ABB - Installation Products 161LRJS-B-5220 - 15KV, 200 Amp, Loadbreak Elbow with Sealing Jacket, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
ABB - Installation Products

161LRJS-B-5220

UPC: 075114241298


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Overview

The ABB 161LRJS-B-5220 is a 15kV, 200 Amp loadbreak elbow connector designed for reliable power distribution applications. This unit features a robust sealing jacket to ensure environmental protection and maintain electrical integrity. The integrated bi-metal compression lug is engineered for secure and durable connections, accommodating conductor sizes from AWG #2 compressed stranded to #1 solid (33.62 mm²). The cable insulation diameter range for this elbow is specified between 0.635 inches and 0.905 inches, providing flexibility for various cable types. The 161LRJS-B series is a key component in medium voltage systems, facilitating safe and efficient connections in substations, industrial facilities, and utility networks. Its construction prioritizes performance and longevity, ensuring consistent operation under rated conditions. The bi-metal lug offers excellent conductivity and corrosion resistance, crucial for maintaining low resistance connections over time. This loadbreak elbow is suitable for applications requiring the disconnection and connection of energized circuits under load, offering a critical safety feature for system maintenance and operation. The sealing jacket provides a barrier against moisture and contaminants, extending the service life of the connection. Key Specifications: - SKU: 161LRJS-B-5220 - Manufacturer: ABB - Installation Products - Voltage Rating: 15kV - Current Rating: 200 A - Cable Insulation Diameter: 0.635" - 0.905" - Lug Material: Bi-Metal Compression - Conductor Size: AWG #2 Stranded / #1 Solid (33.62 mm²) - Connection Type: Loadbreak Elbow with Sealing Jacket - Series: 161LRJS-B
  • 15kV Voltage Rating
  • 200 Amp Current Rating
  • Bi-Metal Compression Lug for reliable connections
  • Sealing Jacket for environmental protection
  • Accommodates cable insulation diameters from 0.635" to 0.905"

Specifications

Amperage Rating
200 A
Application
The 161LRJS is designed for Connecting to and Operating 15kV Class, 200 Amp Distribution apparatus. It Provides a Convenient Method to Connect/Disconnect Cable and Equipment on Power Distribution Systems
Color
Black
Conductor Range
#2 STR/COMPR AWG , #1 SOL/COMPT AWG
Environmental Conditions
Products are designed and constructed for all applications including Padmount, Subsurface, Vault, Indoor, Outdoor, Direct Sunlight, Direct Buried and Continuously Submerged in Water
Insulation
True
Material
Housing - EPDM-Rubber
Special Features
Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Provision for Hot Stick Operation. Provision for Ground Wire Connection. Built in Cable Jacket Seal
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Loadbreak Elbow Connector and Jacket Seal
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
2.2100 L
Package Weight (Metric)
1.0030 kg
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #2 Stranded Wire Size. Bi-Metal Compression Lug

162LR-B-5220

15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #2 Stranded Wire Size. Bi-Metal Compression Lug
6MM2 BLACK CABLE FOR DISTRIBUTION BLOCK ROW TYPE LENGTH 320MM

54211116

6MM2 BLACK CABLE FOR DISTRIBUTION BLOCK ROW TYPE LENGTH 320MM
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.

161LR-D5270

15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
15KV, 200 Amp, Loadbreak Elbow with Sealing Jacket, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67.

161LRJS-B-5210

15KV, 200 Amp, Loadbreak Elbow with Sealing Jacket, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67.
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.

161LR-D5250

15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.

161LR-D5240

15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.

161LR-D5260

15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.

161LR-C5260

15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.

Frequently Asked Questions

Does the elbow have RUS acceptance?

Yes, it has Rural Utilities Service (RUS) acceptance from the U.S. Department of Agriculture (USDA).

What standards does the elbow comply with?

The enhanced Elastimold 200 amp loadbreak elbow is IEEE 386 compliant.

What is the benefit of using Elastimold bushings?

When used with Elastimold bushings, the elbow offers lifetime ease of operation and a non-stick interface.

