ABB Installation Products 167RLR-H-5250 200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable…
UPC: 783786266739
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp current rating for robust power handling.
- 15kV voltage rating suitable for medium-voltage systems.
- Accommodates cable insulation diameters from 0.850" to 1.050".
- Bi-metal compression lug ensures secure conductor termination.
Specifications
Amperage Rating | 200 A |
Application | Designed for connecting to and operating 15kV Class, 95kV BIL apparatus |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection Type | Loadbreak Replacement Elbow Connector |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | 167RLR |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured insulation, insert and jacket. Provision for hot stick operation, Provision for ground wire connection. Wide cable range with minimum number of sizes. Extended length housing and compression lug plus 10-1/2 inch (266.7mm) |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Replacement Elbow Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.2800 L |
Package Weight (Metric) | 1.9410 kg |

162LR-B5250-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS-G3 Jacket Seal and Grounding Kit Included.
274RLR-H-5220
25kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
376LR-L5250
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
167RLR-G-5240-S
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. 200ECS Jacket Seal Included.
167RLR-F-5210
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67.
167LRT-J-5270
15KV, 200 Amp, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
167LRT-G-5270
15KV, 200 Amp, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.Frequently Asked Questions
Does this elbow connector have a test point?
No, this specific model, SKU 167RLR-H-5250, is a loadbreak replacement elbow connector without a test point.
Who is the manufacturer of the 167RLR-H-5250 connector?
The manufacturer of the 167RLR-H-5250 connector is ABB - Installation Products.
What is the maximum voltage rating for this elbow connector?
The ABB 167RLR-H-5250 loadbreak elbow connector has a maximum voltage rating of 15kV.
What cable insulation diameters does this connector support?
This connector is designed to fit cable insulation diameters ranging from 0.850 inches to 1.050 inches.
How to Install 167RLR/168RLR Loadbreak Replacement Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of Elastimold 167RLR and 168RLR loadbreak replacement elbow connectors, converting livefront terminations to deadfront for UD cables.
Estimated time: 1h 30m
Tools needed:
Probe wrench, Wire brush, Crimping tool, Wire strippers, Measuring tape or ruler, Hotstick
Supplies needed:
Replacement Elbow Connector Housing, Compression Lug, Probe, Lubricant (supplied, do not substitute), Hose Clamp, Copper wire (No. 14 AWG / 2.5mm or equivalent), Appropriate connector (for neutral to ground)
- Perform Pre-Installation Checks and De-energize Apparatus
DANGER: Ensure all apparatus is de-energized before beginning installation or removal of any parts. Check the package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Thread the probe into the compression lug to check for resistance; replace damaged components if resistance is encountered. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Remove Existing Livefront Termination
Remove the rubber cap from the terminator. Cut off the existing connector at the top of the terminator. Disconnect the ground lead from the base of the terminator. Carefully remove the terminator housing from the cable.
- Prepare the Cable End
Train the cable to be straight and in-line with the bushing centerline. Measure and cut the cable to 10-1/2 inches from the bushing centerline. If the insulation shield measures less than 6-1/2 inches from the end of the cut cable, proceed. If greater, consult an ELASTIMOLD representative. Remove 1-3/8 inches of cable insulation from the end, cutting squarely. DO NOT NICK THE CONDUCTOR during this process.
- Install the Compression Lug
Wire brush the bare aluminum conductor thoroughly and immediately install the compression lug. Rotate the lug to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Refer to the crimp chart provided with the compression lug for recommended crimp information. Start crimping at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe any excessive inhibitor from the outside of the lug and cable.
- Assemble the Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants as they may be harmful. Keep the insulation clean of dirt and grime. Do not use excess grease or introduce any grease into the gap between the lug and the insulation. Slide the elbow connector onto the cable using a back and forth twisting motion. Wipe off all excess grease. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring not to cross-thread. The probe should turn freely for approximately four turns before becoming snug. Tighten the probe with the probe wrench until the wrench bends.
- Connect the Concentric Neutral
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through the grounding eye on the elbow. Twist it tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires for elbow operation. Add the supplied hose clamp as shown in the diagram and tighten it snugly. Do not overtighten the hose clamp.
- Connect the Elbow to the Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. DO NOT OPERATE BY HAND. Securely fasten a hotstick to the loadbreak connector pulling eye. After establishing firm footing and positive control, place the elbow connector receptacle area over the bushing plug, inserting the elbow male contact into the bushing until the first slight resistance is felt. Immediately push the elbow home with a fast, firm, straight motion to engage the internal lock on the elbow and bushing interface. Apply sufficient force to ensure the internal lock engages.
- Perform Voltage Test (168RLR Only)
If installing a 168RLR with a test point, you can use it to establish if the circuit is energized. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment; follow the manufacturer’s directions for the specific sensing device. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it tightly on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.