Authorized ABB Distributor (Installation Products)
ABB - Installation Products K655BLR-J0270 - 15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.

ABB Installation Products K655BLR-J0270 15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation…

UPC: 783786417674


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB K655BLR-J0270 is a 15/25kV 600 Series Deadbreak Elbow designed for reliable medium-voltage cable terminations in submersible and fully shielded applications. This deadbreak elbow provides a dead-front, fully insulated connection point for high-voltage apparatus, ensuring operator safety during installation and maintenance. The unit is engineered without a test point but includes a stud for secure mechanical and electrical connection. Key specifications include a voltage rating of 15/25kV with a maximum phase-to-ground operating voltage of 8.3kV (15kV class) and 16.2kV (25kV class). The elbow supports a continuous current rating of 900A and a momentary rating of 25kA symmetrical for 10 cycles. It meets ANSI/IEEE Standard 386 (latest revision) and provides a BIL (Basic Impulse Level) of 95kV for the 15kV class and 140kV for the 25kV class. The K655BLR-J0270 accommodates cable insulation diameters from 0.980 inches to 1.180 inches, making it compatible with stranded aluminum conductors sized 4/0 AWG, compacted solid aluminum conductors up to 250 kcmil, and compact aluminum conductors at 125 mm². The integrated aluminum compression lug ensures a durable and low-resistance electrical connection, while the fully shielded, submersible molded rubber housing provides environmental protection and dielectric integrity. This deadbreak elbow is ideal for applications requiring fully shielded, dead-front connections in medium-voltage systems, including utility substations, industrial power distribution, and renewable energy installations. It can be easily connected or disconnected using standard hand tools in a de-energized state, reducing downtime during maintenance or reconfiguration. Optional accessories are available for visible external separation, bypass, isolation, dead-ending, grounding, and testing, as well as adding taps, surge arrestors, and fault current indicators. The K655BLR-J0270 is part of ABB's 600 Series Deadbreak product line, designed for compatibility with other ABB components such as the K675CP, K675BIP, and K650J series connectors.
  • 15/25kV voltage rating with 900A continuous current capacity
  • Fully shielded, submersible molded rubber housing for environmental protection
  • Accommodates cable insulation diameters from 0.980" to 1.180"
  • Compatible with stranded aluminum 4/0 AWG, compacted solid 250 kcmil, and compact 125 mm² conductors
  • Designed for dead-front, de-energized connections per ANSI/IEEE Standard 386

Specifications

Application
15/25 kV, 600 Amps
Connection
Compression
Material
Aluminum
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Elbow without Test Point
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
4.0000 L
Package Weight (Metric)
1.8140 kg
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.

K655BLR-K0330

600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
900 Amp, 15/25kV, Deadbreak Connecting Plug. Length 8.25 inches. Diameter 3.0 inches. All Copper Connections

K671CP

900 Amp, 15/25kV, Deadbreak Connecting Plug. Length 8.25 inches. Diameter 3.0 inches. All Copper Connections
600 Amp, 15/25kV, Deadbreak, Connecting Plug. Widest Diameter 3 inches. With Factory assembled Stud which is not field removable. SRP.

K650CPSP-SRP

600 Amp, 15/25kV, Deadbreak, Connecting Plug. Widest Diameter 3 inches. With Factory assembled Stud which is not field removable. SRP.
15/25kV, 900 Amp, Deadbreak, Short Shank Bushing for In-Oil and SF6 Applications (Pad-Mounted or Vault-Type or Submersible Transformers or Switchgear). One Factory installed 5/8-11 UNC-2A Stud included, other Stud must be Purchased Separately. Overall Length 8.12 inch, Diameter 4.50 inch. Molded Epoxy with Stainless Steel Flange. SP - Stud Permanent.

