Overview
- 30-amp input with NEMA L22-30P plug and 3-meter cord
- 21 C13/C15 outlets + 21 mixed C13/C15/C19/C21 outlets for versatile compatibility
- 2U rack-mount design for space-efficient power distribution
- TAA-compliant for government and enterprise procurement
- Black enclosure optimized for standard 19-inch racks
Specifications
Color | Black |
Current Rating | 30 A |
Frequency Rating, Maximum | 240 V |
Frequency Rating, Minimum | 240 V |
Material | Metal |
Mounting | Vertical |
Nema Rating | NEMA L22-30P-3M |
Phase | 3 |
Series | TAA EL2P MI PDU |
Standard | UL 62368-1, CAN CSA-C22.2 No. 62368-1 EMC: FCC 47 CFR Part 15, Class A, Subpart B. ICES-003 Issue 7 |
Type | PDU |
Width | 2 in |
Width | 50.8 mm |
Package Dimensions (L x W x H) | 70.08 IN x 3 IN x 3 IN |
Package Dimensions (L x W x H) | 178.0032 cm x 7.62 cm x 7.62 cm |
Package Weight (Imperial) | 22.2700 L |
Package Weight (Metric) | 10.1017 kg |

ST4803PDGM
Surge-Trap® Surge Protective Device is a no-fuse surge suppressor. The Surge-Trap is a UL 1449 Third Edition compliant modular style surge protective device that is DIN-rail mountable featuring a fail-safe self-protected design, visual indicator and a small foot print. A remote indicator option provides status to critical control circuit. The Surge-Trap provides advanced overvoltage protection utilizing Mersen's patented TPMOV® technology without additional protection devices. 480 Volts 3P Delta system type without N-G mode, with microswitch .
STP6X12MIG
This TX6A 10Gig Cat 6A STP Patch Cord is a 12-Meter, Int'l Grey cord constructed of 26 AWG, shielded, twisted pair, stranded, CM/LSZH cable and with high-performance modular plugs. Its tangle-free latch prevents snags and ensures a fast release, streamlining moves, adds, and changes. The slender strain relief boot provides easy access in high-density applications. Enabled with RapidID, the product has pre-installed barcodes for simple port mapping using RapidID software.
F62ERLNSNSNM002
OM1 2 fiber, 16mm jacket, patchcord, Riser (OFNR) rated, LC duplex to SC duplex, Std IL
CESUM3-C15
Membrane plate cable entry system offers a good strain relief while maintaining IP/NEMA ingress sealing rating. The CESUM3-C15 is a Rectangular Un-Terminated Cable Entry System, 4.1" (103 mm) Long, with 8 Openings 0.12" (3.0 mm) to 0.31" (8 mm), 3 Openings 0.20" (5.1 mm) to 0.35" (9.0 mm), 4 Openings 0.3" (7.5 mm) to 0.47" (12.0 mm). Color is Black. Standard Package Quantity is 1 PC.Frequently Asked Questions
What is the maximum operating temperature for Panduit PDUs?
Panduit PDUs are built with premium components to withstand up to 140°F (60°C) at full load. Some ES2P series models operate up to 55°C.
Are Panduit intelligent PDUs compatible with Cisco Nexus Dashboard?
Yes, Panduit's intelligent PDUs seamlessly integrate with Cisco Nexus Dashboard software to enhance energy savings and sustainability insights.
What is the benefit of a hot-swappable PDU controller?
Hot-swappable controllers allow complete removal of the network interface module for service or repair without affecting the PDU's outlet status.
Can Universal PDUs adapt to different power requirements?
Yes, Universal PDUs support power requirements from 3.3kW to 27.6kW. You can simply swap the input cord without replacing the entire PDU.
Which PDU series are compatible with SiteCommand Utility software?
The SiteCommand Utility software is compatible with the ES2P and EL2P series of Panduit intelligent PDUs.
What is the maximum daisy chain capacity for Panduit PDUs?
Daisy chain capacity varies by series: ES2P supports up to 16, G6 up to 32, and EL2P up to 64 PDUs.
What is the metering accuracy of Panduit PDUs?
Metering accuracy is ± 2% for ES2P and G6 series PDUs. The EL2P series offers higher accuracy at ± 0.5%.
Do Panduit PDUs offer remote outlet control?
Yes, Monitored Switched and Monitored Switched Per Outlet PDUs offer remote outlet control, including on/off and power cycling capabilities.
What warranty is included with Panduit PDUs?
Panduit PDUs come with a 3-year standard warranty. An extended 5-year warranty is also available, with some EL2P models offering 5 standard + 1 year extended.
How are Panduit PDUs mounted in a rack?
Panduit PDUs offer tool-less mounting for vertical models using buttons and keyhole slots. Mounting buttons, brackets, and hardware are included.
How to Install a Panduit EL2P Power Distribution Unit (PDU)
This guide provides step-by-step instructions for qualified personnel to safely install a Panduit EL2P Rack Power Distribution Unit (PDU) into a datacenter rack or cabinet, covering mounting, grounding, and power connection procedures for both vertical and horizontal models.
Estimated time: 1h
Tools needed:
#2 Phillips screwdriver, T10 Torx screwdriver, T20 Torx screwdriver, 2.5mm hex key Allen wrench
Supplies needed:
Mounting hardware (screws, cage nuts, brackets as applicable), Ground bonding cable, Star washer
- Review Safety Information and Prepare
Before beginning, carefully read all safety information in the PDU manual. Ensure the installation environment is temperature and humidity controlled, free of conductive contaminants. Verify that all circuit breakers are in the off position before connecting input power. Confirm that the PDU is intended for Information Technology Equipment (ITE) loads with linear/Power Factor Corrected (PFC) input current. Ensure you have a reliable grounded connection available. WARNING: This PDU contains LETHAL VOLTAGES. Installation must be performed by individuals knowledgeable about AC power products.
