ABB Installation Products K655BLR-K0320 600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to…
UPC: 783786417681
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Aluminum compression lug for 450-550 AWG compressed stranded or solid conductors
- Cable insulation diameter range: 1.090" to 1.310"
- Elbow design for 90-degree cable entry, reducing bend radius stress
- No test point for continuous insulation integrity
- Integrated stud for secure mechanical and electrical connections
Specifications
Application | 15/25 kV, 600 Amps |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 600 A |
Material | Aluminum |
Series | 600 |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Elbow without Test Point |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.0000 L |
Package Weight (Metric) | 1.8140 kg |

756LINKC-DP0578743
600 Amp, 35KV, Retrofit Cam-Op Connector Kit, with capacitive test point, ( 756LINK-C-VB-L0300-BRK-DRG-ISO). VB - Visi-Break. L0300 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 350 or Compacted/Solid 400. DRG - Insulating Cap. ISO - International Standard Organization.
K655BVS-L2-M0380
600 Amp, 15/25KV, DeadBreak, Vault Stretcher Housing Only, with stud, 2-Way, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655VS-L2-M0380
600 Amp, 2 Way Vault Strecher Kit, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
675-7 TIN
Copper Tin Plated Stud, 4-9/64 inch long with 5/8-11 UNC-2A Threads on both ends. Center section not threaded.
K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.Frequently Asked Questions
What standards does the K655BLR meet?
The K655BLR meets ANSI/IEEE Standard 386, Latest Revision.
What items are included in the K655BLR kit?
Each kit contains one K655BLR elbow connector housing, one tube of lubricant 82-08, one stud 650SA, and installation instruction IS-0249.
What materials are used in its construction?
The K655BLR features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
What optional accessories are available for the K655BLR?
Optional accessories allow for visible external separation, by-pass, isolation, dead-ending, grounding, and testing. They also allow adding taps, surge arrestors, and fault current indicators.
How is the K655BLR connected or disconnected?
It can be easily connected or disconnected using standard hand tools and equipment when in a de-energized state.
What is the momentary current rating?
The momentary current rating for both 15kV and 28kV voltage classes is 25kA Sym for 10 Cycles.
Is the K655BLR housing submersible?
Yes, the K655BLR features a fully shielded, fully submersible molded rubber housing.
What is the continuous current rating?
The continuous current rating for both 15kV and 28kV voltage classes is 600 Amp.
What is the operating voltage for the 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV and the maximum phase-to-phase is 28kV.
What is the operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and the maximum phase-to-phase is 14.4kV.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 655/675LR and K655/K675LR Deadbreak Elbow Connectors, including cable preparation, lug crimping, and connection to mating apparatus. All apparatus must be de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Wire brush, Crimping tool, Hotstick, Suitable voltage sensing device, Suitable grounding connector
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug (optional), Lubricant, Stud prepack, Threaded stud, Protective caps, HV insulated cap(s) or connector(s), No. 14 AWG Copper wire (or equivalent), Silicone lubricant
- Prepare Cable Slack and Cut
Assemble the cable in its final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Perform Cable Preparation
Remove the outer jacket (if applicable) and prepare the cable according to the specific type (e.g., non-jacketed, jacketed, Unishield, lead sheath, or using a grounding device). Refer to specific instructions for 20MA/21MA grounding devices, 600ECS Jacket Cable Seal, or 10TL cable shield adapters if used.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor should be between 4-1/4” – 4-9/16” (108mm-116mm). If not, redo the assembly.
- Insert and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8”. Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8” to 7-1/8” (162mm-181mm). If not, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products for Connection
WARNING: Ensure all apparatus is de-energized during this step. Do not connect or disconnect mating products while energized. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud, supplied with the elbow, into the mating part if it is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Insert and Torque Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug and Voltage Detection Cap (Optional)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place. Follow the voltage test directions provided in the next steps.
- Ground the Cable Shield
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with a grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
The ELASTIMOLD® deadbreak elbow connector has an integral capacitance test point. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points, following its manufacturer's directions. Contamination or incorrect equipment can give false readings; treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the cap with silicone lubricant and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.