ABB Installation Products K655BLR-K0330 600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to…
UPC: 783786646210
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Medium-voltage elbow connector for reliable electrical terminations.
- Aluminum compression lug for robust conductor connection.
- Designed for cable insulation diameters from 1.090" to 1.310".
- Supports compressed stranded conductors up to 500 AWG and solid conductors up to 600 AWG.
- Includes stud for direct attachment and no test point for simplified installation.
Specifications
Application | 400 Amps |
Connection | Compression |
Connection Type | Elbow with stud |
Connection Type | Elbow with Stud, Compression Lug |
Current Rating | 600 A |
Material | Aluminum |
Series | 600 |
Series | 600 Series |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Elbow without Test Point |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.0000 L |
Package Weight (Metric) | 1.8140 kg |

756LINKC-DP0578743
600 Amp, 35KV, Retrofit Cam-Op Connector Kit, with capacitive test point, ( 756LINK-C-VB-L0300-BRK-DRG-ISO). VB - Visi-Break. L0300 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 350 or Compacted/Solid 400. DRG - Insulating Cap. ISO - International Standard Organization.
K650BIPVS
Insulating Plug with Cap, 600 Amp, 15/25KV. 600/900 Amp deadbreak Voltage Sensing Plug with Lubricant and Installation Instructions
750J3-U
600 Amp Elbow Connector, 3-Way Junction, DeadBreak, 35KV, Rubber Junction with Stainless Steel Mounting Plate, Back Plate and adjustable Mounting Bracket
167-31-1
White Identification Band with Black Stripe, for 3-Phase Loadbreak Elbow. Length 9 inch, Width 1/2 inch, Thickness .025 inch.
755LINK-BLRM0300ADRG
600 Amp, 35KV, Cam-Op Kit, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
1601-348
Gasket, Inside Diameter Diameter 2-59/64 inch, Outside Diameter 3-27/64 inch. Thickness of Gasket 3/16 inch. Oil Resistant Rubber Material.
756LINKC-DP0578805
600 Amp, 35KV, Cam-Op Connector Kit, with capacitive test point, (LR-L0300-BRK-DRG-ISO). L0300 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 350 or Compacted/Solid 400. DRG - Insulating Cap. ISO - International Standard Organization.Frequently Asked Questions
What products are compatible with the K655BLR elbow housing?
The K655BLR can be mated with Elastimold® products including K651CP, K650BIP, K650RTP, K650RTW, K650S1, K650J2, K650J3, or K650J4.
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What is the maximum operating voltage for the 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV and phase-to-phase is 28kV.
What is the continuous current rating of the elbow housing?
The K655BLR elbow housing has a continuous current rating of 600 Amps for both 15kV and 28kV voltage classes.
What items are included in the K655BLR kit?
Each kit contains one K655BLR elbow connector housing, one tube of lubricant 82-08, one stud 650SA, and installation instruction IS-0249.
What is the momentary current rating of the elbow housing?
The elbow housing has a momentary current rating of 25kA Symmetrical for 10 cycles, applicable to both 15kV and 28kV voltage classes.
How do I order the 15/25kV 600A elbow housing?
To order the 15/25kV 600A elbow housing without a test point, specify the ordering number K655BLR.
How do I order the 15/25kV 600A elbow housing?
To order the 15/25kV 600A elbow housing without a test point, specify the ordering number K655BLR.
What items are included in the K655BLR kit?
Each kit contains one K655BLR elbow connector housing, one tube of lubricant 82-08, one stud 650SA, and installation instruction IS-0249.
What is the momentary current rating of the elbow housing?
The elbow housing has a momentary current rating of 25kA Symmetrical for 10 cycles, applicable to both 15kV and 28kV voltage classes.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. It covers cable preparation, lug crimping, and connection to mating apparatus. All apparatus must be de-energized during installation or removal of parts to prevent serious or fatal injury.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Torque wrench, Hotstick, Suitable voltage sensing device
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug, Lubricant, Threaded stud, Tape marker, No. 14 AWG Copper wire (or equivalent), Suitable grounding connector, Silicone lubricant
- Perform Initial Safety Checks and Inspection
Before starting, ensure all apparatus is de-energized. Inspect all parts for damage, verify ratings, and check compatibility with mating parts. Confirm all package contents are complete and undamaged, and that all components fit properly with the cable and/or mating products. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Assemble Cable and Clean Outer Surface
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Thoroughly clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare the Cable
Follow the specific cable preparation steps (A, B, or C) that apply to your cable type. This involves removing the outer jacket (if applicable) and preparing the cable insulation, semi-con shield, and shield wires/tape to the specified dimensions (e.g., 9-3/4, 10-3/4, 12-3/4 inches from the cut end) as shown in the documentation diagrams. If using a grounding device or jacket cable seal, refer to their specific installation instructions for jacket removal and shield connection.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Clean and thoroughly lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution to avoid cutting or nicking the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. Crimp the compression lug according to the instructions supplied with the lug. After crimping, wipe all excess inhibitor from the compression lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If any dimension is incorrect, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter, pushing until it cannot advance further. Verify that the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Once correctly positioned, remove the tape marker.
- Prepare Mating Products
WARNING: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove any protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. Ensure a secure and proper connection.
- Connect Opposite End Mating Part
Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part to the specifications provided in its own instructions. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to its specified torque.
- Install Insulating Plug and Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps into place. Proceed to the voltage test directions.
- Ground the Cable Shield
Insert one end of a piece of wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist it to form a small loop, being careful not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded. Ground it according to the instructions supplied with any grounding device used. If no grounding device is present, ground the shield through an alternate approved method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
The ELASTIMOLD deadbreak elbow connector has an integral capacitance test point. Use a hotstick to remove the test point cap by peeling it off at an angle, not pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can give false readings. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.