Contact for Pricing
Overview
- 15kV voltage rating with 200A continuous current capacity
- Bi-metal compression lug for corrosion-resistant conductivity
- Test point for safe voltage verification without disconnection
- Loadbreak-rated for hot-stick operation in live-line maintenance
- EPDM jacket seal for environmental protection (0.805-1.060in cable insulation)
Specifications
Amperage Rating | 200 A |
Application | 15 kv, 200 Amp |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Built in cable jacket seal. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point and Jacket Seal |
Voltage Rating | 15 kV |
Width | 8.2 in |
Width | 208.28 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

161LR-B5260
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
162LRJS-C5230
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, #1 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-D5270
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug
261LR-B5240
25/28kV, 200 Amp, Loadbreak Elbow Connector, .635 inch - .905 inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug.
261LR-C5220
25/28kV, 200 Amp, Loadbreak Elbow Connector, .805 inch - 1.060 Inch Cable Insulation Diameter, #2 Stranded Wire Size, Bi-Metal Compression Lug.
261LR-C5230-S
200 Amp, 25kV, Loadbreak Elbow without Test Point, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. 200ECS Jacket Seal Included.
262LR-C5250
25kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 2/0 Stranded Wire Size, Bi-Metal Compression Lug.Frequently Asked Questions
Does this connector have a test point?
Yes, the connector includes an integrated test point for voltage verification.
What is the voltage rating of this connector?
The connector is rated for 15kV continuous operation.
What cable insulation diameters does this connector support?
The connector accommodates cable insulation diameters ranging from 0.805 to 1.060 inches.
What wire size is compatible with this connector?
This connector is designed for 3/0 AWG stranded copper wire.
Is this connector loadbreak-rated?
Yes, it is a loadbreak-rated elbow connector for safe live-line disconnection.
Can this connector be used with hot sticks?
Yes, the elbow design allows for hot-stick operation during installation and maintenance.
What standards does this connector meet?
The connector meets ANSI C119.4 and IEEE 386 standards for loadbreak elbow connectors.
How to Install 161LRJS/162LRJS Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of 161LRJS and 162LRJS Loadbreak Elbow Connectors with jacket seals on UD cable, including cable preparation and assembly.
Estimated time: 1h
Tools needed:
Probe Wrench, Crimp tool, Wire brush, Hotstick
Supplies needed:
Lubricant (supplied), Mastic strips (sealing strips supplied), Vinyl tape, Copper wire (No. 14 AWG / 2.5mm or equivalent), Appropriate grounding connector
- Perform Safety Checks and Initial Inspection
DANGER: Ensure all apparatus is de-energized during installation. This product must be installed only by competent personnel trained in high voltage electrical equipment safety. Inspect all package contents for completeness and damage. Check all components for proper fit with the cable and/or mating products. If applicable for 162LRJS, lubricate and install the test point cap if not already present. Read all instructions before proceeding.
- Train and Cut Cable
Train the UD cable to ensure sufficient slack for ease of operation. Provide an extra length of 24-26 inches (61-66 cm) of concentric neutral wires or grounding braid beyond the bushing centerline. Unwrap the neutral wires back past the bushing centerline. Cut the excess cable squarely at the bushing centerline.
- Prepare Cable Jacket and Neutral Wires
Wrap one mastic strip around the cable jacket, stretching it slightly. Bend all neutral wires straight back over the mastic and along the cable, pressing them firmly into the mastic. Wrap a second mastic strip completely around the outer jacket, overlapping the imbedded neutral wires. Use a third mastic strip if necessary to build up the outer diameter. Cover all mastic with vinyl tape.
- Prepare Cable Insulation and Conductor
Remove the insulation shield and insulation from the cable end according to the provided template, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors immediately and install the compression lug. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the insulation shield as shown in the template and bevel the insulation end a maximum of 1/8 inch (3 mm). Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants. Keep the insulation clean of dirt and grime. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring not to cross-thread. The probe should turn freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Connect Concentric Neutral
Pull the hood over the concentric neutral seal area on the cable by pulling the tabs or rolling the seal down. Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow. Twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. WARNING: LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. DANGER: Do not operate by hand. Use a fully insulated 'hotstick' type live-line tool for connection. Refer to the operating instructions for proper loadmake operation, ensuring positive control and a fast, firm, straight motion to fully engage the elbow with the bushing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.