ABB - Installation Products K650CPSP-SRP - 600 Amp, 15/25kV, Deadbreak, Connecting Plug. Widest Diameter 3 inches. With Factory assembled Stud which is not field removable. SRP.
ABB - Installation Products

K650CPSP-SRP

UPC: 783786436996


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Overview

The ABB K650CPSP-SRP is a 600 Amp, 15/25kV deadbreak connecting plug engineered for safe, reliable medium-voltage cable connections in power distribution systems. This factory-assembled unit features a permanently attached stud that cannot be removed in the field, ensuring a secure termination point for 600 Amp connectors. Designed for utility, industrial, and commercial applications, the K650CPSP-SRP enables de-energized connection and disconnection of two 600 Amp connectors, eliminating arc flash risks during maintenance. Its deadbreak design ensures the circuit is de-energized before separation, providing critical safety for personnel and equipment. The plug is installed using a 600SW spanner wrench, with lubricant included for smooth assembly. Key electrical ratings include 8.3kV phase-to-ground and 14.4kV phase-to-phase for 15kV class systems, with 95kV BIL impulse withstand and 600 Amp continuous current. For 25kV class systems, it supports 16.2kV phase-to-ground and 28kV phase-to-phase, with 140kV BIL impulse withstand and 900 Amp continuous current. The unit meets stringent corona extinction requirements at 3pC sensitivity, ensuring long-term reliability in high-voltage environments. Ideal for connecting Elastimold® K655LR/K656LR 600 Amp connectors, the K650CPSP-SRP is part of ABB's Installation Products line, delivering durable performance in medium-voltage power distribution. Its robust construction withstands operational demands, contributing to system uptime and operational safety.
  • 600 Amp continuous current rating for medium voltage applications
  • Deadbreak design enables safe de-energized connections
  • Factory-assembled stud (non-field removable) for secure termination
  • Includes lubricant and installation instructions for ease of use
  • Factory assembled, non-field removable stud (SRP)

Specifications

Application
15/25 kV, 600 Amps
Connection Type
Deadbreak
Current Rating
600 A
Series
SRP
Size
3 Inches
Size
3 inches (widest diameter)
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Connecting Plug
Voltage Rating
15/25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
2.5000 L
Package Weight (Metric)
1.1340 kg
15/25kV 600 Series Deadbreak Reducing Tap Well. Length 5.37 inch. Width 3 inch not counting bracket. 600/200 Amps

K650RTW

15/25kV 600 Series Deadbreak Reducing Tap Well. Length 5.37 inch. Width 3 inch not counting bracket. 600/200 Amps
Plastic Drive Stop® for 7/16" Cable (#4 Wire), Gray

DRIVESTOP4

Plastic Drive Stop® for 7/16" Cable (#4 Wire), Gray
HMI door mounting kit with 15M cable

181B2258

HMI door mounting kit with 15M cable
Polarizing Cover / Hermaphroditic Cover, Black, Nylon, 8 Position, AMPMODU IV/V

103350-4

Polarizing Cover / Hermaphroditic Cover, Black, Nylon, 8 Position, AMPMODU IV/V
Stick-op Bush. Adapter, 25kv 600ser

K655BEA2-WB

Stick-op Bush. Adapter, 25kv 600ser
600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (with Stud), with Ground. Factory Assembled Stud which is not field removable.

K656DRGSP

600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (with Stud), with Ground. Factory Assembled Stud which is not field removable.
15/25kV 600 Series Deadbreak 3-Point Junction, Hardware package consists of brackets and straps only.

K650-J3-6

15/25kV 600 Series Deadbreak 3-Point Junction, Hardware package consists of brackets and straps only.
600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (without Stud), with Ground.

K656DRGN

600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (without Stud), with Ground.

Frequently Asked Questions

What is the current rating of the K650CPSP-SRP connecting plug?

The ABB K650CPSP-SRP connecting plug has a current rating of 600 Amps.

What is the voltage class for this ABB deadbreak plug?

This ABB deadbreak plug is rated for 15/25kV voltage classes.

