ABB Installation Products 755LR-H0240 600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable…
UPC: 783786361007
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating for medium-voltage applications
- Fully shielded, deadbreak elbow design for safe de-energized connections
- Includes insulated plug, cap, copper stud, aluminum compression lug, and cable adapter
- Supports 1/0 AWG or 2/0 AWG (53.49 mm²) conductors with 0.850"-1.050" insulation diameter
- Designed for reliable terminations in switchgear, transformers, and industrial facilities
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 755LR |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.9000 L |
Package Weight (Metric) | 4.0370 kg |

756LR-L0240
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
161LR-B5230-S
15kV, 200 Amp, Loadbreak Elbow without Test Point, Cable Insulation Diameter 0.635 to 0.905 inches (16.13-22.99 mm), Bi-Metal Compression Lug, Conductor Size Stranded/Compressed #1, Solid/Compact 1/0. S is for Cold Shrinkable Jacket Seal.
161LR-B5220
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
161LR-B5210
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67.
161LR-A5240
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.575 inch to 0.740 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
161LR-A5230
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.575 inch to 0.740 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
161LR-A5220
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.575 inch to 0.740 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.Frequently Asked Questions
What is included in a 755LR kit?
Each kit contains an elbow connector housing, a copper compression lug, a stud, an insulated plug with cap, lubricant tubes, a cable adapter, and installation instructions.
What is the impulse withstand rating (BIL) for the elbow?
The impulse withstand (BIL) rating for the 35kV voltage class is 150kV (1.2 x 50 microsecond wave).
What standard does the 755LR elbow meet?
The 755LR elbow meets ANSI/IEEE Standard 386, Latest Revision.
Is the 755LR elbow submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What cable insulation diameters does the elbow support?
The elbow supports cable insulation diameters from 0.760 inches to 2.120 inches.
What conductor sizes are compatible with the 755LR?
The 755LR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
What is the continuous current rating of the elbow?
The 755LR deadbreak elbow has a continuous current rating of 600 Amps.
What is the maximum operating voltage for this elbow?
The 755LR elbow connector is rated for a 35kV voltage class, with a maximum phase-to-ground operating voltage of 21.1kV.
What conductor sizes are compatible with the 755LR?
The 755LR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
Is the 755LR elbow submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
How to Install 755LR/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755LR and 775LR Deadbreak Elbow Connectors, designed for 35kV class systems. It covers cable preparation, connector assembly, and final connection procedures.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Hotstick, Suitable voltage sensing device (for capacitive test points), Suitable grounding connector, Torque wrench (for mating parts and L-Kits)
Supplies needed:
755LR or 775LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant (silicone), Threaded Stud (from stud prepack), Cable (appropriate type for application), Tape marker, Grounding wire (minimum No. 14 AWG Copper), Waterproofing material (for cable jacket), HV insulated caps or connectors (to replace shipping covers)
- Perform Pre-Installation Safety and Inspection
DANGER: Ensure all apparatus is de-energized before beginning installation or removal of any parts. Do not touch or move energized products in the work area. Inspect all package contents to ensure they are complete and undamaged. Verify all components fit properly with the cable and/or mating products. Read the entire installation instructions thoroughly before starting and have all required tools at hand, maintaining cleanliness throughout the procedure.
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for adequate clearance to remove the elbows. If using concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable Shield and Jacket
Prepare the cable according to its specific type (e.g., UNISHIELD, Lead Sheath, Jacketed, Non-Jacketed). If using a 20MA/21MA grounding device or 600ECS Jacket Cable Seal, refer to their specific instructions. For UNISHIELD or Lead Sheath cable, use a 10TL cable shield adapter and follow its instructions. For jacketed and non-jacketed cables, remove the outer jacket (if applicable) and prepare the cable shield and insulation to the specified dimensions (e.g., 10-3/8 inches, 11-3/8 inches, 13-5/8 inches for insulation, semi-con shield, and tape marker respectively).
- Bevel and Lubricate Cable Insulation
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield.
- Install Cable Adapter
Install the cable adapter, small end first, onto the cable insulation until it is flush with the edge of the tape marker.
- Prepare Conductor
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm); if not, redo the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping, ensuring it is less than 7 inches (178mm). Crimp the compression lug according to the instructions supplied with the lug. After crimping, wipe all excess inhibitor from the compression lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter must be between 6-7/8 inches to 7-5/8 inches (175mm-194mm); if not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove any protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
If connecting an opposite mating part, clean and lubricate its mating surface. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part. CAUTION: When constructing 600amp L-Kits, tighten each component to the specified torque per the plug connector instructions.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground the Cable Shield and Waterproof Jacket
Insert one end of a grounding wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow the instructions supplied with your grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap using a hotstick, peeling it off at an angle rather than pulling directly in line with the assembly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device designed for separable connectors with capacitive test points to determine if the cable is energized. Contamination, moisture, or incorrect equipment can give a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.