ABB Installation Products R2T15L4-N0410 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10…
UPC: 783786778485
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Shrink-fit housing with pull-down jacket seal for reliable outdoor terminations
- Covers cable insulation diameters from 1.30 to 2.10 inches (#2 AWG to 1250 kcmil)
- Non-tracking silicone housing with superior weathering and memory retention
- Four-shed design maximizes creepage and strike distances for long-term performance
- Field-removable center core simplifies installation and maintenance
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Corrugated Shielded Wire |
Color | Gray |
Conductor Size | 1000 kcmil |
Connection Type | Aluminum 2-Hole Spade #2-1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Frequency | 60 Hz |
Material | Silicone |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Outdoor |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 1.30-2.10 inch insulation diameter |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15M4-N0410-B3
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N0 - Alunimum 2-Hole Spade #2-1250 kcmil, Conductor Code 410 - Compressed 1000, Cable Mounting Bracket B3 - Material Stainless Steel - Size - 1.45 inch to 1.95 inch (37mm - 50mm)
R2T15J4N0410-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15J1-N0240-B1
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B1 - Stainless Steel - Size .80 inch - 1.25 inch.
R2T15J1-N0230
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed #1 /Compact or Solid 1/0.
R2T15J1-N0220
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 220 -Stranded or Compressed #2 Compact or Solid #1.
R2T15J1-N0210
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 210 -Stranded or Compressed N/A Compact or Solid #2.
R2T15J1-H0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 1-Hole Spade connector for #2 to 500 kcmil. 4/0 Stranded or 250 kcmil Solid
R2T15J1-H0240
Outdoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor 1/0 Stranded/Compressed or 2/0 Compact/SolidFrequently Asked Questions
What is the maximum design voltage to ground for R2T15?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
How many sheds does the 15kV outdoor model have?
The 15kV outdoor model of the R2T15 termination features four sheds.
What is the power system frequency range for R2T15?
The R2T15 termination is designed for a power system frequency range of 48 to 62 Hz.
What is the IEEE classification for the R2T15 outdoor termination?
The R2T15 outdoor termination has an IEEE Classification of Class 1A.
What is the maximum altitude for R2T15 installation?
The R2T15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What is the operating temperature range for the R2T15?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the voltage rating of the R2T15 termination?
The R2T15 termination has a voltage rating of 15 kV.
What cable sizes does the R2T15 termination support?
The R2T15 termination covers insulation diameter cables from 0.64 inches (16 mm) to 2.10 inches (53 mm), accommodating #2 AWG through 1250 kcmil.
How many sheds does the 15kV outdoor model have?
The 15kV outdoor model of the R2T15 termination features four sheds.
What is the maximum design voltage to ground for R2T15?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
How to Install the Ranger 2 Shrink Fit Silicone Rubber Termination
This guide provides step-by-step instructions for preparing the cable, installing the ground braid, connecting the lug, and finally installing the Ranger 2 Shrink Fit Silicone Rubber Termination (e.g., R2T15L4) for high voltage indoor/outdoor applications.
Estimated time: 2h
Tools needed:
Cable stripping tools, Crimping tool, Measuring tape, Utility knife, Scissors, Clean cloths/pads
Supplies needed:
Ranger 2 Shrink Fit Silicone Rubber Termination kit (including termination body, ground braid, constant force spring, silicone rubber tape, sealing mastic, lubricant, gloves), Terminal lug or connector, Vinyl electrical tape, Cable cleaning solvent, Aluminum oxide abrasive (optional)
- Prepare the Cable
DANGER: Ensure all apparatus is de-energized before beginning installation. Confirm the cable size fits within the kit's specified range. Train the cable into its final position and cut it to the required length. Prepare the cable by removing the jacket, insulation, semi-con, and exposing the conductor according to the dimensions provided in Table 1 and the growth allowance for the terminal lug.
- Install the Ground Braid
Carefully wrap one band of sealing mastic around the cable jacket, 1/4 inch (6mm) from the jacket end, using a 50% stretch. Position the preformed high-amp ground braid with its 'U' section over the metallic shield, adjacent to the cable jacket edge. Secure one tail of the ground braid over the cable jacket with vinyl tape, ensuring the solder block is centered over the mastic strip. Press the solder block into the mastic. Wrap the ground braid around the metallic shield and secure it with the constant force spring, cinching it tightly. Wrap two half-lapped layers of vinyl tape around the spring and exposed metallic shield, leaving 1 inch (25mm) of semi-con insulation exposed. Apply a second mastic strip over the solder block and previous mastic. Wrap two half-lapped layers of vinyl tape around the mastic seal, maintaining the 1/4 inch (6mm) dimension, and secure the ground braid to the cable jacket.
- Install the Terminal Lug or Connector
Verify that the termination assembly will fit over the selected terminal lug or connector. If it does not, clean the cable insulation and slide the termination body onto the cable before installing the lug. Do not remove the core at this stage. Position the connector or lug and crimp it according to the manufacturer's directions, ensuring not to crimp the last 3/8 inch to 1/2 inch of the connector. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation thoroughly with solvent-saturated pads. Exercise caution to prevent the solvent from touching the semi-con insulation shield. If an abrasive must be used, apply it only to the insulation, not the semi-con shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's allowed range.
- Install the Termination Body
IMPORTANT: Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber electrical tape from the kit. Wrap a band of silicone tape around the base of the terminal lug; use no more than two layers if the barrel diameter is equal to or greater than the cable primary insulation, or build up the tape to match the insulation diameter if the barrel is smaller. Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until it is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end, ensuring the terminator body remains butted against the leading edge of the mastic seal. Do not push or pull the termination assembly while removing the core. Apply a thin film of silicone lubricant to the skirt and mastic seal area, avoiding the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect both ground braids to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.