ABB Installation Products R2IT15M2-N0300 Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/…
UPC: 075114122771
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- ABB Ranger2 Indoor Termination, 15kV rated
- Accommodates tape shield, wire shield, and unshielded cable types
- Insulation diameter range: 0.84 inch - 1.38 inch
- Aluminum 2-hole spade connector for #2 - 1250 kcmil conductors
- Supports 300 kcmil (Stranded/Compressed), 350 kcmil (Compact), 400 kcmil (Solid) conductors
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 350 to 400 kcmil |
Connection Type | Aluminum 2-Hole Spade #2-1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84 inch - 1.38 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J1-N0300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2IT15M2-N0290
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 300 kcmil stranded or 350 kcmil Solid
R2IT15M2-N0310
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 400 kcmil Stranded or 500 kcmil Solid
R2IT15M1N2300
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 350/ Compact or Solid 400.
R2IT15M1-N0240
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0.
R2IT15J1-N0270
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250.
R2IT15J1-N0250
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-1250 kcmil, Conductor Code - 250 -Stranded or Compressed 2/0 Compact or Solid 3/0.
R2IT15J1-N0220
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-1250 kcmil, Conductor Code - 220 -Stranded or Compressed #2 Compact or Solid #1.Frequently Asked Questions
What is the operating temperature range for this product?
The ambient temperature range for operation is -22 to +149 °F (-30 to +65 °C).
What cable sizes are compatible with this termination?
The termination covers cable sizes from #2 AWG through 1250 kcmil.
What cable insulation diameters does it accommodate?
It accommodates insulation diameter cables from 0.64 in (16 mm) to 2.10 in (53 mm).
What is the voltage rating of this termination?
The R2IT15 cable termination has a voltage rating of 15 kV.
What is the maximum altitude for installation?
The maximum altitude range for installation is 3300 feet (1005 m).
What is the IEEE classification for this indoor termination?
The IEEE classification for this indoor termination is Class 2.
What are the available sizes for the R2IT15 termination?
The R2IT15 termination is available in sizes 1, 2, and 4.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2IT15 is 9.5 kV.
What is the power system frequency range?
The power system frequency range for this termination is 48 to 62 Hz.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2IT15 is 9.5 kV.
How to Install the 15kV Ranger 2 Shrink-fit Silicone Rubber Termination
This guide provides step-by-step instructions for installing the 15kV Ranger 2 Shrink-fit Silicone Rubber Termination on high voltage cables for indoor applications. It covers cable preparation, ground braid installation, lug connection, and termination placement. DANGER: Ensure all apparatus are de-energized before beginning installation.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools, Crimping tool, Solvent applicator pads, Aluminum oxide abrasive (grit 120 or finer, if needed)
Supplies needed:
15kV Ranger 2 Shrink-fit Silicone Rubber Termination kit, Copper foil tape (for tape shield cables), Vinyl electrical tape, Cable connector or lug, Cable cleaning solvent, Oxide inhibitor (for aluminum lugs), Semi-conductive rubber tape (e.g., Scotch No. 13, if applicable)
- Prepare Cable
Ensure the cable size fits the termination chart. Train the cable and cut to the required length. Prepare the cable by removing the jacket, semi-conductive layer, and insulation according to the specified dimensions, allowing for terminal lug depth and aluminum lug growth. For tape shielded cables, secure the tape shield edge with a single wrap of supplied copper foil tape to prevent unrolling.
- Install Ground Braid
Wrap one band of vinyl tape 1/4 inch (6mm) from the cable jacket end as a marker. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the vinyl tape. Secure the ground braid to the cable jacket with vinyl tape. Apply a second vinyl tape band directly over the first and the solder block, maintaining the 1/4 inch (6mm) dimension. Wrap the ground braid around the cable tape shield once, trim excess, and secure with the constant force spring, wrapping in the same direction and cinching the final winding. Secure the spring with two wraps of vinyl tape. If using cloth or paper semi-con insulation shield, overwrap with one half-lapped layer of highly stretched semi-conductive rubber tape.
- Install Lug or Connector
Verify the termination assembly fits over the selected lug. If not, slide the termination onto the cable before installing the lug, but do not remove the core yet. Position the connector or lug and crimp it according to the manufacturer's instructions. Do not crimp the last 3/8 to 1/2 inch of the connector. After crimping, remove any excess oxide inhibitor and all sharp crimp flashings or edges.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation thoroughly with solvent-saturated pads. Exercise caution to prevent the solvent from touching the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive, grit 120 or finer, and apply it solely to the insulation. Do not use abrasive on the semi-conductive insulation shield, and ensure the cable insulation diameter is not reduced below the kit's specified allowance.
- Install Termination
Apply a liberal coating of silicone grease to the edge of the semi-conductive insulation shield to fill the step at the cut-off. Carefully slide the termination body onto the cable, aligning its edge with the forward edge of the vinyl tape marker. Begin to remove the core by pulling counter-clockwise. Continuously recheck the termination's position as you remove the core. Avoid pushing or pulling on the termination assembly during this process. Finally, connect the ground braid to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.