ABB Installation Products R2T28M2-N0280-B2 Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/…
UPC: 075114362191
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 28kV outdoor-rated termination for tape shield, wire shield, or unshielded cables
- Supports 250 kcmil stranded/compressed or 300 kcmil compact/solid conductors
- Aluminum 2-hole spade connector (#2-1250 kcmil) for high-conductivity terminations
- Cable mounting bracket fits 1.10 to 1.50 inch (28-38mm) diameters
- Insulation range: .84 to 1.38 inches for 28kV-rated cables
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 250 to 300 kcmil |
Connection Type | 2-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Cable Mounting Bracket (1.10 to 1.50 inch) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 Termination |
Size | 0.84 inch - 1.38 inch (Cable Insulation Range) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15M1H0280-B2
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 280 -Stranded or Compressed 250 Compact or Solid 300. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
R2T28M4-N0330-B4
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 330 -Stranded or Compressed 500 kcmil or Compact or Solid 600 kcmil. Cable Mounting Bracket B4 - 1.80 to 2.40 inch (45-61mm).
R2IT15J4N0410
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30 inch - 2.10 inch, Connector Type N0 - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code 410 - Stranded or Compressed 1000.
R2T28M2-N0240
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0.
69TCT222130PABN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 2, Connection Type 2 - 2 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 30P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required
69TCT22N238PANN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 38P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
69TCT20N232PABN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 0, Connection Type - None, Connector Type - Copper, Conductor Size Code 32P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required
69TCT312233PABN
69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket RequiredFrequently Asked Questions
What is the voltage rating of the R2T28 termination?
The R2T28 termination has a voltage rating of 25/28 kV.
What is the maximum design voltage to ground for R2T28?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
What is the lightning impulse withstand voltage (BIL)?
The lightning impulse withstand voltage (BIL Dry 110 Withstand) for the R2T28 is 150 kV Crest.
What are the minimum strike and creepage distances?
The minimum strike distance is 14.5 in (368 mm), and the creepage distance is 22.8 in (579 mm).
What is the operating ambient temperature range for R2T28?
The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What mounting options are available for the R2T28?
The R2T28 termination can be free hanging or mounted with an optional bracket.
What is the maximum altitude for R2T28 operation?
The R2T28 termination is rated for an altitude range of 3300 feet max (1005 m).
What is the power system frequency range for R2T28?
The R2T28 termination is designed for a power system frequency range of 48 to 62 Hz.
What are the minimum strike and creepage distances?
The minimum strike distance is 14.5 in (368 mm), and the creepage distance is 22.8 in (579 mm).
What is the power system frequency range for R2T28?
The R2T28 termination is designed for a power system frequency range of 48 to 62 Hz.
How to Install the R2T15M4 Silicone Rubber Termination on Tape Shielded Cables
This guide provides detailed instructions for installing the 15kV Ranger 2 Shrink-fit Silicone Rubber Termination (R2T15M4) on tape shielded cables, covering cable preparation, ground braid installation, and final termination setup. Ensure all apparatus are de-energized before starting.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools, Crimping tool, Measuring tape or ruler, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, if needed)
Supplies needed:
R2T15M4 Silicone Rubber Termination kit, Silicone lubricant, Gray silicone rubber electrical tape, Constant force spring, Preformed ground braid, Sealing mastic, Copper foil tape, Gloves, Vinyl tape, Terminal lug or connector
- Prepare the Cable
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits within the insulation range specified in the Termination Selection Chart. Train the cable into position and cut it to the required length. Prepare the cable using the dimensions provided in Table 1, allowing for the depth of the terminal lug and additional exposed conductor distance for aluminum lug growth. Secure the edge of the tape shield with a single wrap of the supplied copper foil tape to prevent unrolling.
- Install the Ground Braid
Carefully wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, using 50% stretch, and cut it flush without overlapping. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket using vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block and previous mastic, maintaining the 1/4 inch (6mm) dimension, and cut it flush. Wrap two half-lapped layers of vinyl tape around the mastic seal. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid, cinch it after the final winding, and secure it with two wraps of vinyl tape. For cloth or paper semi-conductive shields, overwrap with one half-lapped layer of highly stretched semi-conductive rubber tape.
- Install the Terminal Lug or Connector
Check that the termination assembly fits over the selected lug. If it does not, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer’s directions, ensuring not to crimp the last 3/8 inch to 1/2 inch of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-conductive insulation shield. If abrasive material is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, not on the semi-conductive insulation shield. Be careful not to reduce the cable insulation diameter below the kit's allowed specifications.
- Install the Termination Body
Create a track-resistant moisture seal between the termination insulator and the lug/connector by wrapping a band of gray silicone rubber electrical tape around the base of the terminal lug. Adjust the number of tape layers (not exceeding two) if the barrel diameter is equal to or greater than the cable primary insulation, or form the tape band to equal the insulation diameter if the barrel is smaller. Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top until it is flush with the bottom of the termination. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue removing the core without pushing or pulling on the termination assembly.
- Complete Moisture Seal and Ground Connection
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.