Overview
- Supports tape shield, wire shield, and unshielded cables (0.64–1.12" insulation diameter)
- One-hole aluminum spade connector for #2 AWG to 500 kcmil conductors (stranded/compressed 250 kcmil or solid 300 kcmil)
- Stainless steel B2 mounting bracket (1.10–1.50" O.D.) for secure outdoor installation
- Shrink-fit silicone housing with pull-down jacket seal for simplified field installation
- Four sheds for 15kV outdoor model; optional insulating sleeves for enhanced creepage protection
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 250 to 300 kcmil |
Connection Type | 1-Hole Spade #2-500 kcmil |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.64 inch - 1.12 inch (Insulation), 1.10 inch - 1.50 inch (Mounting Bracket) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2IT15M2N0280
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 250 / Compact or Solid 300.
R2T15M1-T1270-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed 4/0 /Compact or Solid 250. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2T15M1-T0230
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0.
R2T15M1-T0240
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 1/0/ Compact or Solid 2/0.
R2T15M1-N0240
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1/0/ Compact or Solid 2/0.
R2T15M1-N0330
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 500 Stranded/Compressed or 600 Compact/Solid
R2T15M1-T1230-B1
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed #1 /Compact or Solid 1/0. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)
R2T15M1-N0230
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0.Frequently Asked Questions
What is the IEEE classification for the R2T15 outdoor termination?
The R2T15 outdoor termination has an IEEE Classification of Outdoor = Class 1A.
What installation instructions are provided with the R2T15 kit?
The kit includes specific installation instructions: IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is the power system frequency range for the R2T15?
The R2T15 cable termination is designed for power system frequencies ranging from 48 to 62 Hz.
What is the maximum altitude for R2T15 installation?
The R2T15 cable termination can be installed at a maximum altitude of 3300 feet (1005 m).
What types of cables are compatible with the R2T15?
The R2T15 units accommodate popular XLP and EPR cable types and shield constructions. They cover a range from #2 AWG to 1250 kcmil.
What is the operating temperature range for the R2T15?
The R2T15 cable termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the voltage rating of the R2T15 cable termination?
The R2T15 cable termination has a voltage rating of 15 kV. Its maximum design voltage to ground is 9.5 kV.
What cable sizes are compatible with the R2T15 termination?
The R2T15 termination accommodates insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil cables. It supports XLP and EPR cable types.
What installation instructions are provided with the R2T15 kit?
The kit includes specific installation instructions: IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is the operating temperature range for the R2T15?
The R2T15 cable termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
How to Install the R2T15M1/R2T28M Shrink Fit Silicone Rubber Termination
This guide provides detailed instructions for installing the 15kV and 28kV Ranger 2 Shrink Fit Silicone Rubber Termination on various cable types, including tape shield, wire shield, and UniShield® cables. It covers cable preparation, ground braid installation, lug/connector attachment, and the final termination body installation.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Wire strippers, Soldering iron, Utility knife, Solvent applicator pads, Aluminum oxide abrasive (120 grit or finer), Measuring tape or ruler
Supplies needed:
R2T15M1/R2T28M Shrink Fit Silicone Rubber Termination kit (includes termination, lubricant, gray silicone rubber tape, constant force spring, preformed ground braid, sealing mastic, copper foil tape, gloves), Vinyl electrical tape, Terminal lug or connector, Approved solvent, Oxide inhibitor (for aluminum lugs), Scotcht No. 13 semi-conductive rubber tape (if applicable)
- Prepare the Cable
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits within the termination's insulation range. Train the cable into position and cut it to the required length for installation. Prepare the cable by removing the jacket, shield (tape, wire, or semi-conductive jacket for UniShield®), and semi-conductive layer according to the specified dimensions, allowing for the depth of the terminal lug and any growth allowance for aluminum lugs. For tape shield cables, secure the tape shield edge with a single wrap of the supplied copper foil tape. For wire shield cables, bend the leading 1-1/2" (38mm) of exposed shield wires back to the jacket edge. For UniShield® cables, follow specific instructions for removing the semi-conductive jacket and managing shield wires.
- Install the Ground Braid
Carefully wrap one band of sealing mastic (using 50% stretch) around the cable jacket 1/4" (6mm) from the jacket end. Position the preformed ground braid with the short tail over the cable shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket using vinyl tape and press the solder block firmly into the mastic. Apply a second mastic band (50% stretch) over the solder block and the previously applied mastic, maintaining the 1/4" (6mm) dimension, and cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal. Wrap the ground braid around the cable shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid, cinch (tighten) it after the final winding, and secure it with two wraps of vinyl tape. SPECIAL NOTE: If the cable has a cloth or paper semi-conductive insulation shield, overwrap it with one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotcht No. 13.
- Install the Lug or Connector
Check to ensure the termination assembly fits over the selected lug. If the lug will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug; do not remove the core at this time. Position the connector or lug and crimp it according to the manufacturer’s directions. Do not crimp the last 3/8" to 1/2" of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges following crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, avoiding the semi-conductive insulation shield. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
- Install the Termination Body and Complete Seals
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber electrical tape around the base of the terminal lug. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If the barrel diameter is smaller, use the tape strip to form the tape band equal to the insulation diameter. Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core. Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate the skirt tabs). Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1" and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5".
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.