ABB Installation Products K655VS-L2-M0380 600 Amp, 2 Way Vault Strecher Kit, 15/25KV, Cable Insulation Diameter 1.370 inch to…
UPC: 783786430512
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetric momentary withstand
- Supports 15/25kV voltage class with 140kV BIL and 45kV AC withstand
- Fully shielded, submersible molded rubber housing with peroxide-cured EPDM
- Accommodates cable insulation diameters from 1.370" to 1.630"
- Compatible with compressed stranded (700-750 kcmil) and compacted solid (900 kcmil) conductors
Specifications
Application | 400 Amps |
Connection | Compression |
Current Rating | 600 A |
Material | Aluminum |
Series | K655VS |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | 2-Way Vault Stretcher Kit |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
675-7 TIN
Copper Tin Plated Stud, 4-9/64 inch long with 5/8-11 UNC-2A Threads on both ends. Center section not threaded.
756LINKC-DP0578743
600 Amp, 35KV, Retrofit Cam-Op Connector Kit, with capacitive test point, ( 756LINK-C-VB-L0300-BRK-DRG-ISO). VB - Visi-Break. L0300 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 350 or Compacted/Solid 400. DRG - Insulating Cap. ISO - International Standard Organization.
K650BIPVS
Insulating Plug with Cap, 600 Amp, 15/25KV. 600/900 Amp deadbreak Voltage Sensing Plug with Lubricant and Installation Instructions
750J3-U
600 Amp Elbow Connector, 3-Way Junction, DeadBreak, 35KV, Rubber Junction with Stainless Steel Mounting Plate, Back Plate and adjustable Mounting Bracket
167-31-1
White Identification Band with Black Stripe, for 3-Phase Loadbreak Elbow. Length 9 inch, Width 1/2 inch, Thickness .025 inch.Frequently Asked Questions
What is the maximum cable insulation diameter supported?
The K655VS-L2-M0380 supports cable insulation diameters ranging from 1.370 inches to 1.630 inches.
What conductor sizes are compatible with this stretcher kit?
This kit is compatible with compressed stranded conductors from 700/750 kcmil and compacted solid conductors up to 900 kcmil.
What is the voltage rating for this ABB vault stretcher kit?
The K655VS-L2-M0380 is rated for 15/25KV applications.
What type of lug is included in this kit?
The kit includes an aluminum compression lug for electrical connections.
What is the current rating of the K655VS-L2-M0380?
The K655VS-L2-M0380 has a current rating of 600 Amps.
How to Install the Elastimold 655VS/K655VS Deadbreak Vault Stretcher
This guide provides step-by-step instructions for the safe installation and connection of the Elastimold 655VS or K655VS Deadbreak Vault Stretcher, including cable preparation, crimping, and final assembly for 15kV and 25kV class systems.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Measuring tape or ruler, 5/8 inch bolt and nut (for lug alignment)
Supplies needed:
Elastimold 655VS or K655VS Deadbreak Vault Stretcher, Cable Adapters (2), Compression Lugs (2), Insulating Plugs (2), Lubricant, Stud Prepack, Suitable grounding wire (min. No. 14 AWG copper), Suitable grounding connectors
- De-energize Apparatus and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Ensure all components fit properly with the cable and/or mating products. Read all instructions before starting and have all required tools ready.
- Prepare Concentric Neutral Cable (if applicable)
For concentric neutral cable, overlap both cables and cut to 14 inches (355mm) from the centerline of the joint. Bend back the concentric neutral wires.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back neutrals.
- Prepare Cable Jacket and Shield
Follow the specific instructions for your cable type (20MA/21MA grounding device, 600ECS jacket cable seal, Unishield/Lead Sheath, or Jacketed/Non-Jacketed cable) to remove the outer jacket (if applicable) and prepare the cable as shown in the product documentation, including specific dimensions for insulation, semi-con shield, and tape markers.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Cable Insulation and Verify Conductor Length
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Be careful not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches and 4-11/16 inches (111mm-119mm). If not, redo the assembly.
- Insert Conductor into Compression Lug and Align
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-1/2 inches. Align the flat portions of the compression connector using a 5/8 inch bolt as a temporary locator.
- Crimp Compression Lug
Hold the compression connector in the proper position and make the first crimp connection 3-1/2 inches from the open end of the compression fitting at the mark indicated. Rotate each successive crimp 180 degrees to prevent bowing. Carefully wipe excess inhibitor from the outside of the connector and cable insulation. Verify the connector end is 6-1/2 inches to 7-1/4 inches (165mm-184mm). Remove any sharp flash from the crimp.
- Install Vault Stretcher Body onto Cable Adapter
Lubricate the inside of the vault stretcher body and the outside of the cable adapter. Using a rotating motion, slip the body onto the cable adapter. Ensure the compression lug aligns and seats with the inside mating portion of the vault stretcher. Push the compression lug until it cannot advance further, ensuring the base of the adapter remains aligned with the marking tape.
- Connect Opposite Cable to Vault Stretcher
To insert the opposite cable, push the vault stretcher and compression lug sideways until the compression lug enters the open end of the vault stretcher body. Slowly push both units toward their final alignment, ensuring the lubricated adapter slides into position.
- Final Alignment and Tape Removal
Check the location of the compression lug through the viewing hole of the vault stretcher. When fully seated, ensure both cable adapters are still flush with their respective tape markers. If not, reposition the cable adapters. Once confirmed, remove the tape markers.
- Install Special Conversion Stud and Connect Mating Parts
NOTE: A special stud (650VSA) 1/2 inch longer than the standard stud must be used. DANGER: DO NOT connect or disconnect mating products while energized, and DO NOT energize while disconnected. Remove protective caps. Hand tighten the supplied stud into one mating part. Clean and lubricate the vault stretcher and both mating parts. Insert the mating part into the elbow, engage threads, hand tighten, and then torque according to the mating part's instructions.
- Install Insulating Plug and Voltage Detection Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground Concentric Neutral Cable
Insert one end of a wire (with ampacity at least equivalent to No. 14 AWG copper) through a grounding eye and twist to make a small loop. Repeat for the other grounding eye, being careful not to damage the eyes. Connect these wires to ground using suitable connectors.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.