ABB Installation Products K655BVS-L2-M0380 600 Amp, 15/25KV, DeadBreak, Vault Stretcher Housing Only, with stud, 2-Way, Cable…
UPC: 783786430505
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating
- Accommodates cable insulation diameters from 1.370 to 1.630 inches
- Supports 700/750 kcmil compressed stranded or 900 kcmil compacted solid conductors
- Fully shielded, fully submersible molded rubber housing with 100% peroxide-cured EPDM insulation
- Fully shielded, fully submersible molded rubber housing for underground vaults
Specifications
Application | 400 Amps |
Connection | Compression |
Connection Type | Deadbreak |
Connection Type | Deadbreak, Compression Lug |
Current Rating | 600 A |
Material | Aluminum |
Material | EPDM, Aluminum |
Mounting Type | Vault Stretcher Housing |
Poles | 2-Way |
Series | 600 |
Series | 600 Series |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Vault Stretcher |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
K655VS-L2-M0380
600 Amp, 2 Way Vault Strecher Kit, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
675-7 TIN
Copper Tin Plated Stud, 4-9/64 inch long with 5/8-11 UNC-2A Threads on both ends. Center section not threaded.
756LINKC-DP0578743
600 Amp, 35KV, Retrofit Cam-Op Connector Kit, with capacitive test point, ( 756LINK-C-VB-L0300-BRK-DRG-ISO). VB - Visi-Break. L0300 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 350 or Compacted/Solid 400. DRG - Insulating Cap. ISO - International Standard Organization.
K650BIPVS
Insulating Plug with Cap, 600 Amp, 15/25KV. 600/900 Amp deadbreak Voltage Sensing Plug with Lubricant and Installation Instructions
750J3-U
600 Amp Elbow Connector, 3-Way Junction, DeadBreak, 35KV, Rubber Junction with Stainless Steel Mounting Plate, Back Plate and adjustable Mounting BracketFrequently Asked Questions
What is the maximum cable insulation diameter supported?
The housing supports cable insulation diameters ranging from 1.370 inches to 1.630 inches.
What is the voltage rating of this vault stretcher housing?
This vault stretcher housing has a voltage rating of 15/25 kV.
What conductor sizes are compatible with this housing?
It is compatible with 700/750 kcmil compressed stranded or 900 kcmil compacted solid conductors.
What is the current rating of the ABB K655BVS-L2-M0380?
The current rating for this housing is 600 Amps.
What type of lug material is used in this housing?
The housing features an aluminum compression lug.
How many ways does this vault stretcher housing offer?
This is a 2-way vault stretcher housing.
How to Install the K655VS Deadbreak Vault Stretcher
This guide provides step-by-step instructions for the installation of the Elastimold K655VS Deadbreak Vault Stretcher, covering cable preparation, lug crimping, and final assembly for high-voltage systems.
Estimated time: 4h
Tools needed:
Wire strippers, Cutting tool, Wire brush, Measuring tape, Crimping tool, 5/8 inch bolt and nut, Torque wrench
Supplies needed:
K655VS Deadbreak Vault Stretcher, Cable adapters, Compression lugs, Insulating plugs (if applicable), Lubricant, Special conversion stud (650VSA), Cable (concentric neutral, jacketed, etc.), No. 14 AWG copper wire, Grounding connectors, Tape markers
- Prepare for Installation and Safety Check
DANGER: Ensure all apparatus are de-energized before beginning installation. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Inspect the package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Gather all required tools and maintain cleanliness throughout the procedure.
- Prepare Concentric Neutral Cables
For concentric neutral cable, overlap both cables and cut them to 14 inches (355mm) from the centerline of the joint. Carefully bend back the concentric neutral wires.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back neutral wires.
- Prepare Cable Ends
Follow the specific cable preparation steps (A, B, or C) applicable to your cable type. This involves removing the outer jacket (where applicable) and preparing the cable insulation and semi-con shield to the specified dimensions as shown in the documentation figures.
- Install Cable Adapters
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Be careful not to cut or nick the cable adapter or the conductor. Verify that the length of the exposed conductor is between 4-3/8 inches and 4-11/16 inches (111mm-119mm). If not, redo the assembly.
- Insert Conductor into Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-1/2 inches. If not, redo the assembly.
- Perform Initial Crimp
Before making the first crimp, align the flat portions of the compression connector using a 5/8 inch bolt as a temporary locater. Hold the compression connector in the proper position and make the first crimp connection 3-1/2 inches from the open end of the compression fitting at the mark indicated on the connector.
- Complete Crimping and Finish Lug
Rotate each successive crimp 180 degrees to prevent bowing. Carefully wipe any excess inhibitor from the outside of the connector and the cable insulation. Verify that the connector end is between 6-1/2 inches and 7-1/4 inches (165mm-184mm). Remove any sharp flash from the crimp before inserting it into the vault stretcher body.
- Assemble Vault Stretcher Body
Lubricate the inside of the vault stretcher body and the outside of the cable adapter. Using a rotating motion, slip the body onto the cable adapter, ensuring the compression lug aligns and seats with the inside mating portion of the vault stretcher. Push the compression lug until it cannot advance further, ensuring the adapter base is aligned with the marking tape. Repeat this process for the opposite cable.
- Align and Seat Components
Slowly push both units towards their final alignment, ensuring the lubricated adapter slides into the proper position within the vault stretcher. Check the compression lug's location through the viewing hole. Once fully seated, confirm both cable adapters are flush with their respective tape markers. Reposition if necessary, then remove the tape markers.
- Connect Mating Parts
DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Use a special stud (650VSA) 1/2 inch longer than a standard stud. Remove protective caps from the vault stretcher and the mating part. Hand tighten the stud into one mating part. Clean and lubricate the vault stretcher and both mating parts. Insert the second mating part, engage the threads, hand tighten, and then torque it according to its specific instructions.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground Concentric Neutral Cable
Insert one end of a piece of wire, with ampacity at least equivalent to No. 14 AWG copper, through each grounding eye and twist to form a small loop. Do not damage the eyes. Connect these wires to ground using suitable connectors.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.