K675S1SP

15/25kV, 900 Amp, Deadbreak, Short Shank Bushing for In-Oil and SF6 Applications (Pad-Mounted or Vault-Type or Submersible Transformers or Switchgear). One Factory installed 5/8-11 UNC-2A Stud included, other Stud must be Purchased Separately. Overall Length 8.12 inch, Diameter 4.50 inch. Molded Epoxy with Stainless Steel Flange. SP - Stud Permanent.
Stick-op Bush. Adapter, 25kv 600ser

K655BEA2-WB

Stick-op Bush. Adapter, 25kv 600ser
900 Amp, 15/25kV, Insulated Parking Bushing, Stand Off Plug. Factory Assembled Stud which is not field removable.

K675SOP-SP

900 Amp, 15/25kV, Insulated Parking Bushing, Stand Off Plug. Factory Assembled Stud which is not field removable.
600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (with Stud), with Ground. Factory Assembled Stud which is not field removable.

K656DRGSP

600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (with Stud), with Ground. Factory Assembled Stud which is not field removable.
15/25kV 600 Series Deadbreak 3-Point Junction, Hardware package consists of brackets and straps only.

K650-J3-6

15/25kV 600 Series Deadbreak 3-Point Junction, Hardware package consists of brackets and straps only.

Frequently Asked Questions

What is the voltage rating of the K655BLR-J0270 deadbreak elbow?

The K655BLR-J0270 deadbreak elbow has a voltage rating of 15/25kV.

What is the cable insulation diameter range for this elbow?

This deadbreak elbow is designed for cable insulation diameters ranging from 0.980 inches to 1.180 inches.

What type of lug does the K655BLR-J0270 use?

The K655BLR-J0270 features an aluminum compression lug for secure electrical connection.

What conductor sizes are compatible with this deadbreak elbow?

It is compatible with stranded aluminum conductors 4/0 AWG, compacted solid aluminum conductors 250 kcmil, and compact aluminum conductors 125 mm².

Does this deadbreak elbow have a test point?

No, the K655BLR-J0270 is a deadbreak elbow without a test point, but it includes a stud for connection.

How to Install K655/K675LR Series Deadbreak Elbow Connectors

This guide provides step-by-step instructions for the safe and proper installation of K655/K675LR series deadbreak elbow connectors, including cable preparation, lug crimping, and connection to high voltage apparatus. Ensure all apparatus are de-energized before starting.

Tools needed:

Wire strippers, Crimping tool, Torque wrench, Hotstick, Voltage sensing device (for capacitive test points), Wire brush (for aluminum conductors), Measuring tape

Supplies needed:

K655/K675LR Deadbreak Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Lubricant, Stud Prepack), Insulating Plug (if required), Grounding wire (minimum No. 14 AWG Copper), Suitable grounding connector, Cable jacket waterproofing material, HV insulated caps or connectors (to replace shipping covers)

  1. De-energize Apparatus and Prepare Cable

    DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Assemble the cable in its final position with enough slack for elbow removal. Unwind concentric neutral wires if applicable. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable a distance of 24” (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield according to the specified dimensions (e.g., 9-3/4”, 10-3/4”, 12-3/4” tape markers).

  2. Install Cable Adapter and Prepare Conductor

    Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4” and 4-9/16” (108mm-116mm); otherwise, redo this assembly step.

  3. Crimp Compression Lug

    For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 6-3/8”. Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-3/8” to 7-1/8” (162mm-181mm); otherwise, redo this assembly step.

  4. Install Elbow and Prepare Mating Parts

    Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; reposition if necessary. Remove the tape marker. DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.

  5. Connect Elbow to Mating Parts

    Push the elbow onto the first mating part, aligning the hole in the compression lug with the stud on the mating part. Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down hard until it snaps into place.

  6. Ground the Cable Shield and Waterproof

    Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device; if no device is used, ground the shield through an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.

  7. Perform Voltage Test (Post-Installation)

    WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device made for capacitive test points, following the manufacturer’s directions. Contamination, moisture, or incorrect equipment can provide a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. Remove the test point cap with a hotstick, peeling it off at an angle. Test to determine if the cable is energized. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.