Contact for Pricing
Overview
- Thermostat range adjustable from 0 F to 100 F (-18 C to 38 C)
- Four 10-32 x self-tapping screws are included with each heater
- Ball bearing fan
- Terminal strip with clamp connector that accepts both solid and stranded wire
- Terminal strip with clamp connector that accepts both solid and stranded wire
- Suitable for hazardous locations (Class I Div 1, Class II Div 1)
- Prevents condensation and corrosion
Specifications
Amperage Rating | 1.89 A |
Application | Power Distribution; Controls and Drives |
Color | Unpainted |
Color | Brushed |
Current Rating | 1.7 A |
Depth | 102 mm |
Depth | 4 in |
Finish | Brushed |
Frequency | 50/60 Hz |
Frequency Rating | 50/60 Hz |
Height | 140 mm |
Height | 5.5 in |
Housing Material | Aluminum |
Material | Aluminum |
Material | Brushed Aluminum |
Max Current | 1.89 A |
Nominal Capacity Watts | 200 W |
Nominal Voltage | 115 V |
Series | DAH2001A |
Size | 5.50x4.00x4.00 inch |
Thickness | 0.06 IN |
Thickness | 1.5 mm |
Type | Heaters |
Voltage AC | 100-120 V |
Voltage Rating | 115 VAC |
Voltage Rating | 100 - 120 VAC |
Weight | 0.73 kg |
Weight | 1.9 lb |
Width | 102 mm |
Width | 4 IN |
Package Dimensions (L x W x H) | 8.7 IN x 6.5 IN x 6.5 IN |
Package Dimensions (L x W x H) | 22.098 cm x 16.51 cm x 16.51 cm |
Package Weight (Imperial) | 1.900 L |
Package Weight (Metric) | 0.862 kg |
How to Install the DAH2001A Electric Heater
This guide provides step-by-step instructions for installing and configuring the DAH2001A electric heater safely and effectively.
Estimated time: 45m
Tools needed:
Screwdriver, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Terminal connectors
- Disconnect power supply
Ensure that all power supplies to the enclosure are disconnected to avoid electric shock and equipment damage.
- Mount the heater
Secure the DAH2001A heater to a non-combustible metal panel using the four included 10−32 UNF self-tapping screws. Position the heater vertically with the terminal block at the bottom and the air outlet openings at the top.
- Connect wiring
Connect the heater lead wires to the appropriate A.C. power source, ensuring that the heater is properly grounded. Verify that exposed wires do not contact the heater housing.
- Set the thermostat
Adjust the thermostat to the desired temperature, ensuring it does not exceed 75°F for optimal performance.
- Verify installation
Double-check all connections and ensure that the heater is securely mounted and free from obstructions before restoring power.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.