ABB Installation Products R2T35J2-N0270-B3 Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed…
UPC: 783786387106
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35 kV Outdoor Cable Termination for Concentric Neutral/Jacketed Concentric Neutral Cables
- Aluminum 2-Hole Spade Connector for #2 AWG - 1250 kcmil Conductors
- Includes B3 Stainless Steel Cable Mounting Bracket (1.45" - 1.95" O.D.)
- Non-tracking Silicone Housing with 8 Sheds for Superior Weathering and Dielectric Performance
Specifications
Application | Cable Termination, Outdoor Application, 35kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 4/0 AWG , 250 kcmil |
Connection Type | Concentric Neutral/Jacketed Concentric Neutral |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Cable Mounting |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84 - 1.38 inches |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T35J2-N0270
Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250.
R2T15J2-N0220
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable. Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed #2 /Compact or Solid #1.
R2T35J2-H0240
Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0.
R2T35J2-T0240-B2
Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
R2T28M4-N0410
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 410 -Stranded or Compressed 1000 Compact or Solid N/A.
R2T28M4-T0220-B2
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1, Stainless Steel Mounting Bracket 1.10 inch - 1.50 inch
R2T28J4-T0260
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 3/0 /Compact or Solid 4/0
R2T15J1-N0240
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 1/0 Stranded or 2/0 SolidFrequently Asked Questions
What cable insulation diameters does the R2T35 termination cover?
The R2T35 termination covers cable insulation diameters from 0.84 in (21.3 mm) to 2.10 in (53 mm). This accommodates #2 AWG through 1250 kcmil cables.
What cable types are compatible with the R2T35 termination?
The R2T35 units accommodate popular XLP and EPR cable types and shield constructions.
What is the Coronal Extinction Voltage for the R2T35?
The Coronal Extinction Voltage (Partial Discharge) for the R2T35 is 30 kV (≤ 3pC).
How many sheds does the 35 kV outdoor R2T35 model have?
The 35 kV outdoor R2T35 model features eight sheds.
What is the creepage distance for the R2T35 outdoor termination?
The creepage distance for the R2T35 outdoor termination is 30.0 in (762 mm).
What is the minimum strike distance for the R2T35 outdoor termination?
The minimum strike distance for the R2T35 outdoor termination is 16.8 in (427 mm).
What is the maximum altitude for installing the R2T35 termination?
The R2T35 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What power system frequency is compatible with the R2T35?
The R2T35 termination is compatible with a power system frequency range of 48 to 62 Hz.
What is the acceptable ambient temperature range for the R2T35?
The R2T35 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the voltage rating of the R2T35 outdoor termination?
The R2T35 outdoor termination has a voltage rating of 35 kV. Its maximum design voltage to ground is 22 kV.
How to Install the R2T35J2-N0270-B3 35kV Ranger 2 Cable Terminator
Complete installation guide for the R2T35J2-N0270-B3 35kV Ranger 2 Cable Terminator, designed for indoor/outdoor concentric and jacketed concentric neutral cables. This guide covers cable preparation, lug installation, cleaning, and termination assembly.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Measuring tape, Utility knife
Supplies needed:
Silicone Rubber Termination Halves, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Terminal lug or Connector, Cable Support Bracket (optional), Vinyl tape or Binding wire, Approved solvent, Aluminum oxide abrasive (optional), Silicone grease
- Perform Pre-Installation Checks and Ensure Safety
DANGER: De-energize all apparatus before beginning installation or removal of parts. Inspect all kit contents for completeness and damage. Verify all components fit properly with the cable and mating products. Gather all required tools and maintain a clean work area throughout the procedure.
- Prepare the Cable
Verify the cable size fits within the kit's specified range. Train the cable into position and cut to the required length, ensuring sufficient neutral wire length for grounding connection. Prepare the cable using the provided dimensions, allowing for terminal lug depth and additional exposed conductor distance for crimping. Wrap one band of sealing mastic around the cable jacket 1/4” (6mm) from the jacket end, stretching 50%. Cut flush without overlapping. Bend neutral wires back over the mastic and press them into it, securing them to the cable jacket 4-6” (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, stretching 50%. Cut flush without overlapping. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4” (6mm) dimension.
- Install the Lug or Connector
If using a lug that will not fit through the termination core, slide the termination onto the cable before installing the lug; do not remove the core at this time. Position the connector/lug and crimp it according to directions, ensuring the last 1/4” to 3/8” of the connector is not crimped. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only; do not use abrasive on the semi-con insulation shield and be careful not to reduce the cable insulation diameter below that allowed by the kit.
- Install the Lower Termination Half
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, use the tape strip to form the tape band equal to the insulation diameter. Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step. For the lower termination, pull the loose end of the removable core through the top until the core is flush with the bottom of the termination. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body is butted against the leading edge of the mastic seal and avoid pushing or pulling the termination assembly while removing the core material.
- Install the Upper Termination Half and Complete Sealing
Using the second termination housing, carefully pull its core down to within one coil of the bottom. Slide the second terminator over the cable and carefully pull its core counterclockwise, overlapping the first terminator by 1-1/2” (40mm). Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground. Confirm that the High-K step does not exceed 1.5”.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.