ABB Installation Products 252LR-A5230 15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 075114345781
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating for medium voltage applications
- 200 Amp continuous current rating
- Accommodates cable insulation diameters from 0.575-0.740 inches (14.61-18.80mm)
- Bi-metal lug for compatibility with stranded/compressed or solid/compact conductors
- Includes test point for safe voltage verification
Specifications
Amperage Rating | 200 A |
Application | 15/25kV, 200 Amp Deadbreak Connector |
Color | Black |
Color | Blue |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Deadbreak Elbow Connector |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 7.531 in |
Length | 191.2874 mm |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal Lug, Poly (assumed from connector housing) |
Series | 252LR |
Size | 5.454 x 7.531 inches, 2.097 inch diameter |
Special Features | Fully Shielded, fully Submersible Molded Rubber Housing. Provision for Hot Stick Operation. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 5.454 in |
Width | 138.5316 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
K656LR-H0270-S
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .850 to 1.050 inch. Aluminum Lug, Conductor Size 4/0 stranded/compressed or 250 Compact/solid. With Cold Shrinkable Jacket Seal
252LR-A5240
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80mm), Bi-Metal Lug, Conductor Size 240 - 1/0 Stranded/Compressed, 2/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5250
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 250 - 2/0 Stranded/Compressed, 3/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5220-S
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 220 - #2 Stranded/Compressed, #1 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter. Cold-Shrinkable Jacket Seal.
252LR-B5260
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 260 - 3/0 Stranded/Compressed, 4/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-B5270-S
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 270 - 4/0 Stranded/Compressed, 250kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter. Cold-Shrinkable Jacket Seal.
252LR-C5230
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.805-1.060 inches (20.45-26.92mm), Bi-Metal Lug, Conductor Size 230 - #1 Stranded/Compressed, 1/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.Frequently Asked Questions
What are the voltage and current ratings of this connector?
The 252LR Elbow Connector is rated for 15/25kV voltage class and has a continuous current rating of 200 Amps.
Which industry standards does the 252LR connector meet?
The 252LR Elbow Connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and the maximum phase-to-phase is 14.4kV.
What is the maximum operating voltage for the 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV and the maximum phase-to-phase is 26.3kV.
What types of conductors are compatible with the compression lugs?
Bi-metal compression lugs are suitable for both copper and aluminum conductors. Copper compression lugs are only suitable for copper conductors.
When is a cable adapter required for this connector?
A cable adapter (160CA-XX) is required for cables that have an outer diameter less than 0.565 in.
What safety measure is highly recommended during installation?
For safety purposes, a sealing and grounding kit with the deadbreak elbow is highly recommended.
What sealing kit is used for Jacketed Concentric Neutral Cables?
For Jacketed Concentric Neutral Cables, use sealing kit 200ECS or add suffix "-S" to the part number for cables with a nominal O.D. between 0.80 in. and 1.50 in.
What sealing kit is used for Copper Tape Shield Cables?
For Copper Tape Shield Cables, use sealing kit 200ECS or add suffix "-S" to the part number for cables with a nominal O.D. between 0.80 in. and 1.50 in.
What shield adapter is used for Unishield Cables?
For Unishield Cables, the shield adapter part number is 10TL-W, where "W" is determined by the cable's insulation diameter, or add suffix "-TL" to the part number.
How to Install the 252LR Deadbreak Elbow Connector
This guide provides step-by-step instructions for installing the 252LR Deadbreak Elbow Connector, including cable preparation, assembly, and connection to a 25kV class deadbreak bushing or accessory device.
Estimated time: 1h 30m
Tools needed:
Wrench, Cable cut back template, Wire brush, Crimp tool, Hot stick, Suitable sensing device
Supplies needed:
252LR Elbow Connector Housing, Compression Lug, Probe, Probe Contact, Lubricant, Hold-down Bail, UD cable (concentric neutral and semi-con shielding), No. 14 AWG (2.5mm) copper wire, Appropriate grounding connector
- Verify Components and Ensure Safety
Before starting, ensure all apparatus is de-energized. Do not touch or move energized products. Check the package contents for completeness and damage. Verify the elbow housing cable entrance size and compression lug size match the cable. Check threads by hand-threading the probe into the compression lug; replace damaged components if resistance is encountered. Read all instructions and have required tools ready, maintaining cleanliness.
- Train and Prepare Cable End
Train the UD cable to ease operation, ensuring a minimum of 20 inches (508.0mm) extends beyond the end of the cable pad mount transformer. Cut any excess cable squarely at the bushing's center line. Unwrap and bind concentric neutral wires 8-1/2 inches (216.0mm) back from the cable end. Remove the shield and insulation squarely, avoiding conductor nicks. Wire brush bare aluminum conductors and immediately install the compression lug, rotating to spread inhibitor. Align the lug's threaded hole with the bushing bore. Crimp the lug per the chart, starting at the crimp line and rotating 180 degrees for each successive crimp. Wipe off excess inhibitor. Remove the semi-con shield and bevel the insulation end 1/8 inch (3.2mm) maximum. Thoroughly clean insulation to remove conductive residue.
- Assemble Elbow and Probe
Clean and lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; do not substitute. Slide the elbow connector onto the cable with a back and forth twisting motion, then wipe off all excess silicone lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring not to cross-thread, and tighten with the supplied wrench until the wrench bends.
- Install the Hold-down Bail
Place the hold-down bail into the hold-down bracket. Compress the bail and insert it securely into the brackets.
- Connect Concentric Neutral Wires to Ground
Insert one end of a separate No. 14 AWG (2.5mm) copper wire through the grounding eye on the elbow and twist tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack in the wires for elbow operation.
- Connect Elbow to Mating Bushing
Clean the receptacle portion of the elbow connector and the mating bushing, then lubricate with the supplied lubricant ONLY if the transformer and elbow are known to be de-energized. Use a fully insulated hot stick to place the elbow onto the bushing; do not operate by hand or separate if energized.
- Secure the Elbow with Hold-down Bail
Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt clockwise. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator, acting as a stop to prevent excessive force on the elbow. Once the nut is in its final position, it will not need readjustment for future removal and replacement.
- Perform Optional Voltage Test
If equipped, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized; do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.