Authorized ABB Distributor (Installation Products)
ABB - Installation Products R2T35J2-N0270 - Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250.

ABB Installation Products R2T35J2-N0270 Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed…

UPC: 075114195072


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 35 kV outdoor cable termination (SKU: R2T35J2-N0270) is engineered for reliable medium-voltage power distribution in outdoor environments. This termination utilizes shrink-fit technology combined with Elastimold's pull-down jacket seal for broad application coverage with minimal model variation. The integrated aluminum 2-hole spade connector is rated for #2-1250 kcmil conductors, ensuring secure, low-resistance connections. Constructed with a non-tracking silicone housing, the R2T35J2-N0270 offers superior memory and weathering characteristics, crucial for long-term dielectric integrity. The housing features eight sheds for the 35 kV outdoor model, providing enhanced creepage and strike distances for optimal performance in all field conditions. Installation is simplified by the field-removable center core and pull-down tabs for the built-in jacket seal. This design allows for installation in restricted spaces and supports free-hanging applications. Key specifications include a maximum design voltage to ground of 22 kV, a coronal extinction voltage of ≤ 3 pC at 30 kV, and a lightning impulse withstand (BIL Dry) of 200 kV crest. The termination meets stringent insulation withstand voltage requirements: 80 kV (10-second wet 60Hz), 90 kV (1-minute dry 60Hz), 75 kV (5-hour dry 60Hz), and 140 kV (DC withstand 15 min. dry). It is compatible with XLP and EPR cable types and shield constructions. Optional insulating silicone sleeves are available for increased creepage or wildlife protection. The ABB Ranger2 series is recognized for precision-engineered components in high-voltage cable systems.
  • 35 kV outdoor cable termination with shrink-fit technology and pull-down jacket seal.
  • Accommodates cable insulation diameters from 0.84" to 1.38" and conductor sizes #2 AWG to 1250 kcmil.
  • Features an aluminum 2-hole spade connector for secure, low-resistance connections.
  • Non-tracking silicone housing provides superior memory and weathering characteristics with eight sheds.
  • Designed for installation in restricted spaces and supports free-hanging applications.
  • Minimum strike distance: 16.8 inches (427 mm)
  • Voltage ratings: 22 kV max design to ground, 200 kV BIL Dry withstand
  • Field-removable center core for simplified installation and maintenance
  • Compatible with XLP and EPR cable types and shield constructions
  • Optional insulating silicone sleeves for enhanced creepage or wildlife protection

Specifications

Application
Cable Termination, Outdoor Application, 35kV
Cable Type
Concentric Neutral Wire
Color
Gray
Conductor Size
4/0 AWG , 250 kcmil
Connection Type
2-Hole Spade Connector (#2-1250 kcmil)
Connection Type
Aluminum 2-Hole Spade #2-1250 kcmil
Earthing
Products Includes Their Own Grounding System
Material
Aluminum
Mounting
Product Need to have Cable Holder (not included)
Mounting Type
Outdoor Termination
Number Of Terminals
(1) Single Phase
Series
Ranger2
Size
0.84 inch - 1.38 inch (insulation range)
Size
0.84-1.38 inch (Insulation Range)
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
35 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.

R2T35J2-N0270-B3

Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 3/0 /Compact or Solid 4/0

R2T28J4-T0260

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 3/0 /Compact or Solid 4/0
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 1/0 Stranded or 2/0 Solid

R2T15J1-N0240

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 1/0 Stranded or 2/0 Solid
Ranger2 Termination for 28KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Conductor Code 210 - Compact or Solid #2.

R2T28M2-N0210

Ranger2 Termination for 28KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Conductor Code 210 - Compact or Solid #2.
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead, Stranded or Compressed 2/0 /Compact or Solid 3/0

R2T35J2-T0250

Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead, Stranded or Compressed 2/0 /Compact or Solid 3/0
Outdoor, Ranger2 Termination, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range - .64-1.12 inch (16-28mm). Connector Type Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0. Conductor - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cable Mounting Bracket Material - Stainless Steel, Size .80-1.25 inch (20-32mm).

