ABB Installation Products K655BLR-N0400 600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.515 inch to…
UPC: 783786417964
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Accommodates cables with 1.515" to 1.780" insulation diameter
- Aluminum compression lug supports compressed stranded conductors up to 900 AWG and solid conductors up to 1000 AWG (500 mm²)
- Elbow design simplifies installation in tight spaces and reduces cable stress
- Includes stud for secure mounting and lubricant tube (82-08) for optimal installation
- Compatible with copper and bi-metal conductors; no test point for streamlined installation
Specifications
Application | 400 Amps |
Connection | Compression |
Connection Type | Compression Lug |
Material | Aluminum |
Series | 600 |
Size | 1.515-1.780 inch (insulation diameter) |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Elbow without Test Point |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.0000 L |
Package Weight (Metric) | 1.8140 kg |

K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
K655BLR-K0320
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 450 /Solid 500/550.
K655BVS-L2-M0380
600 Amp, 15/25KV, DeadBreak, Vault Stretcher Housing Only, with stud, 2-Way, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655VS-L2-M0380
600 Amp, 2 Way Vault Strecher Kit, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
675-7 TIN
Copper Tin Plated Stud, 4-9/64 inch long with 5/8-11 UNC-2A Threads on both ends. Center section not threaded.Frequently Asked Questions
What is the cable insulation diameter range for this elbow?
This ABB 600 Series Elbow is designed for cables with an insulation diameter ranging from 1.515 inches to 1.780 inches.
What conductor sizes does the aluminum compression lug support?
The aluminum compression lug supports compressed stranded conductors up to 900 AWG and solid conductors up to 1000 AWG (500 mm²).
Does this elbow have a test point?
No, this ABB 600 Series Elbow is specified as having 'out Test Point'.
What material is the compression lug made of?
The compression lug on this ABB 600 Series Elbow is made of aluminum.
What is the manufacturer of the K655BLR-N0400?
The manufacturer of the K655BLR-N0400 is ABB - Installation Products.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 655/675LR and K655/K675LR deadbreak elbow connectors. These connectors create fully shielded, submersible deadfront cable connections for high voltage apparatus rated for 15kV and 25kV class systems.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Capacitive voltage sensing device, Torque wrench (for mating parts), Screwdriver
Supplies needed:
Lubricant (supplied with kit), No. 14 AWG Copper equivalent grounding wire, Suitable grounding connector, Silicone lubricant (for test point cap), Waterproofing material (for cable jacket)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Verify that all components are complete, undamaged, and compatible with the cable and mating products. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare the Cable
Position the cable with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm). Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the dimensions specified in the documentation for your cable type.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Lug
Remove any protruding cable insulation by cutting it even with the end of the cable adapter, taking care not to nick the adapter or conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). For aluminum conductors, wire brush the conductor immediately before insertion. Fully insert the conductor into the compression lug. Measure the 'Check Dimension' before crimping (must be less than 6-3/8 inches). Crimp the compression lug according to its supplied instructions. Wipe off any excess inhibitor and verify the post-crimp distance from the lug end to the cable adapter is 6-3/8 to 7-1/8 inches (162mm-181mm).
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect to Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, aligning the compression lug hole with the stud. If connecting a second mating part, clean, lubricate, insert, and torque it according to its instructions. If using an insulating plug, clean, lubricate, and push the voltage detection cap onto the elbow until it snaps into place.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper equivalent grounding wire through the grounding eye, twist to form a small loop, and connect it to ground using a suitable connector. Ensure the cable shield is grounded according to the instructions for your grounding device or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable capacitive sensing device, following its manufacturer's directions, to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.