Overview
- 15kV voltage rating for medium voltage applications
- 200 Amp continuous current capability
- Accommodates cable insulation diameters from .575" to .740"
- Includes a test point for voltage verification
- Bi-metal compression lug for #2 stranded wire
Specifications
Amperage Rating | 200 A |
Application | 15 kv, 200 Amp |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Built in cable jacket seal. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point and Jacket Seal |
Voltage Rating | 15 kV |
Width | 8.2 in |
Width | 208.28 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-F5220
25kV, 600 Amp, Deadbreak Elbow, No Sealing Kit, without Test Point, Cable Insulation .640-.820 inches, Bi-Metal Lug, Conductor Size AWG Compressed/Stranded #2 or Compacted/Solid #1 or mm2 Compact 35.
162LRJS-B5210
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #3 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-B5220
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector without Test Point, .635 inch - .905 inch Cable Insulation Diameter, #2 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-B5230
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, Wire Size #1 Stranded or 1/0 Compact/Solid, Bi-Metal Compression Lug
162LRJS-B5240
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-B5230A
200 Amp, 15kV, Loadbreak Elbow with Jacket Seal, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
162LRJS-C5250
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 2/0 Stranded Wire Size, Bi-Metal Compression LugFrequently Asked Questions
What voltage series are available for the elbow?
The enhanced Elastimold 200 amp loadbreak elbow is available in 15 kV and 25 kV series.
Does the product have RUS acceptance?
Yes, the enhanced Elastimold 200 amp loadbreak elbow has Rural Utilities Service (RUS) acceptance from the U.S. Department of Agriculture (USDA).
What material is the pulling eye made from?
The pulling eye is made from robust stainless steel, promoting durable hotstick control.
What certifications does the enhanced elbow have?
The enhanced Elastimold loadbreak elbow is IEEE 386 compliant, ANSI certified, and has Rural Utilities Service (RUS) acceptance from the U.S. Department of Agriculture (USDA).
What safety enhancements are included in the design?
Safety enhancements include improved insulation for 15 kV elbows, rigid probe support, a no-stick interface with Elastimold bushings, a robust stainless-steel pulling eye, and dual grounding eye positions.
What product is enhanced by this document?
This document describes enhancements to the Elastimold 200 amp loadbreak elbow, available in 15 kV and 25 kV series.
What safety enhancements are included in the design?
Safety enhancements include improved insulation for 15 kV elbows, rigid probe support, a no-stick interface with Elastimold bushings, a robust stainless-steel pulling eye, and dual grounding eye positions.
What product is enhanced by this document?
This document describes enhancements to the Elastimold 200 amp loadbreak elbow, available in 15 kV and 25 kV series.
What certifications does the enhanced elbow have?
The enhanced Elastimold loadbreak elbow is IEEE 386 compliant, ANSI certified, and has Rural Utilities Service (RUS) acceptance from the U.S. Department of Agriculture (USDA).
What material is the pulling eye made from?
The pulling eye is made from robust stainless steel, promoting durable hotstick control.
How to Install 161LRJS and 162LRJS Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 161LRJS and 162LRJS Loadbreak Elbow Connectors with Jacket Seal on UD cable, including cable preparation, assembly, and neutral connection. Always ensure all apparatus is de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Hotstick, Wire brush, Crimp tool (refer to chart), Wire strippers, Multimeter (for voltage test)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (supplied), Sealing strips (3), Mastic strips, Vinyl tape, Copper wire (No. 14 AWG / 2.5mm), Appropriate connector (for neutral ground)
- Perform Initial Safety Checks and Part Verification
DANGER: All apparatus must be de-energized during installation or removal of parts. Inspect all parts for damage, rating, and compatibility with mating parts. Check package contents for completeness. Verify proper fit of all components. Thread the probe into the compression lug to check for resistance; replace damaged components if resistance is encountered. Read all instructions before starting and maintain cleanliness. For 162LRJS, lubricate and install the test point cap if not already installed.
- Train Cable and Prepare Neutral Wires
Train the cable to ensure sufficient slack for ease of operation. Provide an extra length of concentric neutral wires or grounding braid wire (24-26 inches beyond the bushing centerline). Remove the outer jacket 7 3/4 to 8 inches back from the bushing centerline. Unwrap the neutral wire back past the bushing centerline. Cut the excess cable squarely at the centerline of the bushing.
- Prepare Cable End with Mastic and Tape
Wrap one strip of mastic, stretching slightly, around the jacket. Bend all neutral wires straight back over the mastic and along the cable, pressing them into the mastic. Wrap a second strip of mastic completely around the outer jacket, overlapping the imbedded neutral wires. Use a third strip if needed to build up the outer diameter. Cover all mastic with vinyl tape.
- Remove Insulation and Install Compression Lug
Remove the insulation shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread the inhibitor. Position the compression lug so the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable.
- Bevel Insulation and Clean Cable
Remove the insulation shield as indicated by the template (6-7/8 inches). Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble Elbow Housing and Probe
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the wrench until the wrench bends.
- Connect Concentric Neutral Wires
Pull the hood over the concentric neutral seal area on the cable by pulling the tabs or rolling the seal down. Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow; twist tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Operate the connection using a fully insulated 'hotstick' type tool. DO NOT OPERATE BY HAND. Consult your company's safe work practices for the required tool length.
- Perform Voltage Test (162LRJS Only)
For 162LRJS connectors, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; it is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device made for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.