- Mount the PDU in the Rack
Secure the PDU within the datacenter rack. For vertical PDUs, insert the pre-installed mounting buttons into the keyhole slots on the rack's PDU mounting bracket and tighten with a #2 Phillips screwdriver to 3.0Nm. For horizontal 1U/2U PDUs, install cage nuts at the desired U-locations on the RETMA rails. Then, attach the PDU's mounting bracket ears to the rails using screws. For high-power horizontal PDUs, also secure front mounting brackets to the PDU chassis with a 2.5mm hex key Allen wrench.
- Ground the PDU Chassis
Connect a ground bonding cable from the external ground bonding point on the PDU chassis to a known earthed reference terminal in the building or the rack's grounding strip/bus bar. Ensure conductor sizes meet National or Local Electrical Codes (e.g., NEC Table 250.122). This provides supplementary Earth bonding to the rack metalwork. HIGH LEAKAGE CURRENT. Ensure a reliable grounded (earthed) connection.
- Connect the PDU to a Power Source
Ensure the feed circuit breaker for the power source is OFF. Verify all circuit breakers on the PDU are set to ON. Connect the PDU's input power cord to an appropriately rated, grounded branch circuit, adhering to all local and national electrical codes. Refer to the compliance label on the PDU for input ratings. Once connected, turn the feed circuit breaker ON and wait for the operating system to load.
- Rotate or Replace Network Controller (Optional)
If desired, rotate or replace the network control module. Use a T10 Torx screwdriver to remove the two retaining screws. If rotating, disconnect the ribbon cable to prevent damage, rotate the controller, and carefully reconnect the ribbon cable. If replacing, disconnect the old ribbon cable, connect the new ribbon cable to the new controller, and mate it to the PDU chassis. Reinstall and torque the two screws to 2.2–3.1 lbf-in [0.25–0.35 N-M]. WARNING: Overtightening may cause metal deformation.
Frequently Asked Questions about Panduit
What environmental ratings do Panduit products have?
Panduit products feature comprehensive environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13; CSA Type 1, 2, 3, 4, 4X, 12, and 13; and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. They meet IEC 60529 IP66 rating, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments, with operating temperatures ranging from -40°C to 130°C.
What certifications and standards do Panduit products comply with?
Panduit products are certified to multiple critical industry standards, including UL (Underwriters Laboratories) in the USA and Canada, CSA (Canadian Standard Association), EN IEC 61386, LVD 2006/G5/EC, and ARRA standards. Our products meet rigorous certifications for electrical safety, environmental compliance (WEEE and RoHS), and are designed to perform in extreme temperatures ranging from -55°C to 105°C, making them suitable for demanding industrial environments.
What industries and applications are Panduit products used for?
Panduit products are engineered for critical applications across multiple industries, including commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety-critical environments. Their solutions span electrical infrastructure, wire management, cable ties, power connectors, and safety systems designed to withstand extreme conditions like high vibration, temperature variations, UV exposure, and corrosive agents. Key industries include solar and wind energy, aerospace, heavy trucking, military, commercial transportation, and industrial manufacturing.
What are the main product lines offered by Panduit?
Panduit offers a comprehensive range of electrical infrastructure products including power connectors, cable ties, grounding connectors, identification products, safety solutions, terminals, cable cleats, wiring duct, and cable tie accessories. These products are engineered for industrial environments across multiple sectors like commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety applications.
What are the key features of Panduit products?
Panduit products are engineered for robust performance in heavy-duty industrial environments, featuring a comprehensive range of solutions including cable ties, power connectors, terminals, and identification products. Key features include proven quality performance, subject matter expertise, and customer-driven innovation across multiple industrial sectors such as commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety applications. The product line is designed to maximize productivity, reliability, and safety while meeting stringent industry standards.
What is Panduit's warranty policy?
Panduit provides a comprehensive Limited Product Warranty that can be fully reviewed on their official website at www.panduit.com/warranty. All Panduit products are subject to the terms, conditions, and limitations of this current warranty. Customers are advised to review the specific warranty details for their particular product, as Panduit requires buyers to determine product suitability for their intended use and assumes all associated risks.
What technical support does Panduit offer?
Panduit offers comprehensive technical support through their dedicated customer service team, accessible via phone at 1-800-777-3300. They provide expert assistance for their full range of industrial infrastructure products, including cable ties, power connectors, terminals, and identification solutions. Customers can also access additional technical resources and product information through their website at www.panduit.com.
What accessories are available for Panduit products?
Panduit offers a wide range of accessories across multiple product lines, including cable ties, cable tie accessories, cable tie tools, identification products, cable cleats, grounding connectors, and VeriSafe accessories like the VeriSafe Network Module and Insulation Piercing Connectors. For a comprehensive view of all available accessories, customers are recommended to visit www.panduit.com for the full product catalog.
How are Panduit products typically installed?
Panduit products are engineered for comprehensive installation across industrial environments, utilizing specialized tools and techniques for precise mounting. Installation methods vary by product line - from cable ties and power connectors to terminals and identification solutions - but all are designed for robust performance in heavy-duty settings. Technicians typically use Panduit's dedicated installation tools and follow manufacturer guidelines available at www.panduit.com to ensure proper fitting and maximum infrastructure reliability.