrical equipment safety.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Wire brush, Crimp tool (specific to compression lug), Hotstick (for energized operations and test point caps), Cable cut back template
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (supplied, do not substitute), Sealing Strips (3), Mastic strips, Vinyl tape, Copper wire (No. 14 AWG / 2.5mm) or equivalent, Appropriate connector (for neutral to ground), UD cable with jacketed concentric neutral wires and extruded insulation shielding, HV insulated cap(s) or connector(s) (if shipping covers are present)
- De-energize and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts, except for test point caps and indicators. Check the contents of the package to ensure all components are complete and undamaged. Inspect all parts for proper fit with the cable and/or mating products. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Prepare Cable for Training
Train the cable to ensure sufficient slack for ease of operation. Pull extra cable 24-26 inches beyond the centerline of the bushing. Place a tape mark at the bushing centerline. Remove the outer jacket 7-3/4 to 8 inches further back from the tape mark. Unwrap the neutral wires back past the bushing centerline and cut the excess cable squarely at the bushing centerline.
- Apply Mastic and Embed Neutral Wires
Wrap one strip of mastic, stretching slightly, around the cable jacket. Bend all neutral wires straight back over the mastic and along the cable, pressing them firmly into the mastic. Wrap a second strip of mastic completely around the outer jacket, overlapping the embedded neutral wires. Use a third strip of mastic if needed to build up the outer diameter. Cover all mastic with vinyl tape.
- Prepare Cable End for Lug Installation
Using a cable cut-back template for dimensional guidance, remove the insulation shield and insulation from the cable end. Cut squarely, taking extreme care not to nick the conductor or insulation. Bevel the insulation end a maximum of 1/8 inch.
- Install Compression Lug
Wire brush bare aluminum conductors immediately before installation. Install the compression lug, rotating it to spread the inhibitor. Position the compression lug so the contact threaded hole aligns with the bushing bore. Refer to the crimp chart packaged with the compression lug for recommended crimp tool information. Start crimping at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe any excessive inhibitor from the outside of the lug and cable.
- Clean Insulation
Thoroughly clean the insulation to remove all traces of conductive residue, ensuring a straight, smooth, and squared surface. Do not cut or nick the insulation during this process.
- Lubricate and Assemble Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants, as they may be harmful. Keep the insulation clean of dirt and grime. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant.
- Install and Tighten Probe
Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. The probe should turn freely for approximately four turns before becoming snug. Tighten the probe with the probe wrench until the wrench bends, indicating proper torque.
- Connect Concentric Neutral Wires
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm) or equivalent through the grounding eye on the elbow. Twist it tightly, ensuring not to damage the eye. Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and/or rolling the seal down. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack for elbow operation.
- Connect Elbow to Mating Bushing
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Securely fasten a hotstick to the loadbreak connector pulling eye. Confirm positive control of the elbow connector. Insert the probe tip approximately 2 inches (50mm) into the bushing, then immediately push the elbow home with a fast, firm, straight motion, using sufficient force to engage the internal lock on the elbow connector and bushing interface. DO NOT OPERATE BY HAND.
- Perform Voltage Test (262LRJS Only)
For 262LRJS models, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Follow the manufacturer's directions for a suitable sensing device to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.