What is the widest diameter of the K650CPSP-SRP?

The widest diameter of the K650CPSP-SRP connecting plug is 3 inches.

Does the K650CPSP-SRP have a field-removable stud?

No, the K650CPSP-SRP features a factory-assembled stud that is not field removable.

What type of connection does the K650CPSP-SRP offer?

The K650CPSP-SRP offers a Deadbreak connection type for enhanced safety.

How to Install the LINK-C Deadbreak Cam Link Operable Connector System

This guide provides step-by-step instructions for the safe installation and setup of the LINK-C 600 amp deadbreak cam link operable connector system, including mounting, wiring, and grounding procedures.

Estimated time: 1h

Tools needed:

Torque wrench, Socket wrench (1 inch hex), Hot stick, Wire strippers, 600ATM Operating Tool

Supplies needed:

ELASTIMOLD supplied lubricant, #14 AWG or #12 AWG solid copper wire, Appropriate grounding connector, HV insulated cap(s) or connector(s) (if replacing shipping covers)

  1. Prepare for Installation and Ensure Safety

    DANGER: Ensure all apparatus is de-energized before beginning installation or removal of any parts. This product must only be installed by competent personnel trained in high voltage electrical equipment safety practices. Inspect all parts for damage, proper rating, and compatibility with mating components. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before energizing or submerging the circuit. Read all instructions thoroughly before starting.

  2. Install the 600 Amp Elbow onto the Cable

    Install the 600 amp elbow onto the cable according to the specific installation instructions provided with the elbow. Ensure it is positioned to properly align with the stand-off plug or apparatus bushing.

  3. Install the Bushing Extender

    Clean and thoroughly lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender using ELASTIMOLD supplied lubricant. Insert the 600ATM Operating Tool into the retainer contact and engage its internal hex broach. Install the bushing extender onto the apparatus bushing. Insert the retainer contact into the bushing extender and thread it into the apparatus bushing using a suitable tool applied to the 1-inch hex portion of the 600ATM Operating Tool. Torque to 50-60 ft-lbs.

  4. Install the 600 Amp Elbow onto the Epoxy Standoff Plug

    Clean and thoroughly lubricate the epoxy standoff plug and both interfaces of the 600 amp elbow with ELASTIMOLD supplied lubricant. Insert the 600ATM Operating Tool into the retainer contact and engage its internal hex broach. Install the elbow onto the epoxy standoff plug. Insert the retainer contact into the 600 amp elbow through the hole in the compression lug and thread it into the epoxy standoff plug using a suitable tool applied to the 1-inch hex portion of the 600ATM Operating Tool. Torque to 50-60 ft-lbs.

  5. Install the Alignment Bracket

    Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender at a dimension of 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until the clamp tabs are flush and tight on both sides.

  6. Position and Secure the Elbow in the Alignment Bracket

    Position the elbow in the alignment bracket so that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until the clamp tabs are flush and tight on both sides. Ensure the elbow clamp notch faces the cable entrance of the elbow.

  7. Insert and Engage the LINK-C Connector

    Clean and thoroughly lubricate both 600 ampere interfaces of the Link with ELASTIMOLD supplied lubricant. Align the Link so it is perpendicular to the switch faceplate when inserted into the bushing extender and elbow. Insert the Link, ensuring both lever arms are on the inside of the alignment bracket legs. Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, move the lever arms downward using a hot stick eye, engaging the roller pin and moving the Link inward. Continue moving lever arms until they are perpendicular to the alignment bracket leg.

  8. Ground the System and Install Mating Products

    Ground the elbow by feeding a #14 AWG or #12 AWG solid copper wire through the grounding eye, twisting it tight, and connecting it to ground. Clean and lubricate the 200 amp interface on the Link. Ground the cable: if using concentric neutral cable, twist the neutral wires together and connect to ground with an appropriate connector; if using 20MA or 21MA grounding devices, connect the ground lead to ground with a suitable connector. For three-phase installations, tie all grounds from all three phases to a common ground point. Install the desired 200 amp mating product onto the Link's 200 amp interface according to its specific instructions.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.