R2T15J1-T0250-B1

Outdoor, Ranger2 Termination, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range - .64-1.12 inch (16-28mm). Connector Type Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0. Conductor - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cable Mounting Bracket Material - Stainless Steel, Size .80-1.25 inch (20-32mm).
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 380 -Stranded or Compressed 750 Compact or Solid 900. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.

R2T28J4-N0380-B3

Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 380 -Stranded or Compressed 750 Compact or Solid 900. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. #1 Stranded to 1/0 Solid

R2T28J2-T0230

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. #1 Stranded to 1/0 Solid

Frequently Asked Questions

What voltage rating does this termination support?

This termination is rated for 35kV applications.

What conductor sizes are compatible with this termination?

The termination supports conductor sizes from 4/0 compact or solid to 250 kcmil stranded or compressed.

What insulation diameter range does this termination accommodate?

The termination is designed for insulation diameters between 0.84 and 1.38 inches.

What type of cable designs are compatible with this termination?

This termination works with concentric neutral or jacketed concentric neutral cable designs.

Is this termination suitable for outdoor installations?

Yes, this termination is designed for outdoor applications.

What connector type does this termination use?

The termination features an aluminum 2-hole spade connector rated #2-1250 kcmil.

How to Install the 35kV Ranger 2 Cable Terminator (R2T35J2)

A comprehensive guide for installing the 35kV Ranger 2 Cable Terminator (R2T35J2) on concentric and jacketed concentric neutral cables for indoor/outdoor applications. This guide covers cable preparation, lug installation, cleaning, and the final termination assembly.

Estimated time: 1h 30m

Tools needed:

Cable preparation tools, Measuring tape or ruler, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional), Vinyl tape

Supplies needed:

2 Silicone Rubber Termination Halves, Lubricant, 2 Strips Grey Silicone Rubber Tape, 2 Strips Sealing Mastic, 2 Gloves, Connector or Lug, Binding wire (optional)

  1. Ensure Safety and Prepare Cable

    DANGER: All apparatus must be de-energized during installation. Confirm the cable size fits within the kit's specified range. Train the cable into position and cut it to the required length, ensuring sufficient neutral wire length for grounding connection. Prepare the cable according to the specified dimensions for the jacket, semi-con, and conductor, allowing for terminal lug depth and additional exposed conductor distance for aluminum lug growth.

  2. Apply Mastic and Secure Neutral Wires

    Carefully wrap one band of sealing mastic around the cable jacket 1/4” (6mm) from the jacket end, stretching it 50%. Position the mastic precisely as it serves as a marker for the terminator. Bend the neutral wires back over the mastic, press them into the seal, and secure them to the cable jacket 4-6” (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the previously applied mastic, stretching it 50%. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4” (6mm) dimension.

  3. Install Lug or Connector

    Position the connector or lug onto the prepared conductor. Crimp the lug or connector according to its specific directions, ensuring not to crimp the last 1/4” to 3/8” of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.

  4. Clean Cable Insulation and Lug Barrel

    Wipe the cable insulation with an approved solvent. IMPORTANT: Do not allow the solvent to touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, not the semi-con insulation shield. Be careful not to reduce the cable insulation diameter below the kit's allowed range.

  5. Apply Initial Moisture Seal and Silicone Grease

    Create a track-resistant moisture seal between the termination insulator and the lug/connector by wrapping a band of gray silicone rubber tape around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, use the tape strip to build up the tape band equal to the insulation diameter. Liberally coat the edge of the semi-con insulation shield with silicone grease; this grease fills the step at the semi-con cut-off.

  6. Install Termination Body Halves

    For the lower termination with a fold-down skirt, pull the loose end of the removable core through the top until the core is flush with the bottom of the termination. Slide the first termination body onto the cable, aligning the terminator with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material. Using the second housing, carefully pull its core down to within one coil of the bottom. Slide this terminator over the cable, overlapping the first terminator by 1-1/2” (40mm), and carefully pull the core counter-clockwise to remove it.

  7. Finalize Termination and Grounding

    Apply a thin film of silicone lubricant to the skirt and mastic seal area. IMPORTANT: Do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1” and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them securely to the system ground. Finally, confirm that the High-K step does not exceed 1.5”.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.