ABB - Installation Products 69TCT22N238PANN - 69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 38P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
ABB - Installation Products

69TCT22N238PANN

UPC: 783786544714


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Overview

This ABB 69kV Transmission Cable Terminator (SKU: 69TCT22N238PANN) is engineered for high-voltage power transmission applications. It features a Housing Size 3, designed to accommodate specific cable dimensions. The terminator utilizes a copper connector for reliable current transfer and is specified for Conductor Size Code 38P, indicating compatibility with a defined range of conductor cross-sections. The metallic screen kit includes a flat braid for effective shielding, and the armour kit comprises jacketing tape and mastic for robust cable protection. This configuration does not require a separate bracket for installation, simplifying the mounting process. The UNSPSC code 26121648 categorizes this product within electrical power transmission and distribution equipment. ABB's Installation Products division delivers reliable components for critical infrastructure. This terminator is a key element in ensuring the integrity and safety of 69kV transmission cable systems, providing secure termination and protection against environmental factors and electrical stresses. Its design prioritizes efficient installation and long-term operational performance in demanding electrical networks.
  • 69kV Transmission Cable Terminator
  • Housing Size 3
  • Copper Connector Type
  • Conductor Size Code 38P
  • Includes Flat Braid Metallic Screen Kit and Jacketing Tape/Mastic Armour Kit

Specifications

Application
Cable Terminations, 69kV
Cable Type
Copper Tape Shielded Wire
Color
Gray
Conductor Size
0.936 to 1.011 in
Earthing
Products Includes Their Own Grounding System
Mounting
No Bracket Required
Number Of Terminals
(1) Single Phase
Special Features
Molded EPDM Elastomer Housing is Durable under Severe Envoronmental Conditions. Lightweight and easy to Handle
Standard
IEEE 48 and IEC-840
Type
Cable Termination
Voltage Rating
69 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3 - Bore Diameter 1.975 inch, Type of Connection - None, Connector Type - None, Conductor Size - None, Metallic Screen Kit - None, Armour Kit - Heat Shrink, No Bracket Required

69TCT23NNNNNNBN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3 - Bore Diameter 1.975 inch, Type of Connection - None, Connector Type - None, Conductor Size - None, Metallic Screen Kit - None, Armour Kit - Heat Shrink, No Bracket Required
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 0, Connection Type - None, Connector Type - Copper, Conductor Size Code 32P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required

69TCT20N232PABN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 0, Connection Type - None, Connector Type - Copper, Conductor Size Code 32P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required
69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required

69TCT312233PABN

69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 2, Connection Type 2 - 2 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required

69TCT-222-133P-AAN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 2, Connection Type 2 - 2 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 42P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required

69TCT23N242PABN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 42P, Metallic Screen Kit - Flat Braid, Armour Kit - Heat Shrink, No Bracket Required
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type 4 - 4 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 43P, Metallic Screen Kit - 1/0 Bonding Cable 6 foot quantity 1 with split Bolts Quantity 2, Armour Kit - not required, No Bracket Required

69TCT234143PBNN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type 4 - 4 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 43P, Metallic Screen Kit - 1/0 Bonding Cable 6 foot quantity 1 with split Bolts Quantity 2, Armour Kit - not required, No Bracket Required
69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required

69TCT312233PAAN

69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 46P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required

69TCT23N246PAAN

69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 46P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required

Frequently Asked Questions

What is the AC withstand rating for the 69TCT?

The AC withstand rating is 175 kV for 60Hz 1 Minute Dry.

What is the partial discharge rating of the 69TCT?

The partial discharge is less than 3pC at 60kV.

What items are included in the 69TCT Terminator kit?

Each kit contains one TCT Terminator, one instruction sheet, one conductive paint package, and two mastic tapes.

Does the 69TCT Terminator require surface oil or grease?

No, the non-tracking polymer requires no surface oil or grease to maintain its non-tracking properties.

What material is the 69TCT Terminator housing made of?

The housing is made of molded EPDM elastomer, which is durable under severe environmental conditions.

What is the weight of the 69TCT Terminator?

The 69TCT Terminator is lightweight, weighing 14kg (30.1 lb.).

What conductor sizes can the 69TCT Terminator accommodate?

It accommodates conductor sizes from 90mm2 (4/0) to 1700mm2 (3500 kcmil).

What cable insulation diameters does the 69TCT accommodate?

The 69TCT Terminator is designed for solid dielectric cables with insulation diameters up to 86.4mm (3.400 inches).

What is the maximum working voltage for the 69TCT?

The maximum working voltage for the 69TCT Terminator is 72.5 kV.

What is the nominal voltage of the 69TCT Terminator?

The nominal voltage (Uo/U) for the 69TCT Terminator is 40kV/59kV.

How to Install the ELASTIMOLD TCT Outdoor Transmission Cable Termination

This guide provides detailed, step-by-step instructions for the safe and proper installation of the ELASTIMOLD TCT outdoor transmission cable termination, including cable preparation, assembly, grounding, and final mounting.