Does the elbow have a no-stick interface?

Yes, it features a no-stick interface when used with Elastimold bushings, which has been NEETRAC tested.

What is the Elastimold 200 amp loadbreak elbow?

It is an enhanced 200 amp loadbreak elbow available in 15 kV and 25 kV series, designed for switching operations.

What is the benefit of using Elastimold bushings?

When used with Elastimold bushings, the elbow offers lifetime ease of operation and a non-stick interface.

What is the Elastimold 200 amp loadbreak elbow?

It is an enhanced 200 amp loadbreak elbow available in 15 kV and 25 kV series, designed for switching operations.

Does the elbow have a no-stick interface?

Yes, it features a no-stick interface when used with Elastimold bushings, which has been NEETRAC tested.

What standards does the elbow comply with?

The enhanced Elastimold 200 amp loadbreak elbow is IEEE 386 compliant.

Does the elbow have RUS acceptance?

Yes, it has Rural Utilities Service (RUS) acceptance from the U.S. Department of Agriculture (USDA).

How to Install 161LRJS/162LRJS Loadbreak Elbow Connectors

This guide provides step-by-step instructions for the safe and proper installation of 161LRJS (without test point) and 162LRJS (with test point) Loadbreak Elbow Connectors with Jacket Seal on UD cable.

Estimated time: 1h 30m

Tools needed:

Probe Wrench, Crimp tool, Wire brush, Hotstick, Suitable sensing device (for capacitive test points)

Supplies needed:

Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Sealing strips (3), Vinyl tape, Copper wire (No. 14 AWG / 2.5mm or equivalent), Appropriate connector (for neutral wires)

  1. Perform Pre-Installation Checks and De-energize Apparatus

    Verify package contents, component fit, and lug/probe threads. Read instructions and gather all tools. Ensure all apparatus is de-energized during installation or removal of parts, except for test point caps and indicators. If a test point cap is not installed, lubricate and install it.

  2. Train Cable

    Train the UD cable to ensure sufficient slack for operation. Mark the bushing centerline and pull extra cable 24-26 inches beyond it. Unwrap neutral wires past the centerline and cut the cable squarely at the centerline.

  3. Prepare Cable End with Mastic

    Apply the first mastic strip, stretching slightly, around the cable jacket. Bend all neutral wires straight back over the mastic and along the cable, pressing them into the mastic. Wrap the second mastic strip completely around the outer jacket, overlapping the imbedded neutral wires. Use a third strip if needed to build up the outer diameter in the area of the first mastic location. Cover all mastic with vinyl tape.

  4. Prepare Conductor and Install Compression Lug

    Remove the insulation shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread inhibitor. Position the compression lug so its threaded hole aligns with the bushing bore. Crimp the lug according to the chart packaged with it, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable.

  5. Finish Insulation Preparation

    Remove the remaining insulation shield as indicated by the cable cut back template. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.

  6. Assemble Elbow Housing

    Lubricate the cable insulation and the inside of the elbow housing with the lubricant supplied; DO NOT SUBSTITUTE. Other lubricants may be harmful to this product or its mating part(s). Slide the elbow connector onto the cable with a back-and-forth twisting motion. Wipe off all excess lubricant.

  7. Align Elbow and Secure Probe

    Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. The probe must turn freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.

  8. Connect Concentric Neutral

    Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and/or rolling the seal down. Insert one end of a separate copper wire (No. 14 AWG / 2.5mm) or equivalent through the grounding eye on the elbow and twist tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack in the wires for elbow operation.

  9. Connect Elbow to Bushing Plug

    Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY IF the transformer and elbow are known to be de-energized. Operate the elbow using a fully insulated 'hotstick' type tool as per operating instructions; DO NOT OPERATE BY HAND.

  10. Perform Voltage Test (162LRJS only)

    If using the 162LRJS model, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line. WARNING: The voltage test point is a capacitance device; it is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, etc., or use of the wrong measuring equipment can provide a false 'no voltage' indication. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.