ABB Installation Products 167LRT-J-5270 15KV, 200 Amp, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.980 inch to…
UPC: 783786368174
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV, 200A deadbreak loadbreak elbow connector with integrated tap
- Accommodates cable insulation diameters from 0.980 to 1.180 inches
- Bi-metal compression lug for corrosion-resistant connections
- Loadbreak-rated tap for phasing, grounding, testing, or arrester protection
- Accommodates cable insulation diameters from 0.980" to 1.180" and conductors from AWG 4/0 to 250 or 126.67 mm²
Specifications
Amperage Rating | 200 A |
Application | 15kV, 200 Amps |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | Includes 02800X Bi-Metal Contact |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Bolted Elbow with Tap |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

162LR-D5270-S
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.
167LRT-G-5270
15KV, 200 Amp, Loadbreak Bolted Elbow with Tap, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
167DELR-7495-5240
200 Amp, 15kV, Loadbreak Direct Test Repair Elbow Connector, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0 or mmSquared 53.49.
375LR-H-5240-S
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. 200ECS Jacket Seal Included.
375LR-J5260
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
375LR-K-5270
35kV 200 Amp, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
375LR-K-5250-S
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1090 inch to 1.310 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS Jacket Seal Included.
375LR-J-5220
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.Frequently Asked Questions
What items are included in the 167LRT kit?
The kit includes the elbow housing, compression lug, stud extender, lubricant, installation tool, wrench, installation instructions, and a crimp chart.
What type of insulation does it use?
The 167LRT utilizes peroxide-cured insulation for its insert and jacket.
What is the maximum operating voltage?
The maximum phase-to-ground operating voltage is 8.3 kV.
What is the maximum phase-to-phase voltage?
The maximum phase-to-phase voltage rating is 14.4 kV.
What is the BIL impulse withstand rating?
It has a 95kV BIL impulse withstand rating (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 34 kV.
What is the corona extinction voltage?
The corona extinction voltage is 11 kV AC at 3p.C. sensitivity.
What is the momentary and fault close rating?
It has a 10kA Symmetrical momentary and fault close rating for 10 cycles.
What are the primary applications of the 167LRT?
It is designed for connecting to and operating 15kV-class, 95BIL distribution apparatus.
What bushing wells is it compatible with?
It mates with bushing wells that conform to ANSI Std. 386, Fig. 3.
How to Install the Elastimold 167LRT Loadbreak Bushing Tap
This guide provides step-by-step instructions for the safe and proper installation of the Elastimold 167LRT Loadbreak Bushing Tap, designed to terminate UD cable and interface with 15kV class loadbreak elbows or accessories.
Estimated time: 1h 15m
Tools needed:
Cable cutter, Cable stripping tool, Wire brush, Crimp tool (for compression lug), Wrenches (supplied), Installation Tool (supplied), Wire strippers, Crimp tool (for ground connector)
Supplies needed:
Elastimold 167LRT Loadbreak Bushing Tap Kit, Lubricant (supplied, Do Not Substitute), UD Cable (concentric neutral and semi-con shielding), No. 14 AWG (2.5mm) copper wire or equivalent, Appropriate ground connector, Insulated Cap or Elbow (if not immediately mated)
- Ensure Safety and Prepare Components
DANGER: All apparatus must be de-energized during installation. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions will result in serious injury or death. Inspect all package contents for completeness and damage. Verify all components are compatible with the cable and mating products. Have all required tools ready and maintain cleanliness throughout the procedure.
- Train and Cut the Cable
Train the UD cable as shown in the documentation to ease future operation. Carefully cut the excess cable squarely at the intended center line of the bushing.
- Prepare Cable and Install Compression Lug
Unwrap and bind the concentric neutral wires 8-1/2 inches back from the cable end. Remove the shield and insulation from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately install the supplied compression lug. Rotate the lug to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe off any excessive inhibitor. Remove the semi-con shield as shown in the template, and bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Bushing Well Contact
Thread the supplied well contact onto the bushing well stud by hand, ensuring not to cross-thread. Use the provided wrench to tighten the contact until the wrench bends, signifying proper torque.
- Assemble the Bushing Tap Housing onto the Cable
Remove the protective cap from the bushing tap and retrieve the socket contact stored inside the housing. Lubricate the cable insulation and the inside of the bushing housing with the supplied lubricant ONLY; do not substitute. Keep the insulation clean and avoid introducing excess grease into the gap between the lug and insulation. Slide the bushing tap onto the cable using a back-and-forth twisting motion, then wipe off any excess grease. Align the bushing with the compression lug hole and assemble the socket contact into the bushing tap, ensuring the socket contact stud passes through the lug hole.
- Mount the Bushing Tap to the Apparatus
Inspect the apparatus bushing well to ensure it is dry and free from contaminants. Lubricate the bushing well interface area of the bushing tap with the supplied or ELASTIMOLD approved lubricant. Place the lubricated bushing tap portion into the apparatus bushing well. Insert the installation tool into the bore of the bushing tap until fully seated. Insert the wrench through the wrench hole of the tool and turn clockwise until the wrench bends, indicating proper assembly torque. Remove the wrench and installation tool.
- Connect the Concentric Neutral
Insert one end of a No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the bushing tap. Twist it tight, taking care not to damage the eye. Twist the neutral wires together and connect them to ground using an appropriate connector.
- Prepare for Mating Product Installation
Thoroughly wipe the bushing tap interface clean of any contaminants. Apply a light, uniform coat of the supplied lubricant, working it thoroughly into the surface. CAUTION: Excess lubricant may prevent a loadbreak elbow from fully seating. Install the mating product (e.g., loadbreak elbow, insulated cap) according to its specific instructions. If not immediately mating, replace the shipping cap with an appropriate HV insulated cap or connector before energizing or submerging the circuit, as the shipping cap is not insulated or watertight.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.