Estimated time: 4h

Tools needed:

Measuring Tape, Cable Stripping Tool, Hose Clamp, Cable Cleaner, Winch Assembly, Crimping Tool, Wire Brush, Soldering Iron, Heat Gun, Screwdriver

Supplies needed:

Spade Contact (2 or 4 hole), Heat Shrink Sleeve, Semi-conductive Paint (supplied with kit), Vinyl Tape, Lubricant (supplied with kit), Mastic, Scintillation Ring, #12 AWG Copper Drain Wire, Flat Braid, Silicone Tape, Mounting Hardware for Supporting Structure (customer supplied)

  1. Prepare the Cable End

    DANGER: All apparatus must be de-energized during installation. Straighten the cable and place it in its final position, using the spade contact as a guide. Square cut the cable and note the depth 'X' of the spade contact hole. Carefully remove the outer jacket material to expose the cable shield, measuring 45.5 inches (111.6 cm) from the end of the cable. Slide the heat shrink sleeve onto the cable.

  2. Remove Shield and Non-Metallic Screen

    Remove the cable shield to a distance of 43.5 inches (110.5 cm) from the end of the cable. Remove the non-metallic screen, measuring 40 inches (101.5 cm) from the end of the conductor. Do not cut or nick the exposed insulation, as this could result in cable failure. Chamfer the non-metallic screen edge for a minimum of 1/2 inch (1.5 cm).

  3. Cut and Chamfer Cable Insulation

    Using a hose clamp as a guide, square cut the cable insulation at a distance of X+1 inch from the end of the conductor, being careful not to nick the conductor (refer to Step 1 for 'X' measurement). Remove the hose clamp. Sand out all nicks and abrasions on the extruded non-metallic screen chamfer and cable insulation. Chamfer the edge of the cable insulation for approximately 3 inches (7.5 cm).

  4. Clean and Paint Cable Insulation

    Using cable cleaner, clean the cable insulation and extruded non-metallic screen, cleaning towards the outer jacket to prevent semi-conductive particles from contaminating the insulation. Place a vinyl tape marker on the cable insulation surface at 39.5 inches (100.5 cm) from the end of the conductor. Stir the supplied semi-conductive paint well. Paint the exposed insulation and a minimum of 1 inch (2.5 cm) of the extruded non-metallic screen. Remove the vinyl tape within 5 to 15 minutes, ensuring the paint edge is smooth and square. Allow the paint to dry for 60 minutes.

  5. Assemble Clamps and Lubricate Cable

    Place a vinyl tape marker onto the cable non-metallic shield 2 inches (5 cm) from the edge of the paint. Assemble the Cable Clamp at least 55 inches (140 cm) back from the conductor and tighten it securely. Place the Winch Assembly in front of the Cable Clamp and attach its stationary hooks to the Cable Clamp. Attach the Adapter Plates to the Housing Clamp with the supplied bolts. Assemble the Housing Clamp around the Terminator Base Section. Extend the steel cable(s) on the Winch Assembly until the hooks reach the Housing Clamp, then hook the cables to the Housing Clamp. Thoroughly lubricate the cable in the specified area and direction with the supplied lubricant; do not substitute.

  6. Install Terminator Sections

    Assemble the Terminator Base Section onto the cable approximately 12 inches from the end of the conductor. Release tension on each steel cable, then extend the steel cables and Housing Clamp. Position the Terminator Module Section in the Housing Clamp. Install the units until they overlap and continue assembling the mated units until the Terminator Base Section is flush with the tape marker. Remove the Winch Assembly, Housing Clamp, Adapter Plate, and Cable Clamp.

  7. Connect Conductor and Apply Mastic

    Remove the tape marker on the insulation shield. Remove the cut section of insulation on the cable to expose the conductor. Wirebrush the conductor of the cable and immediately insert it into the spade contact. Crimp the connector according to the enclosed crimping instructions. Remove any excess inhibitor where applicable. Apply two layers of mastic: one at the end of the stress cone and one 2 inches (5 cm) back from the end of the cable jacket.

  8. Install Grounding and Seal Terminator

    Install the scintillation ring and the #12 AWG copper drain wire. Solder the flat braid and the #12 drain wire to the shield. Apply a second layer of mastic over the drain wire, on top of the previously applied mastic around the base of the stress cone. Apply a second layer of mastic over the flat braid, on top of the previously applied mastic on the cable jacket. Slide the heat shrink sleeve up to the grounding eye of the terminator base. Apply heat to the sleeve, starting in the middle and continuing towards each end, until mastic sealer squeezes from the ends. Connect the flat braid to the system ground. Seal the cable end with mastic tape between the contact and cable insulation. Apply two half-lapped layers of silicone tape covering the crimp connector, mastic tape, and the upper portion of the terminator skirt.

  9. Mount Terminated Cables

    Mount the terminated cables to a supporting structure (supplied by customer). Ensure a minimum clearance of 4.0 inches (10 cm) between the terminator stress cone base and the supporting structure. Ensure a minimum clearance of 44.0 inches (112 cm) from the supporting structure to the end of the terminator. DANGER: All apparatus must be installed and operated in accordance with individual user, local, and national work rules. Do not touch or move energized products.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.