ABB Installation Products K655LR-F5220 25kV, 600 Amp, Deadbreak Elbow, No Sealing Kit, without Test Point, Cable Insulation…
UPC: 075114320115
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV voltage rating for medium-voltage applications
- 600 Amp current rating for high-load systems
- Bi-metal lug for copper-to-aluminum conductor transitions
- Cable insulation diameter range: 0.640–0.820 inches
- Supports AWG #2 compressed/stranded or #1 compacted/solid conductors
- No sealing kit or test point included for simplified installation
- Deadbreak design enables safe connection/disconnection of energized cables
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
K656LR-L5330-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold-Shrinkable Jacket Seal Included.
K656LR-J0330
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
K656LR-L0270
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 4/0 or Compact/Solid 250 or mm2 Compact 125.
K655LR-F0270
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125.
K656LR-L0240-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-K0270
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed/Stranded 4/0 or Compact/Solid 250 or mm2 Compact 125.Frequently Asked Questions
What is the voltage rating of the K655LR-F5220?
The ABB K655LR-F5220 has a voltage rating of 25 kV.
What is the current rating for this deadbreak elbow?
This deadbreak elbow connector is rated for 600 Amps.
What cable insulation sizes does the K655LR-F5220 support?
It supports cable insulation sizes ranging from 0.640 to 0.820 inches.
What type of lug material is used in this ABB elbow?
The K655LR-F5220 features a bi-metal lug for its conductor connection.
Does this deadbreak elbow include a test point?
No, this model of the K655LR-F5220 does not include a test point.
What conductor sizes are compatible with the K655LR-F5220?
It is compatible with AWG #2 compressed/stranded or AWG #1 compacted/solid conductors, and mm² compacted conductors up to 35 mm².
Is a sealing kit included with the K655LR-F5220?
No, this specific model does not come with a sealing kit.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K655/K675LR and 655/675LR Deadbreak Elbow Connectors on 15kV and 25kV class systems, ensuring fully shielded and submersible cable connections.
Estimated time: 1h 30m
Tools needed:
Wire brush, Hotstick, Suitable sensing device for capacitive test points, Crimping tool, Torque wrench
Supplies needed:
K655/K675LR Deadbreak Elbow Connector kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Cable (appropriate type for connector), Mating product, HV insulated cap(s) or connector(s) (if replacing shipping covers), Wire with ampacity at least equivalent to No. 14 AWG Copper, Suitable connector (for grounding wire), Silicone lubricant, Tape marker
- De-energize Apparatus and Inspect Components
DANGER: Before beginning, ensure all apparatus is de-energized. Inspect all components of the K655/K675LR connector kit for damage, proper rating, and compatibility with the cable and mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors if the circuit is to be submerged or energized later. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Prepare Cable for Installation
Assemble the cable in its final position, ensuring enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires. Refer to specific instructions for 20MA/21MA grounding devices, 600ECS Jacket Cable Seals, or UNISHIELD*/LEAD SHEATH cables.
- Prepare Cable Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure the exposed conductor length is between 4-1/4 inches and 4-9/16 inches (108mm-116mm); if not, redo the assembly. For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Measure the 'Check Dimension' before crimping (it must be less than 6-3/8 inches). Crimp the compression lug according to its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8 inches to 7-1/8 inches (162mm-181mm); if not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; if not, reposition it. Remove the tape marker.
- Connect Elbow to Mating Product
Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean. Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. DANGER: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZEN WHILE DISCONNECTED.
- Connect Opposite End of Elbow (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down hard until it snaps into place. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to specified torque per instructions.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper ampacity) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with a grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Optional but Recommended)
To determine if the circuit is energized, use the integral capacitance test point. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Contamination, moisture, dirt, or incorrect equipment can cause a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.